The synthetic lubricant presently used with ternary blends containing HCFCs is:
Alkylbenzene
Which is NOT true of recycling and recovery equipment manufactured after November 15, 1993?
It must have an oil separator.
Oil separators are NOT required.
Charging liquid refrigerant into a refrigeration system under 29 inches Hg vacuum can cause:
System water to freeze
R-22 is an ______ refrigerant
HCFC
R-12 is a _____ refrigerant.
CFC
R-123 is a ___ ______ refrigerant under EPA regulations for recycling refrigerant.
Low pressure
When working with solvents, chemicals, or refrigerants, a technician should review the:
Material safety data sheets
Under what code group of ASHRAE Standard 34 does R-123 fall?
B1
When leak testing a low-pressure centrifugal with nitrogen, what is the maximum test pressure?
10 psig
What else is NOT true of refrigerant recycling and recovery equipment manufactured after November 15, 1993?
It must be able to handle more than one refrigerant.
Refrigerants should NEVER be mixed!
Identify the pressure corresponding to 32°F for R-123
20 inches Hg vacuum
Each chlorine atom in the stratosphere can destroy ______ ozone molecules
100,000
How do you determine when enough vapor has entered the refrigeration system before you charge refrigerant liquid?
Refrigerant saturation temperature increases to 36°F
Recovery equipment that relies upon the Compressor in the appliance and/or the pressure of the refrigerant in the appliance would be considered:
System-dependent
Excessive running of a purge system on a low-pressure chiller generally indicates what condition?
The system is leaking
It will be illegal to vent substitutes for CFCs and HCFCs after:
November 1995
The oils that will be employed with most of the HFC-134a refrigeration applications are:
Esters
Liquid charging of an R-12 refrigeration system with risk of freezing is begun with vapor from a vacuum level to a pressure of approximately:
33 psig
The system dependent (passive) recovery process:
Recovers refrigerant in a non-pressurized container
Leak testing a low-pressure refrigeration system with the nitrogen in excess of 10 psig could cause what to fail?
Rupture disc
R-11 at 14.7 psia will boil at approximately:
74.5°F
When a system trace gas becomes absolutely necessary, which of the available refrigerants should be used to identify a leak?
HCFC-22
High head pressure could be an indication of:
non-condensables collecting in the condenser
Frost build up on the suction side of the compressor can
indicate __________.
too little superheat in refrigerant vapor
Which condition(s) can cause excessive pressure
conditions on the high side of a self-contained (active)
recovery device?
when the recovery tank inlet valve has not been
opened, and …
when there is excessive air in the recovery tank
When using recovery and recycling equipment
manufactured BEFORE November 15, 1993, technicians
must evacuate an appliance containing 10 pounds of
CFC-500 to what level before disposing of the
appliance?
4 inches of Hg vacuum.
Recovery equipment used during maintenance, service or repair of small appliances must be certified by an EPA-
approved laboratory if manufactured after:
November 15, 1993.
EPA regulations include which of the following in the
definition of a “small appliance”?
products manufactured, charged and hermetically
sealed in a factory, AND
products having 5 pounds or less of refrigerant
What should be done to reduce refrigerant loss from a
purge unit on a CFC-11 chiller?
leak test and repair the chiller
A heater used on a recovery vessel aids in the faster
transfer of ______ from the chiller during recovery.
vapor
On a sealed system with an operating compressor that
has a completely restricted capillary tube, how many
access valves are needed to evacuate the refrigerant?
Only one access valve, on the high of the system.