Reaction Subsystem- Major Equipment, How it works, Controlling, & Shut Down Flashcards
What are the 3 subsystems of the 634 HDS?
Reaction Subsystem, Stipper Subsystem, Hydrogen Compression Subsystem
Overall, what happens in the Reaction Subsystem?
undesirable sulfure and nitrogen compounds in the feed stream are converted to hydrogen sulfide and ammonia. Olefins and aromatics in the feed are saturated with hydrogen.
Why are the feed filters important?
They remove solids from the feed stream which could foul the catalyst beds in the reactor.
What does an increasing differential pressure across the in-service filter indicate?
The filter media is plugging and must be replaced. If the differential pressure is excessive, the stand-by filter is placed in service and the in-service filter is taken out of service
The natural gas blanket on the Feed Surge Drum Prevents _________ from entering the drum and provides sufficient suction pressure for the Reactor Fresh Feed Pumps.
Oxygen
The Target Outlet temperature for the Reactor Feed heater (F1) is ________ F
665 F
What is the normal control mode for the Feed Surge Drum pressure (pc0001)?
Local
What can happen if the fresh feed flow (as indicated by FT0003 A/B/C) drops below 1070 BPH?
Low- Low (2oo3 voting) The SIS interlock is activated which initiates a shutdown of the Reactor feed heater.
The potential effects of a low combined hydrogen flow to the fresh feed (FI0016) are ________ ______ and insufficient hydrogen for desired ______, resulting in off-spec product.
catalyst deactivation, reactions
The potential effects of a high reactor outlet temperature are premature _________ of the catalyst and loss of _________ of the recycle hydrogen stream.
deactivation, purity
What is the high pressure alarm setpoint on the unit pressure controller (PC0007) _________ -psig?
907 psig
A low hot flash drum level can allow high-pressure gas to flow to the Product Stripper resulting in damage to the tower’s _________ and the possibility of lifting PSVs.
tray’s
The potential effect of a high Hot Flash Vapor Air Coolers outlet temperature is a decrease in the __________ of the recycle Hydrogen
purity
The Reactor Feed Heater high coil pressure alarm activates at _________-psig.
980 psig
The SIS will trip the Reactor Feed Heater on a low-low fuel gas pressure of _______
2%
What happens if the SIS detects a low current of 20 amps to the Forced Draft Fan motor?
After a 30 decond delay, the SIS interlock is activated to switch the heater to natural draft.
What are the process variables on the Reactor Feed Heater that are equipped with triple redundant instrumentation.
Feed flow (FT3A/B/C), Hydrogen flow (FT16A/B/C), Fuel gas pressure (PT5134A/B/C), Furnace pressure (PT5131A/B/C)
If the SIS initiates a trip of the heater due to a high or low furnace pressure, the heater is switched to _________ ________ mode prior to the actual trip.
natural draft
What action does teh DCS take if the SIS trips the Reactor Feed Heater due to either Low Feed flow or Low Hydrogen Flow?
The DCS will automatically override the signal from termperature controller TC1 and place teh fuel gas pressure controller (PC5134) in manual with a minimum fire output of 10% to prevent coking of the heater tubes.
If the SIS automatically switches the Reactor Feed Heater from Balanced draft to Natural Draft, what actions must occur to prevent an eventual complete trip of the heater?
Within 30 seconds of trip to natural draft, both transmitters on the stack damper and forced draft air door much show >50% open to avoid an SIS trip of the heater. After 30 minutes, one transmitter on each damper must indicate >30% open to avoid a heater trip.
What are the three circumstances under which the Reactor Feed Heater SIS can be bypassed?
Startup, Maintenance, and Emergency
The ___________ use fiber filter elements to remove particulates from the gas oil. The filtered feed exits to the feed surge drum
Feed Filters 634 D1001/D0006B
The ____________ is a holding tank for feed to the unit. It provides surge capacity to operate for 30 mins without receiving feed. It also serves as a reservoir to provide steady feed flow to the reactor fresh feed pumps.
Feed Surge Drum 634D0001
The ____________ is an electric motor-drivin pump. The _____________ is a turbine driven pump that uses 550-psig steam to drive teh turbine. Medium pressure steam (125-psig) exhausts from the turbine. The pumps increase the pressure of the feed stream to 730-psig. The increased pressure allows the feed stream to join the combined hydrogen stream
Reactor fresh feed pumps 634P0001