a gas pressure regulator when installed out doors should have the vent
opening pointing down stream
when installing an appliance regulator and the vent opening is completely blocked this will cause the regulator to
remain permanently open
a two stage propane regulator would typically be set for
first stage 10 psig second stage 11’ w.c
when the inlet supply pressure to line pressure exceeds .5 psig it shall
be of a positive shut off type
the leak limiting device should be installed
vertically
if a 5psig line pressure regulator has a 3/4 vent tapping and the ventline must be 65 feet what must be done
use 1” pipe for the entire lengh-make the change at the vent tapping
too mant fittings on a vent line could cause
the regulator to hunt
the purpose of a pilot tube in a regulator is
keep downstream pressure closer to set point during flow conditions
if a 5 psig line regulator ( with internal relief) was installed in a boiler room, which of the following would be required
the vent must be piped to a safe location outdoors
a line pressure regulator operating at 2psig or less shall be exampt from the requirments of clause 5.2.1.5 B when equipped with
a vent leaking limiiting system