Refrigerant 2 Flashcards
- What is the minimum allowable refrigerant velocity in a reduced discharge riser?
1000-1500 fpm
What is the function of the “p” trap in vapour risers
Assists oil movement
What is the correct method to transfer HFC 404A for a refrigeration system?
. Removed as a liquid from cylinder and flashed into the system using a refrigeration manifold
When is a crankcase pressure regulator set up?
After defrost cycle has terminated and compressor has started
What pressure shall be used to calculate the superheat setting of the evaporator when a TXV is used as the metering device?
b. Evaporator outlet pressure near the sensing bulb
Defrost may be initiated by:
Time, temperature or pressure
Defrost may be terminated by:
Time, temperature or pressure
Calculate the total “u” factor of a freezer wall constructed of the following: 6” of polyurethane; having an “R” value of 6.25 per inch
8” concrete; having a “C” factor of 0.58 Btu/(hr)(ft2)(°F)
5/8” fire rated gypsum board; having a “u” factor of 3.2 Btu/(hr)(ft2)(°F).
.0253 Btu/(hr)(ft2)(°F).
What heat load value is unique when cooling fresh fruit and vegetables?
Heat of respiration
- The oil pump in a large semi hermetic compressor is located where?
on the crankshaft end
What type of TEV bulb charge is required on a large tonnage AC rooftop unit to reduce compressor overloading at startup under high load conditions?
Vapour charged
Off Cycle Defrost for a single circuit system, involves:
condensing unit off and evaporator fan on
Electric Defrost for a single circuit system, involves:
condensing unit off and evaporator fan off
Hot Gas Defrost for a multi circuit system, involves:
condensing unit on and evaporator fan off
Where is the Evaporator Pressure Regulator located
Outlet of the higher temperature evaporator
What type of oil used in stationary refrigeration and air conditioning systems will more readily absorb moisture when the container is opened?
Polyolester oil
walls of a building are 20’ high and 200’ long. The drywall has an R value of 0.5, the insulation is R10, the outside polystyrene board is R4 and the outside finish is R0.5. The indoor temperature is 72ºF and the outdoor design temp is -5ºF. Calculate the heat loss through the wall.
20,533 Btu/hr
a receiver is located in a location that may become colder than the evaporator
Thermostatically controlled heater elements are attached to the surface area of the receiver shell and shell is insulated
What is the effect on a system when the liquid line solenoid valve is installed backwards?
System won’t pump down
Where should the liquid line solenoid valve be installed?
. In the liquid line after the liquid line filter drier
What is the result when the TXV loses the charge in the sensing
Increase in evaporator superheat
Where should the TXV bulb be located for best sensing results?
. Evaporator outlet and placed to avoid effects of oil temperature
What is the correct mounting procedure of the thermostatic element bulb to ensure proper control of the TEV?
Clean evaporator outlet tubing after suction header, secure with similar metal clamp and insulate
- What is the purpose of the fan delay after a defrost cycle?
Allow moisture to drip off and the remainder to solidify on the coil
What is the term given to the device within the time clock that will cause the defrost cycle to end before its time
Defrost termination solenoid
What is the amount of sub cooling provided within a standard receiver?
0F
When will the king valve on a receiver be completely front seated?
When pumping refrigerant out of the liquid line
What happens to a reciprocating compressor when the suction service valve is completely front seated?
Compressor crankcase pressure should draw into a vacuum if the low pressure switch cut out is set low enough
The manifold gauge that shall be used to measure suction pressure is called
Compound guage
- What is the unit of measure for velocity?
Fpm
What two temperatures were measured by the electronic temperature control in the refrigeration lab
Box and coil
What type of input is used by the JCI MR4 and/or Omnistat for defrost termination?
Variable / analog
What switching action is used by a three-phase compressor j?
Tpst
What is the function of the low pressure switch used in the refrigeration lab to control the compressor
Recycling Pump down
What was the purpose of the delay on make timer in a recycling pump down control
Minimum off cycle for the compressor
What is the control voltage used in the refrigeration lab for the load switching components (relay and contactor)?
208vac
What voltage is required to power the Omni stat in this lab application
120vac
How many contactor poles were required for the single phase evaporator fan control in the low temp coil
2
What device is connected to the X & N terminal strip on the evaporator
Defrost termination thermostat
How many poles were required to disconnect the single phase defrost heater in the refrigerated box safely
2
How should all electrical loads be isolated when not in use for extended periods of time?
b. Tagged and locked out
Which is the pressure drop value of venturi and orifice type distributors
15 psi venturi and 25 to 35 psi orifice
Which TXV port design is intended for operation with floating head pressure
Balanced port
Under what condition would the refrigeration lab compressor lock out and not automatically restart
High pressure
Which force will close the compressor contactor?
Magnetic
What is illustrated by the pictorial electrical schematic
Location of electrical components
What is the function of a ladder electrical schematic
Sequence of operation
What is the purpose of the suction line trap at the base of a riser
Oil return
What is the term given to the device that held the pipe hanger to the beam
Beam clamp
Why was the electrical current draw higher on two of the lines feeding the compressor in the refrigeration lab
Single and three phase loads
- What tool(s) are required to set up a CRO?
Allen wrench, compound gauge & amp meter
Where is the refrigerant heat exchanger installed to improve sub cooling
Suction and Liquid
Which is the function of the suction /liquid heat exchanger in the refrigeration piping system
Sub cool refrigerant in liquid line
Superheat refrigerant in suction line
Increase NRE
The direct expansion shell and tube evaporator, water circuit can be cleaned by
Chemical cleaning
What happens to the refrigerant within the condenser
. De-superheated, condensed and sub cooled
Condensers must reject the heat from ____________when open drive compressors are used ?
Evaporator, suction line and compression