Radiation Monitoring System Flashcards
what are the three Rad monitoring subsystems?
SRMS Safety related mon sys
PAMS post accident mon sys
DCUs digital radiation display and control units
What do SRMS do?
provides an actuation signal for the ESF isolation systems tech spec related monitoring and control functions only class Q radmonitors
What does PAMS do?
long term post accident monitoring
monitors condenser effluent and plant vent
notifies operators of abnormal radiation in CTMT, MS, CR areas
What does RU-1 actuate?
isolation valves at the penetration auto shutto isolate the monitor from pressure and temperature transients following a LOCA
Valves close on CIAS
what do RU-29 and 30 monitor and actuate?
monitors noble gas concentrations in the CR air intake
hi-hi alarm activating the CR essential filtration units
what do RU-37 and 38 monitor and actuate?
monitors the PAP ducts for radioactivity that could dose the public
inititates CTMT building purge supply and exhaust isolation, also CREFAS A & B
what does RU-145 monitor and actuate?
low range monitoring of the fuel building ventilation
isolates the normal fuel building ventilation and initiates the essential vent system
HF A & B
HJ A & B
what does RU-31 monitor and actuate?
monitors the fuel pool area
actuates on the hi hi alarm
isolates the FB vent and initiates a FBEVAS
what does RU-141A&B monitor and actuate?
monitors gases from the vac pumps and GS condenser resulting from primary to secondary leak
initiates operation of the air removal system post filter system A.
B provides alarm function only
what does RU-7 monitor and actuate?
- AS cond returning from the BAC, LRS evap and gas stripper is monitored before leaving the receiver tank.
- caused by radioactivity leak into a component or improper operation
- initiates an auto diversion of the condensate to the LRS system
what does RU-12 monitor and actuate?
- monitors gross beta radioactivity in the decay tank discharge header
- high alarm initiates isolation of the decay tank discharge header
how frequently are the radmonitors calibrated?
at least every 18 months
where will a high alarm annunciate?
CR, RMS/effluent office, chemistry count room.