Refrigeration excellance Flashcards
- In a dry type (direct expansion) evaporator, liquid refrigerant must boil away as close to the end of the coil as possible in order to:
A. Operate at high-efficiency
- The difference between the temperature of the refrigerant boiling in the evaporator and the temperature at the evaporator outlet is known as
A. Evaporator superheat
- An expansion device that is stuck open will cause
D. A flooded evaporator
- When measuring evaporator superheat on a commercial system that has a long suction line, the pressure reading should be taken at the
A. Compressor inlet
- Superheat measurements are best taken
D. With the system operating at design conditions
- A technician is checking the superheat on a multi circuit evaporator and finds one of the circuits has a superheat that is higher than the others. This could be caused by
D. A blocked distributor
- A TXV with an external equalizer is used on
A. Evaporators with a high pressure drop
- Dry type evaporators operate most efficiently with the superheat setting of approximately
A. 8°F to 12°F
- An evaporator used to chill liquids is operating within normal superheat setting. But the system is not cooling the product properly. Which of the following is most likely the cause?
A. Overcharge of refrigerant
- What time interval is required between each superheat adjustment?
B. About 10 to 15 minutes
- A low temperature evaporator used for cooling space or product refrigeration
D. Must be defrosted periodically
- Some special applications use a flooded evaporator (operated full of refrigerant) in order to maintain the proper level of liquid refrigerant, a ______ type devices used.
D. Low side float
- A properly functioning condenser will first
D. De-superheat, then sub-cool
- The effect of an inefficient water cooled condenser will
A. Act the same as an air cooled condenser
- The refrigerant condensing temperature in a water cooled condenser is normally about _____ higher than the leaving water.
B. 10°F
- The refrigerant and an air cooled condenser will normally contends at approximately _____ higher temperature than the air passing over it.
B. 30°F
- Workable head pressure during periods of low ambient temperature can be achieved by using
D. Fan cycle control
- Cooling towers that pass air over water to remove system heat are limited in capacity by
A. Outside air wetbulb temperature
- Parallel compressors often referred to as a rack system may use
A. A common suction, but not a common discharge header
- The major difference between a cooling tower and an evaporative condenser is
D. The refrigerant is indirectly cooled in the cooling tower
- Multiple compressors provide
C. Capacity control
- A dirty evaporator and subsequent low evaporator pressures will cause
B. Low compression ratios
- The thermostatic expansion valve (TEV) maintains a constant _______ in the evaporator.
D. Superheat
- What type of ice is made with the commercial icemaker that uses a gear motor and auger?
B. Shaved ice
- Some capillary tube systems take advantage of heat exchange by soldering the capillary tube to the suction line. In order to obtain the correct superheat reading, it must be taken
A. After the capillary tube suction line heat exchanger
- A ______ is usually required for ultra low temperature applications.
D. Cascade system
- A hot gas defrost cycle can be initiated by a
A. Timer
- When the defrost cycle is terminated, the evaporator fans will
D. Delay coming on
- An off-cycle defrost method is often used on evaporators operating at a minimum of
C. 35°F