Quiz Flashcards
CH 00
Building Height
the number of storeys contained between the r____ and the f____ of the first storey.
the number of storeys contained between the roof and the floor of the first storey.
지붕과 1층 바닥 사이에 포함된 층의 수.
CH 00
*According to Table 9.23.16.2.A,
what is the minimum thickness of exterior type plywood sheathing supported on wall studs spaced at 406 mm o/c?
Answer: 6 mm
Reference:
9.23.16.2.(1),
Table 9.23.16.2.A
CH 00
If wood shingles were being installed and fastened directly to the sheathing
(not the studs or blocking),
what would this do to the minimum thickness of plywood sheathing determined from the Table?
목재 외장재를 설치하고 외장재에 직접 고정시
(스터드 또는 차단재가 아닌)
표에서 결정한 합판 외장재의 최소 두께는 어떻게 됩니까?
Answer:
Increase the thickness from 6 mm to 7.5 mm
Reference:
9.27.5.1.(3).(b)
attachment of cladding
CH 00
Building Area
greatest h________ area of a building above grade
-within the outside surface of e________ walls, or
-within the outside surface of exterior walls and the centre line of f________.
greatest horizontal area of a building above grade
-within the outside surface of exterior walls, or
-within the outside surface of exterior walls and the centre line of firewalls.
CH 00
Major Occupancies
principal occupancy for which a building or part of a building is used or intended to be used,
and is deemed to include the subsidiary occupancies that are an integral part of the principal occupancy
건물 또는 건물의 일부가 사용되거나 사용될 예정인 주요 점유를 의미하며,
주요 점유의 필수적인 부분인 보조 점유를 포함하는 것으로 간주됨
Group A, Division 1 Group C
Group A, Division 2 Group D
Group A, Division 3 Group E
Group A, Division 4 Group F, Division 1
Group B, Division 1 Group F, Division 2
Group B, Division 2 Group F, Division 3
Group B, Division 3
Major Occupancies
principal occupancy for which a building or part of a building is used or intended to be used, and is deemed to include the subsidiary occupancies that are an integral part of the principal occupancy
CH 00
Which of the following is a Part 9 building?
-A 550 m² one storey seniors care facility
-A 300 m² three storey office building
-A 650 m² two storey warehouse
-A 1250 m² single family dwelling
Answer:
b)
Reference:
Div. A. 1.1.2.4.(1)
CH 00
Which of the following is NOT a Part 9 building?
-A 500 m² two storey row house with a basement
-A 600 m² three storey office building
-A 480 m² one storey warehouse
-A 500 m² one storey movie theatre
Answer:
d)
Reference:
Div. A. 1.1.2.4.(1)
CH 00*
If wood shingles were being installed and fastened directly to the sheathing (not the studs or blocking),
what would this do to the minimum thickness of plywood sheathing determined from the Table?
목재 외장재를 설치하고 sheathing에 직접 고정시
(not studs or blocking)
표에서 결정한 합판 외장재의 최소 두께는 어떻게 됩니까?
Answer:
6 mm
Reference:
9.23.16.2.(1),
Table 9.23.16.2.A
CH 00
Strudture of Building Code
-S—–y (4)
-H—-h (7)
-A———–y (2)
-F—, St——-, W—–, S—— Protection of buildings (5)
-R——– Conservation (2)
-Envitonmental I——-y (0)
-Conservation of B——-s (0)
Strudture of Building Code
-Safety (4)
-Health (7)
-Accessibility (2)
-Fire, Structure, Water & Sewage Protection of buildings (5)
-Resource Conservation (2)
-Envitonmental Integrity (0)
-Conservation of Buildings (0)
CH 00
Structure of Building Code
-Safety (4)
– f— safety
– st——– safety
– s—– in use
– resistance to unwanted entry
CH 00
Structure of Building Code
-Safety (4)
–fire safety
–structural safety
–safety in use
–resistance to unwanted entry
CH 00
Structure of Building Code
-Health (7)
– In—- conditions
–Sanit—–
–No— protection
–Vib—— & def——- limitation
–haz—— substances containment
–Priv—
–view to the outdoor
CH 00
Structure of Building Code
-Health (7)
–Indoor conditions
–Sanitation
–Noise protection
–Vibration & deflection limitation
–hazardous substances containment
–Privacy
–view to the outdoor
CH 00
Structure of Building Code
-Accessibility (2)
–Barrier-f— p— of Travel
–Barrier-free f———
CH 00
Structure of Building Code
-Accessibility (2)
–Barrier-free path of Travel
–Barrier-free facilities
CH 00
Structure of Building Code
-Fire, Structure, Water & Sewage Protection of buildings (5)
–Fire p——— of building
–structural s———- of building
–protection of adjacent buildings from f—
–protection of adjacent buildings from structural d—–
–w—- & se—- protection of building & facilities
CH 00
Structure of Building Code
-Fire, Structure, Water & Sewage Protection of buildings (5)
–Fire protection of building
–structural sufficiency of building
–protection of adjacent buildings from fire
–protection of adjacent buildings from structural damage
–water & sewage protection of building & facilities
CH 00
Structure of Building Code
-Resource Conservation
–W—- Conservation
–En—- Conservation
-Env———- integrity
-Con——— of Building
CH 00
Structure of Building Code
-Resource Conservation
–Water Conservation
–Energy Conservation
-Environmental integrity
-Conservation of Building
CH 01
Authority for the establishment of building codes,
along with their administration and enforcement,
is found in the
Building Code Act (BCA)
Section 3.?
Section 3.?
Section 7.?
CH 01
Authority for the establishment of building codes,
along with their administration and enforcement,
is found in the
Building Code Act (BCA)
Section 3.1
Section 3.2
Section 7.1
CH 01
1.1
List the necessary categories of qualifications that are required by the designer responsible for the design of 3 storey,
599 m2 building to be used as a house to be constructed in Bradford West Gwillimbury, Ontario.
H—–
P——- house
HV– house
Ge—– Legal
On-S— se—-
Reference:
15.11 (5) Building Code Act,
3.5.2.1.(1) Div. C
Answer:
House;
Plumbing House;
HVAC House;
General Legal;
On-site Sewage.
Reference:
15.11 (5) Building Code Act,
3.5.2.1.(1) Div. C
CH 01
Role of inspectors
exercise their p—- + carry out d—–
related to
reviewing plans + inspecting construction
including (maintenance inspections, + issuing orders).
검사관의 역할은
**을 행사하고
유지 보수 ** 및 명령 발급을 포함하여
** 검토 및 공사 **와 관련된 업무를 수행하는 것입니다.
CH 01
Role of inspectors
exercise their powers + carry out duties
related to
reviewing plans + inspecting construction
including (maintenance inspections, + issuing orders).
검사관의 역할은
권한을 행사하고
유지 보수 검사 및 명령 발행을 포함하여
계획 검토 및 공사 검사와 관련된 업무를 수행하는 것입니다.
CH 01
Designers’ role is
to provide designs in accordance with the Act and the Code,
including detailed documentation which will allow the design to be reviewed to ensure compliance with the regulation and for construction to proceed in accordance with the design.
설계자의 역할은
**을 준수하고
설계에 따라 **을 진행할 수 있도록
설계를 검토할 수 있는 세부 문서를 포함하여
법률 및 강령에 따라
**를 제공하는 것입니다.
CH 01
Designers’ role is
to provide designs in accordance with the Act and the Code,
including detailed documentation which will allow the design to be reviewed to ensure compliance with the regulation and for construction to proceed in accordance with the design.
설계자의 역할은
규정을 준수하고
설계에 따라 시공을 진행할 수 있도록
설계를 검토할 수 있는 세부 문서를 포함하여
법률 및 강령에 따라
설계를 제공하는 것입니다.
CH 01
Processing a Building Permit Application
It must be determined whether the proposed construction complies with
–provisions of z—– by-laws,
–other applicable laws and ag——–,
–Building Code.
제안된 건축물이 아래를 따르는지 결정해야 합니다
–구역 설정 조례,
–기타 관련 법률 및 계약,
–건축법의 조항을 준수.
Builder submit (1~4) to municipality.
1 pl___,
2 sp__________,
3 dra_____,
4 sch______
건축업자는 제안된 건물의 계획, 사양, 도면 및 일람표를 지방 자치 단체에 제출합니다.
CH 01
Processing a Building Permit Application
It must be determined whether the proposed construction complies with
–provisions of zoning by-laws,
–other applicable laws and agreements,
–Building Code.
제안된 건축물이 아래를 따르는지 결정해야 합니다
–구역 설정 조례,
–기타 관련 법률 및 계약,
–건축법의 조항을 준수.
Builder submit (1~4) to municipality.
1 plans,
2 specifications,
3 drawings,
4 schedules
건축업자는 제안된 건물의 계획, 사양, 도면 및 일정을 지방 자치 단체에 제출합니다.
CH 01
Municipal building by-laws require that
all plan documents & drawings
be submitted electronically or in duplicate.
시립 건축 조례에 따라
모든 계획 문서와 도면을
** or **으로 제출해야 합니다.
documents must be attached to
–processed plans:
–A copy of **** documents
–Minister’s Rulings, + authorizations from **,
–notice regarding mandatory & additional inspections
–procedure for requesting inspections
-도면
-허가 문서 사본
-**의 판결 + 건축 자재 평가위원회의 승인
-의무 및 추가 **에 관한 통지
-검사 요청 절차
CH 01
Municipal building by-laws require that
all plan documents and drawings
be submitted electronically or in duplicate.
시립 건축 조례에 따라
모든 계획 문서와 도면을
전자 or 이중으로 제출해야 합니다.
documents must be attached to
–processed plans:
–A copy of permit documents
–Minister’s Rulings, + authorizations from BMEC,
–notice regarding mandatory & additional inspections
–procedure for requesting inspections
도면
허가 문서 사본
장관의 판결 + 건축 자재 평가위원회의 승인
의무 및 추가 검사에 관한 통지
검사 요청 절차
CH 01
Required Drawings + Documentation
01- 대지 지형도
02- 지질조사보고서
03- 평면도:
—지하
—1층
—2층
—3층, etc.
04- 지붕 도면
05- 트러스 레이아웃
06- 입면
07- 단면 (Wall section)
08- 상세도
09- 기계식 환풍 요약본
10- Heat Loss/ gain 계산서
11- 덕트 디자인
12- 에너지효율 설계 양식
CH 01
Required Drawings + Documentation
01-Site grading plan
02-Subsurface investigation report
03-Floor plans:
—Basement
—First floor
—Second floor
—Third floor, etc.
04-Roof plan
05-Truss layout
06-Elevations
07-Cross-section (Wall section)
08-Detail drawings
09-Mechanical Ventilation Summary
10-Heat Loss/Heat gain calculations
11-Duct design
12-Energy Efficiency Design form
CH 01
Plans Examination Checklist
01 Design of R—- & Spaces
02 Performance of W——, D—-, S——–
03 Construction of S—-, G—– & H——–
04 Means of Eg—-
05 F— Protection & S—- Control
06 F——- & Foundations Design
07 Fra—-, Structural, Interior Finishes
08 Cla—– & Building Envelope
09 Pl—– & El——– Facilities
CH 01
Plans Examination Checklist
01 Design of Rooms & Spaces
02 Performance of Windows, Doors, Skylights
03 Construction of Stairs, Guards & Handrails
04 Means of Egress
05 Fire Protection & Sound Control
06 Footings & Foundations Design
07 Framing, Structural, Interior Finishes
08 Cladding & Building Envelope
09 Plumbing & Electrical Facilities
2.1: Combination Rooms ⇒ 9.5.1.4*
Consider floor area located in a single storey dwelling unit,
which is designed to be used as a bedroom and a living room.
If combined area of floor space is equal to 20m²,
what is the minimum required area for the bedroom?
13.5 m²
7 m²
4.2 m²
4.2 m² with direct passage provided btw 2 areas.
2.1: Combination Rooms ⇒ 9.5.1.4
Consider floor area located in a single storey dwelling unit,
which is designed to be used as a bedroom and a living room.
If combined area of floor space is equal to 20m²,
what is the minimum required area for the bedroom?
13.5 m²
7 m²
4.2 m²
4.2 m² with direct passage provided btw 2 areas.
Answer: d)
Ref:
9.5.7.3. (1) areas of combination bedrooms
집에서 다른 공간과 결합된 침실의 면적은 4.2m² 이상.
9.5.1.4. (2) combination rooms
dependent 영역이 침실인 경우,
두 영역 사이에 직접 통로가 제공되어야함
9.5.1.4. Combination Rooms
(1) 영역 사이의 오프닝이 3m² or 종속 영역 측면에서 측정한 벽의 40% 이상 중 큰 영역을 차지하는 경우,
둘 이상의 영역을 combination room 으로 간주.
(2) 종속 영역이 침실인 경우,
두 영역 사이에 direct passage가 제공되어야.
(3) 문장 (1)에서 요구되는 오프닝에는 문이나 창문이 없어야.
9.5.1.4. Combination Rooms
(1) 2 or more areas may be considered as a combination room if opening between areas occupies the larger of 3 m² or 40% or more of wall measured on side of dependent area.
(2) Where dependent area is a bedroom, direct passage shall be provided between 2 areas.
(3) Opening required in Sentence (1) shall not contain doors or windows
9.5.3.1. Ceiling Heights of Rooms or Spaces
(1) The ceiling heights of rooms or spaces in residential occupancies and live/work units shall conform to Table 9.5.3.1. (2) Areas in rooms or spaces over which ceiling height is not less than the minimum specified in Table 9.5.3.1. shall be contiguous with the entry or entries to those rooms or spaces.
(1) 주거용 건물 및 생활/작업 단위의 방 또는 공간의 천장 높이는 표 9.5.3.1에 따라야.
(2) 천정 높이가
표 9.5.3.1에 명시된 최소값 이상인 방 or 공간의 영역.
해당 방 or 공간의 입구 or 입구와 인접해야.
9.5.3.1. Ceiling Heights of Rooms or Spaces
(1) The ceiling heights of rooms or spaces in residential occupancies and live/work units shall conform to Table 9.5.3.1. (2) Areas in rooms or spaces over which ceiling height is not less than the minimum specified in Table 9.5.3.1. shall be contiguous with the entry or entries to those rooms or spaces.
2.2: Minimum Ceiling Heights in Rooms & Spaces ⇒ 9.5.3*
What is the minimum ceiling height of a 7m² bedroom located on the second floor of a house?
-2300 mm over 50% of bedroom and 2100 mm over the floor area,
-2100mm over required floor area,
-2300 mm over more than 50% of bedroom,
-2300 mm over 50% or 2100mm of all of required floor areas.
Reference: 9.5.3.1.(1). Ceiling Heights of Rooms or Spaces Table 9.5.3.1. room ceiling height
Answer: d)
2.2: Minimum Ceiling Heights in Rooms & Spaces ⇒ 9.5.3*
The minimum ceiling height below a structural Steel beam located in the basement of the house is:
1950 mm
2100 mm
1950 mm over 75% of the basement
2100mm over 75% of the basement
Reference:
9.5.3.1.(1).
Ceiling Heights of Rooms or Spaces
Table 9.5.3.1. room ceiling height
Answer: a)
2.3: Room Sizes & Ceiling Heights
1 What is the minimum required clear height of a storage garage?
Reference:
9.5.3.3.(1) Storage Garage
Answer: 2000 mm or 2 m
2.3: Room Sizes & Ceiling Heights*
2 What is the minimum required clear height over at least 75% of the required floor area for a living room?
Reference:
9.5.3.1.(1).
Ceiling Heights of Rooms or Spaces
Table 9.5.3.1. room ceiling height
Answer: 2300 mm or 2.3 m
2.3: Room Sizes & Ceiling Heights*
3 What is the minimum required clear height over a hall or entrance?
Reference:
9.5.3.1.(1). Ceiling Heights of Rooms or Spaces
Table 9.5.3.1. room ceiling height
Answer: 2100 mm or 2.1 m
2.3: Room Sizes & Ceiling Heights
4 What minimum area and dimension must a bedroom have in a one-bedroom house having no built-in cabinets?
Reference:
9.5.7.2.(1). areas of master bedrooms
Answer: Area: 9.8 m2
Dimension: No minimum dimension is stated.
모든 주택 단위에서,
적어도 하나의 침실은 내장 캐비닛이 없을시,
9.8m² 이상의 면적을 가져야 하며,
내장 캐비닛이 제공시, 8.8m² 이상의 면적을 가져야함
2.3: Room Sizes & Ceiling Heights
5 What is the minimum width of corridors serving only bedrooms without a second exit at the end of the hallway or the bedrooms?
Reference:
9.5.10.1.(1). hallway width
Answer: 860 mm
9.5.10.1.(1). hallway width
(1) 주거 단위 내 복도의 방해받지 않는 너비는 860mm 이상,
아래의 너비는 710mm로 허용.
(a) 거실에서 가장 먼 복도 끝에 침실과 욕실만 있고,
(b) 두 번째 출구가 제공되며,
(i) 거실에서 가장 먼 쪽 복도, or
(ii) 복도에서 제공되는 각 침실
2.3: Room Sizes & Ceiling Heights*
6 What is the minimum height of a basement space?
Reference:
Table 9.5.3.1. room ceiling height
Answer:
2100 mm or 2.1 m over at least 75% of the basement area and
not less than 1950 mm under beams and ducts.
2.4: Living and Dining Rooms
⇒ 9.5.6.1 Kitchen Areas ⇒ 9.5.5.1 Area of Dining Rooms or Spaces ⇒ 9.5.4.1 Area of Living Rooms & Spaces
2.4: Living and Dining Rooms
⇒ 9.5.6.1 Kitchen Areas ⇒ 9.5.5.1 Area of Dining Rooms or Spaces ⇒ 9.5.4.1 Area of Living Rooms & Spaces
2.5: Combined Spaces ⇒ 9.5.8
The owner of a new house wishes to create a separate finished floor area of the house,
in order to accommodate a potential tenant and generate additional income.
What is the minimum required floor area, if the space is intended to be used as a living, dining bedroom, and kitchen?
13.5 m2
14.9 m2
11 m2
None of the above
Reference:
9.5.8.1(1) Combined Living, Dining, Bedroom & Kitchen Spaces
Answer: a)
2인 이하의 침실을 포함하는 집에서
거실, 식당, 침실 및 주방 공간이 결합된 경우,
결합된 공간의 면적은 13.5m2 이상이어야 합니다.
.
2.6: Natural Ventilation ⇒ 9.32.2
1 What is the minimum unobstructed area of a window opening that is required for ventilation purposes in a 3 m × 4.5 m bedroom?
Reference:
Table 9.32.2.1. Natural Ventilation
Answer:
For ventilation, 0.28 m2
2.6: Natural Ventilation ⇒ 9.32.2*
2 What is the minimum unobstructed area of a window opening that is required for ventilation purposes in a bathroom in a house?
Reference:
Table 9.32.2.1. Natural Ventilation
Answer: 0.09 m2
2.6: Natural Ventilation ⇒ 9.32.2*
3 Calculate the minimum unobstructed window area required for ventilation purposes for an unfinished basement measuring 4 m × 6 m?
Reference:
Table 9.32.2.1. Natural Ventilation
Answer:
.2% of floor area
= (0.2/100) X 4.0 m X 6.0m
= 0.048m2
2.6: Natural Ventilation ⇒ 9.32.2
4 Are screens required on windows providing natural ventilation?
Reference:
9.32.2.2.(1). Protection from Weather and Insects
Answer: No
(1) 창문 이외*의 자연환기용 오프닝은
날씨와 벌레로부터 보호할 수 있도록 시공.
2.7: Mechanical Ventilation ⇒ 9.32.3
직접 환기:
연소 공기가 밀폐된 통로를 통해 실외에서 ㅈㅈ 공급되고
연소 생성물이 밀폐된 환기구를 통해 실외에서 ㅈㅈ 배출됨.
— 9.32.3.1. (1)(a)
기계적 환기(*ㅇㄷ 통풍):
연소 공기가 건물 외피 ㄴㅂ에서 공급되고
연소 생성물이 밀폐된 환기구에 의해 실외로 ㅇㄷ됨.
— 9.32.3.1.(1)(b)
건물 외피 내부에서 연소 공기가 공급되고
연소 생성물이 *굴뚝 or type B vent를 통해
실외로 전달되는 ㅈㅇ 통풍
— 9.32.3.1.(1)(c).
분류는 주거 단위 유형 분류를 결정하기 때문에 중요함.
이 분류는 설치된 기계 환기 시스템이 어떤 기준을 충족해야 하는지 결정하는 데 사용.
2.7: Mechanical Ventilation ⇒ 9.32.3
직접 환기:
연소 공기가 밀폐된 통로를 통해 실외에서 직접 공급되고
연소 생성물이 밀폐된 환기구를 통해 실외에서 직접 배출됨.
— 9.32.3.1. (1)(a)
기계적 환기(*유도 통풍):
연소 공기가 건물 외피 내부에서 공급되고
연소 생성물이 밀폐된 환기구에 의해 실외로 확실하게 유도됨.— 9.32.3.1.(1)(b)
건물 외피 내부에서 연소 공기가 공급되고
연소 생성물이 *굴뚝 or type B ven를 통해
실외로 전달되는 자연 통풍
— 9.32.3.1.(1)(c).
분류는 주거 단위 유형 분류를 결정하기 때문에 중요함.
이 분류는 설치된 기계 환기 시스템이 어떤 기준을 충족해야 하는지 결정하는 데 사용.
2.7: Mechanical Ventilation ⇒ 9.32.3
A Type I :
A direct-vented or mechanically vented induced draft, non-solid fuel–burning furnace; or
a direct-vented or mechanically vented induced draft, non-solid fuel–burning domestic hot-water heater; or both.
In addition, it may contain a direct-vented non-solid fuel–burning fireplace.
직접 or 기계 환기 유도 통풍, 비고체 연료 ㅇㅇㅇ, or
직접 or 기계 환기 유도 통풍, 비고체 연료 연소 가정용 ㅇㅇㅇ, or 둘 모두.
or 직접 환기식 비고체 연료 연소식 ㅇㅇㅇ를 포함할 수도.
A Type II :
Any or all of the Type I appliances. + a solid fuel–burning appliance.
Type I 어플라이언스의 일부 or 전체 + 고체 연료 연소 장치.
A Type III :
A mechanically vented induced draft non-solid fuel–fired fireplace.
Or
Any natural draft appliance.
Or both
기계적 환기되는 유도 통풍 비고체 연료 연소식 벽난로. Or
모든 자연 통풍 장치. Or both
A Type IV dwelling unit contains:
Electric space heating.
전기 난방.
2.7: Mechanical Ventilation ⇒ 9.32.3
A Type I :
A direct-vented or mechanically vented induced draft, non-solid fuel–burning furnace; or
a direct-vented or mechanically vented induced draft, non-solid fuel–burning domestic hot-water heater; or both.
In addition, it may contain a direct-vented non-solid fuel–burning fireplace.
직접 or 기계 환기 유도 통풍, 비고체 연료 연소로, or
직접 or 기계 환기 유도 통풍, 비고체 연료 연소 가정용 온수기, or 둘 모두.
or 직접 환기식 비고체 연료 연소식 벽난로를 포함할 수도.
A Type II :
Any or all of the Type I appliances. + a solid fuel–burning appliance.
Type I 어플라이언스의 일부 or 전체 + 고체 연료 연소 장치.
A Type III :
A mechanically vented induced draft non-solid fuel–fired fireplace.
Or
Any natural draft appliance.
Or both
기계적 환기되는 ㅇㅇ 통풍 비고체 연료 연소식 ㅇㅇㅇ.
Or
모든 자연 통풍 장치. Or both
A Type IV dwelling unit contains:
Electric space heating.
ㅇㅇ 난방.
2.7: Mechanical Ventilation ⇒ 9.32.3
2 Are each of the dwelling types required to meet the same requirements for installation of a mechanical ventilation system?
Answer yes or no,
explain why the Code is written with these particular requirements.
Answer:
No
– Types I, II, & IV are required to meet the requirements of subsection 9.32.3.
–Type III dwellings must comply with the stricter requirements of Part 6,
because Type III appliances present a much greater safety & fire risk.
Reference:
9.32.3.2.(1) Required Mechanical Ventilation
2.7: Mechanical Ventilation ⇒ 9.32.3
2 Are each of the dwelling types required to meet the same requirements for installation of a mechanical ventilation system?
Answer yes or no,
explain why the Code is written with these particular requirements.
Answer:
No
– Types I, II, & IV are required to meet the requirements of subsection 9.32.3.
–Type III dwellings must comply with the stricter requirements of Part 6,
because Type III appliances present a much greater safety & fire risk.
Reference:
9.32.3.2.(1) Required Mechanical Ventilation
2.8: Exhaust Fan Capacity 표
What is the principal exhaust fan capacity for a house with 3 bedrooms?
a) 22.5 L/s
b) 30 L/s
c) 15 L/s
d) 37.5 L/s
Reference:
Table 9.32.3.4.A.
Principal exhaust fan capacity
Answer: b)
2.9: Calculation of Total Ventilation Capacity & Fan Capacity 표
Living(5),
Dining(5),
Kitchen(5),
Bathroom(5),
Bedroom(5):
Reference: Table 9.32.3.3.
Master Bedroom(10) & Basement (10)
Reference:
Table 9.32.3.3.
Supplementary Fan Capacity =
Total Ventilation Capacity - Principal Fan Capacity
Note: 1 L/s (1 litre per second) = 2 cfm (2 cubic feet per minute)
Answer:
5 rooms × 5 L/s per room = 25 L/s
Answer:
2 rooms × 10 L/s per room = 20 L/s
Answer:
45 - 22.5 = 22.5 L/s
2.10: Table 9.32.3.9. Fan Sound Ratings XX
- Which of the following standards can be used to determine the sound rating of the principal fan required for the dwelling unit in activity 2.9?
a) CAN/CSA-C260-M
b) HVI 916
c) HVI 915
d) either a) or c)
Ref: 9.32.3.9. (2)(a)(b) Fan Ratings
(2) sound ratings for required fans
(a) CAN/CSA-C260-M
(c) HVI 915
2.10: Table 9.32.3.9. Fan Sound Ratings
Principle Exhaust Fan Capacity Connection
Is the exhaust air intake for the Principle Exhaust Fan connected directly to the duct system?
IF Yes– go to
9.32.3.4. Principal Exhaust
(7)(a) & (b).
(10)
9.32.3.4.(7)(a) & (b). &
Where an exhaust air intake for the principal exhaust fan is connected directly to the duct system of a forced air heating system or other central air circulation system,
(a) be connected to the return air side of the system &
(b) be connected not less than 1000 mm upstream from any outdoor air supply duct.
9.32.3.4.(10)
In applying Table 9.32.3.4.B
(a) Where there is more than one exhaust air inlet duct connected directly to the fan, the diameter of the inlet ducts must be decreased by 25mm, and
(b) Where the exhaust duct is connected to the duct system of a forced air heating system, the duct diameter shall be increased by 25 mm.
2.11 Additional Ventilation Requirements
Principle Exhaust Fan Capacity Connection
Is the exhaust air intake for the Principle Exhaust Fan connected directly to the duct system?
IF No– go to
9.32.3.4. Principal Exhaust
(8), (9) & (10).
9.32.3.4.(8), (9) & (10).
(8) Where an exhaust air intake for the principal exhaust fan is located in the kitchen, it shall be located in the ceiling or on the wall within 300 mm of the ceiling.
(9) Single or multiple exhaust ducts serving the principal exhaust fan required by (1) shall be sized according to Part 6 except that they may be sized according to Table 9.32.3.4.B Where,
(a) the longest total duct length from intake grille to outdoor hood, does not exceed 12 m, and
(b) the number of elbows does not exceed 4,
but, in any case, they shall not be smaller than recommended by the manufacturer of the fan.
(10) Table 9.32.3.4 B Principal Exhaust Duct Size
(a) Where there is more than one exhaust air inlet duct connected directly to the fan, the diameter of the inlet ducts must be decreased by 25mm, and
(b) Where the exhaust duct is connected to the duct system of a forced air heating system, the duct diameter shall be increased by 25 mm.
2.11: Additional Ventilation Requirements
Ventilation Sys
Is the ventilation system coupled with a forced air heating system?
Yes
– for a Type I dwelling unit,
a ventilation supply inlet is not required.
9.32.3.6.(2).
Yes
– for a Type II dwelling unit,
an HRV is required to be installed.
9.32.3.6.(3) – (5).
9.32.3.6 Ventilation system coupled with forced air heating sys
(2) Where a mechanical ventilation system serves a Type I dwelling unit, a ventilation supply inlet is not required
(3) Where a mechanical ventilation system serves a Type II dwelling unit, the system shall include a heat recovery ventilation coupled to the forced air heating system, installed in accordance with Article 9.32.3.11.
(4) The forced air heating system circulation fan shall be controlled by a manual switch located adjacent to be ventilation fan switch required in Sentence 9.32.3.4. (4)
(5) The switch required in (4) shall be identified by the word CIRCULATION FAN
2.11: Additional Ventilation Requirements
Ventilation Sys
Is the ventilation system coupled with a forced air heating system?
No
– where the ventilation system is not coupled with forced air heating system,
an HRV & ductwork system are required to be installed.
Size requirements for these main & branch ducts are specified in Article 9.32.3.7.
2.11: 추가 환기 요구 사항
환기 시스템
환기 시스템과 강제 공기 가열 시스템이 결합되어 있습니까?
아니요.
– 환기 시스템이 강제 공기 가열 시스템과 결합되지 않은 경우,
HRV 및 덕트설비를 설치해야 합니다.
이러한 주 덕트와 분기 덕트의 크기 요건은 제9.32.3.7조에 명시되어 있습니다.
9.32.3.8. Protection Against Depressurization
Is soil gas present?
Yes - 9.32.3.8.(1).
(1) When determining the need to provide protection against depressurization, consideration must be given to,
(a) whether the presence of soil gas is deemed to be a problem, AND
(b) the presence of solid fuel-fired combustion appliances.
Is a solid-fuel-fired appliance present in the house?
Yes - See 9.32.3.8.(2).
(2) Where a solid fuel-fired combustion appliance is installed,
the ventilation system shall include a heat recovery ventilator that is designed to operate
so that the flow of exhaust air does not exceed the flow of intake air in any operating mode,
and that complies with the requirements of Article 9.32.3.11.
9.32.3.8. Protection Against Depressurization
Is soil gas present?
Yes - 9.32.3.8.(1).
(1) 감압에 대한 보호를 제공할 필요 결정 시, 다음 고려.,
(a) 토양 가스의 존재 = 문제 여부 및
(b) 고체 연료 연소식 연소 기구의 존재.
Is a solid-fuel-fired appliance present in the house?
Yes - See 9.32.3.8.(2).
(2) 고체 연료 연소식 연소 장치가 설치 시,
환기 시스템은 배기 흐름이 어떤 작동 모드에서도 흡기 흐름을 초과하지 않도록 설계,
제9.32.3.11조 준수하는 열 회수 환기 장치를 포함해야.
9.32.3.8. Protection Against Depressurization
- A room 2.2m x 3.25m has no natural ventilation and is not mechanically cooled.
How much air must be changed per hour through mechanical ventilation?
Assume a wall height of 2.44 m.2.2m x 3.25m x 2.44m = 17.446m³/h Ref: 9.32.1.3 (3) Ventilation room & spaces
Ref: 9.32.1.3 (3) Ventilation room & spaces
(3) Where a room or space is not provided with natural ventilation as described in (1),
mechanical ventilation shall be provided to exhaust inside air from or to introduce outside air to that room or space at the rate of one-half air change per hour
if the room or space is mechanically cooled in summer, and one air change per hour if it is not.
(3) 제1항의 규정에 의한 자연환기시설이 구비되지 않은 객실 or 공간,
실내 or 공간이 여름철에 기계적으로 냉각시, 시간당 1회 환기가 되지 않을시,
기계적 환기가
시간당 1/2 공기 변화의 속도로 실내 공기를 배출 or
해당 실내 or 공간으로 제공되어야. (외부 공기를 유입시키기 위해)
2.11: Ventilation Systems
- What is the minimum thermal resistance of a duct carrying outdoor air that is not tempered or mixed with indoor air,
which passes through a heated space,
where the duct is exposed in the heated space for 3 meters of length in the heated space?
minimum RSI 0.5
Ref: 9.32.3.10 (4) ducts
Ref: 9.32.3.10 (4) duct
Where a duct carrying outdoor air that is not tempered or not mixed with indoor air passes through heated space,
it shall be insulated to not less than RSI 0.5 except that, where such a duct is exposed in the heated space for more than 3 m of length in the heated space, it shall be,
(a) insulated to not less than the values listed in Table 9.32.3.10 A AND
(b) provided with a vapour barrier
담금질되지 아니하거나
실내공기와 혼합되지 아니한
덕트(실외공기 운반)가 가열된 공간을 통과하는 경우,
RSI 0.5 이상, 단열처리.
단, 덕트가 가열된 공간에서 3m 이상 노출시 예외,
(a) 표 9.32.3.10 A 및 A에 열거된 값 이상으로 절연됨
(b) 증기 장벽이 있는
- May exhaust ducts exhaust into an attic space or a soffit space?No
— Exhaust ducts shall not discharge into heated or unheated enclosed spaces.
배기 덕트는
(가열되거나 가열되지 않은)
밀폐된 공간으로 배출되면 안됨.
Ref: 9.32.3.10 (2) duct
Ref: 9.32.3.10 (2) duct
Exhaust ducts shall not discharge into heated or unheated enclosed spaces
배기 덕트는
(가열되거나 가열되지 않은)
밀폐된 공간으로 배출되면 안됨.
2.12
9.33.3.1 Indoor Design Temperatures
Outside design temperature,
heating facilities must be capable of maintaining an indoor air temperature of not less than:
22°C in all living spaces,
22°C in unfinished basements,
15°C in heated crawl spaces.
외부 설계 온도,
난방 시설은 실내 공기 온도를 다음 처럼 유지
모든 생활 공간에서 22°C,
미완성 지하실에서 22°C,
가열된 크롤링 공간에서 15°C.
2.12
9.33.3.1 Indoor Design Temperatures
Outside design temperature,
heating facilities must be capable of maintaining an indoor air temperature of not less than:
22°C in all living spaces,
22°C in unfinished basements,
15°C in heated crawl spaces.
외부 설계 온도,
난방 시설은 실내 공기 온도를 다음 처럼 유지.
-모든 생활 공간에서 22°C,
-미완성 지하실에서 22°C,
-가열된 크롤링 공간에서 15°C.
2.13 Lighting
Stairway lighting controlled by a 3-way switch located at the head and foot of a stairway must be provided at:
a) Stairways containing three risers in dwelling units.
b) Stairways leading into basements that do not contain finished space.
c) Stairways leading into basements which lead into an outside entrance.
d) None of the above
Reference: 9.34.2.3.(3)
Answer: c)
Reference: 9.34.2.3.(3)
The stairway lighting for basements that do not contain finished space or
lead to an outside entrance or built-in garage and that serve not more than one dwelling unit is permitted to be controlled by a single switch located at the head of the stairs
-완성된 공간이 없거나,
-외부 입구 or 붙박이 차고로 연결되지 않고,
-하나이상의 가구에 사용되는 지하실용 계단 조명은
계단 머리에 있는 단일 스위치로 제어할 수 있음.
2.14 Plumbing 9.31
Service Water Heating Facilities
Hot water with a temperature range from 45°C to 60°C.
Electric storage-type service water heater is required to have a minimum set storage temperature of 60°C
온도 범위가 45°C ~ 60°C인 온수.
ㅇㅇ 저장식 서비스 ㅇㅇㅇ는 최소 설정 저장 온도가 60°C이어야 합니다
2.14 Plumbing 9.31
Service Water Heating Facilities
Hot water with a temperature range from 45°C to 60°C.
Electric storage-type service water heater is required to have a minimum set storage temperature of 60°C
온도 범위가 45°C ~ 60°C인 온수.
전기 저장식 서비스 온수기는 최소 설정 저장 온도가 60°C이어야 합니다
2.14: Plumbing 9.31 X
- What plumbing fixtures are required to be provided in a dwelling unit with a water distribution system?
Answer:
Kitchen sink,
lavatory,
bathtub or a shower stall,
water closet or a composting toilet,
laundry facilities or space for laundry facilities.
Reference:
9.31.4.1.(1),(a),(b),(c),(d)
9.31.4.2.(1).
Reference:
9.31.4.1. Required fixtures
(1) water distribution sys shall contain,
(a) kitchen sink
(b) lavatory
(c) bathtub or shower stall
(d) water closet or a drainless composting toilet
9.31.4.2. laundry fixtures
(1) laundry facilities or a space for laundry facilities shall be provided in every dwelling unit or grouped elsewhere in the building in a location conveniently accessible to occupants of every dwelling unit.
2:14 Plumbing 9:31
9.31.3.2 Required Connection
(1) water distribution sys, Piping for hot and cold water is required to be connected to every
-kitchen sink,
-lavatory,
-bathtub,
-shower,
-slop sink,
-laundry area.
(2) Piping for cold water shall be run to every water closet.
(1) 물 분배 시스템, 온수 및 냉수 배관은 모든
-주방 싱크대,
-화장실,
-욕조,
-샤워기,
-슬로프 싱크대 및
-세탁 구역
에 연결되어야.
(2) 냉수를 위한 배관은 모든 물 옷장에 연결되어야.
2:14 Plumbing 9.31
What plumbing facilities must be supplied with hot and cold water?
Answer:
Reference:
9.31.3.2.(1). Required Water Supply
Can any fixtures be supplied only with cold water?
Answer:
Reference:
9.31.3.2.(2). Required Connections
2:14 Plumbing 9.31
What plumbing facilities must be supplied with hot and cold water?
Answer:
Hot and cold water must be connected to every
-kitchen sink,
-lavatory,
-bathtub,
-shower,
-slop sink, and
-laundry area
Reference:
9.31.3.2.(1). Required Water Supply
Can any fixtures be supplied only with cold water?
Answer:
Cold water shall be run to every water closet.
Reference:
9.31.3.2.(2). Required Connections
2.14 Plumbing 9.31
Is installation of a floor drain required in a dwelling unit?
Answer:
Reference:
7.1.4.2. Floor Drains
(1) Where gravity drainage to a sanitary drainage system is possible, a floor drain shall be installed in a basement forming part of a dwelling unit.
(2) Where gravity drainage to a sanitary drainage system is not possible, the floor drain required by (1) may be connected to a storm drainage system, dry well or drainage ditch provided it is located where it can receive only clear water waste or storm sewage.
9.31.4.4. Floor Drains
(1). A floor drain shall be installed in a basement forming part of a dwelling unit.
2.14 Plumbing 9.31
Is installation of a floor drain required in a dwelling unit?
Answer: Yes.
Reference:
7.1.4.2. Floor Drains
(1) Where gravity drainage to a sanitary drainage system is possible, a floor drain shall be installed in a basement forming part of a dwelling unit.
(2) Where gravity drainage to a sanitary drainage system is not possible, the floor drain required by (1) may be connected to a storm drainage system, dry well or drainage ditch provided it is located where it can receive only clear water waste or storm sewage.
9.31.4.4. Floor Drains
(1). A floor drain shall be installed in a basement forming part of a dwelling unit.
2.14 Plumbing 9.31
What section(s) of the Code specify the special installation requirements for hot water heaters?
Answer:
Reference:
9.31.6.2. Equipment and Installation
(1) Every service water heater and its installation shall conform to Part 7
Answer:
Reference:
9.31.6.2. Equipment and Installation
(3) Where the building is in a location where the spectral response acceleration, Sa(0.2), is greater than 0.55, service water heaters shall be secured to the structure to resist overturning and displacement
2.14 Plumbing 9.31
What section(s) of the Code specify the special installation requirements for hot water heaters?
Answer:
The installation must comply with Part 7.
Reference:
9.31.6.2. Equipment and Installation
(1) Every service water heater and its installation shall conform to Part 7
Answer:
The units must be anchored when located in areas with spectral response accelerations, Sa(0.2) greater than 0.55
Reference:
9.31.6.2. Equipment and Installation
(3) Where the building is in a location where the spectral response acceleration, Sa(0.2), is greater than 0.55, service water heaters shall be secured to the structure to resist overturning and displacement
2.14 Plumbing 9.31
Does the Code require that water supplied by hot-water heating equipment be in a specific temperature range?
If so, what is that range?
Answer:
Reference:
9.31.6.1.(1).
adequate supply of service hot water with a temperature range from 45°C to 60°C.
Answer:
Reference:
9.31.6.1. (2)
An electric storage-type service water heater shall have a minimum set storage temperature of 60°C.
2.14 Plumbing 9.31
Does the Code require that water supplied by hot-water heating equipment be in a specific temperature range?
If so, what is that range?
Answer:
Yes. 45ºC (113ºF) to 60ºC (140ºF)
Reference:
9.31.6.1.(1).
adequate supply of service hot water with a temperature range from 45°C to 60°C.
Answer:
If electric, must be a minimum of 60ºC (140ºF)
Reference:
9.31.6.1. (2)
An electric storage-type service water heater shall have a minimum set storage temperature of 60°C.
3.1 Glass 9.6
Which of the following components does not require the glass to conform to CAN/CGSB-12.1-M “tempered or laminated safety glass”
a) 600mm sidelight in entrances to a house,
b) entrance door into the dwelling unit with a glass area of 0.6 m² located at 890 mm from the bottom of the door
c) glass shower enclosure
d) mirrored glass doors in walk-in closets*
Ref:
9.6.1.2. Material Standards for Glass
(1)(a) CAN/CGSB-12.1-M, “Tempered or Laminated Safety Glass,”
(2) mirrored glass door = entrance to clothes closets = CAN/CGSB-82.6
3.1 Glass 9.6
Which of the following components does not require the glass to conform to CAN/CGSB-12.1-M “tempered or laminated safety glass”
d) mirrored glass doors in walk-in closets
Ref:
9.6.1.2. Material Standards for Glass
(1)(a) CAN/CGSB-12.1-M, “Tempered or Laminated Safety Glass,”
(2) mirrored glass door = entrance to clothes closets = CAN/CGSB-82.6
3.2 Requirement for Windows, Doors & Skylights 9.7.2
Describe the mandatory requirements for entrance doors leading into dwelling units.
Answer:
A door
must be provided at each 00000000, and
must contain a door 000000,
must consist of 0000000000 glazing, or have a 000000000
Reference:
9.7.2.1 Entrance Doors
(1) Door shall be provided at each entrance to a dwelling unit.
(2) Main entrance doors to dwelling units shall be provided with
(a) door viewer or transparent glazing in the door, or
(b) sidelight
3.2 Requirement for Windows, Doors & Skylights 9.7.2
Describe the mandatory requirements for entrance doors leading into dwelling units.
Answer:
A door
must be provided at each entrance, and
must contain a door viewer,
must consist of transparent glazing, or have a sidelight
Reference:
9.7.2.1 Entrance Doors
(1) Door shall be provided at each entrance to a dwelling unit.
(2) Main entrance doors to dwelling units shall be provided with
(a) door viewer or transparent glazing in the door, or
(b) sidelight
3.3 Table 9.7.2.3 Glass Area for Rooms of residential occupancy
- What is the minimum unobstructed glass area for a 2.5m x 3m bedroom located in the basement of house which contains a sliding patio door?Ref: 9.7.2.3. Table 5% ⇒ 2.5 * 3 * 0.05% = 0.375 m²
3.3 Table 9.7.2.3 Glass Area for Rooms of residential occupancy
- What is the minimum unobstructed glass area for a 2.5m x 3m bedroom located in the basement of house which contains a sliding patio door?Ref: 9.7.2.3. Table 5% ⇒ 2.5 * 3 * 0.05% = 0.375 m²
3.3 Table 9.7.2.3 Glass Area for Rooms of residential occupancy
- Consider a 3.5 m * 4.5 m bedroom located on a secondary story of a house
a) What is the minimum unobstructed glass area?
Ref; 9.7.2.3. Table 5% ⇒ 3.5 * 4.5 * 0.05 = 0.7875 m²
3.3 Table 9.7.2.3 Glass Area for Rooms of residential occupancy
- Consider a 3.5 m * 4.5 m bedroom located on a secondary story of a house
a) What is the minimum unobstructed glass area?Ref; 9.7.2.3. Table 5% ⇒ 3.5 * 4.5 * 0.05 = 0.7875 m²
- Consider a 3.5 m * 4.5 m bedroom located on a secondary story of a house
b) What is the minimum unobstructed open portion?
(State the minimum area and the minimum single dimension.)
Ref:
9.9.10.1. (1)(b) Egress Windows or Doors for Bedrooms
Provides an individual, unobstructed open portion having a minimum area of 0.35 m2
with no dimension less than 380 mm
최소 면적이 0.35m2이고
치수가 380mm 이상,
개별 unobstructed open portion을 제공
- Consider a 3.5 m * 4.5 m bedroom located on a secondary story of a house
b) What is the minimum unobstructed open portion?
(State the minimum area and the minimum single dimension.)
Ref:
9.9.10.1. (1)(b) Egress Windows or Doors for Bedrooms
Provides an individual, unobstructed open portion having a minimum area of 0.35 m2
with no dimension less than 380 mm
최소 면적이 0.35m2이고
치수가 380mm 이상,
개별 unobstructed open portion을 제공
- Consider a 3.5 m * 4.5 m bedroom located on a secondary story of a house
c) What is the maximum sill height?
Ref: 9.9.10.1 (2) Egress Windows or Doors for Bedrooms
Except for basement areas,
the window required in (1) shall have a maximum all height of 1000 mm above the floor
바닥에서 최대 1000mm의 문턱의 높이를 가져야함
(지하 제외)
- Consider a 3.5 m * 4.5 m bedroom located on a secondary story of a house
c) What is the maximum sill height?
Ref: 9.9.10.1 (2) Egress Windows or Doors for Bedrooms
Except for basement areas,
the window required in (1) shall have a maximum all height of 1000 mm above the floor
바닥에서 최대 1000mm의 문턱의 높이를 가져야함 (지하 제외)
3.4 Performance of Windows, Doors & Skylights
Must be designed, constructed and installed
so that, when in the closed position,
they
-resist the ingress of precipitation into interior space,
-resist wind loads,
-control air leakage,
-resist the ingress of insects and vermin,
-where required, resist forced entry, and
-are easily operable, unless they are fixed units.
-Heat Transfer Performance
-Thermal Characteristics
-Manufactured Windows, Doors and Skylights
3.4 Performance of Windows, Doors & Skylights
Must be designed, constructed and installed
so that, when in the closed position,
they
-resist the ingress of precipitation into interior space,
-resist wind loads,
-control air leakage,
-resist the ingress of insects and vermin,
-where required, resist forced entry, and
-are easily operable, unless they are fixed units.
-Heat Transfer Performance
-Thermal Characteristics
-Manufactured Windows, Doors and Skylights
3.4 Performance of Windows, Doors & Skylights
Which of the following characteristics is not a requirement for performance of storm doors, and sliding doors?
a) Resist wind loads when in closed position,
b) Control air leakage to minimum allowable 5 m3h/m or maximum 8.35 m3h/m,
c) Resist ingress of insects and vermin
d) Are easily operable
Answer:
Reference:
9.7.3.1.General Performance Criteria
(4) Storm doors, sliding doors and their components shall be designed, constructed and installed so that, when in the closed position, they
(a) resist wind loads,
(b) control air leakage to a minimum allowable 5 m3h/m and a maximum allowable 8.35 m3h/m,
(c) resist the ingress of insects and vermin, and
(d) are easily operable
3.4 Performance of Windows, Doors & Skylights
Which of the following characteristics is not a requirement for performance of storm doors, and sliding doors?
a) Resist wind loads when in closed position,
b) Control air leakage to minimum allowable 5 m3h/m or maximum 8.35 m3h/m,
c) Resist ingress of insects and vermin
d) Are easily operable
Answer: b)
Reference:
9.7.3.1.General Performance Criteria
(4) Storm doors, sliding doors and their components shall be designed, constructed and installed so that, when in the closed position, they
(a) resist wind loads,
(b) control air leakage to a minimum allowable 5 m3h/m and a maximum allowable 8.35 m3h/m,
(c) resist the ingress of insects and vermin, and
(d) are easily operable
A thermal break is required to be provided in windows doors and skylights when:
a) Metal frames and sashes are used.
b) They are installed as vehicular access doors.
c) They are installed as storm windows and doors.
d) The windows and doors are required to have fire resistance rating.
Answer:
Reference:
9.7.3.3. Thermal Characteristics of Windows, Doors and Skylights
(2) Windows and doors described in Sentence (1) do not require a thermal break where they are installed as,
(a) vehicular access doors,
(b) storm windows and doors, or
(c) windows and doors that are required to have a fire -resistance rating.
A thermal break is required to be provided in windows doors and skylights when:
a) Metal frames and sashes are used.
b) They are installed as vehicular access doors.
c) They are installed as storm windows and doors.
d) The windows and doors are required to have fire resistance rating.
Answer: a)
Reference:
9.7.3.3. Thermal Characteristics of Windows, Doors and Skylights
(2) Windows and doors described in Sentence (1) do not require a thermal break where they are installed as,
(a) vehicular access doors,
(b) storm windows and doors, or
(c) windows and doors that are required to have a fire -resistance rating.
3.5 Resistance to Forced Entry for Windows 9.7.5.3
What is the height above ground level beyond which windows resistant to forced entry are not required?
강제 진입을 방지할 수 있는 창문이
필요하지 않은 지면 위의 높이는 얼마?
Answer: ?? m
Reference:
9.7.5.3. Resistance to Forced Entry for Windows
(1) Windows, where any part is within 0 m of the outside ground level, must meet certain standards for resistance to forced entry
창문 (부품이 외부 지면에서 2m 이내에) =
강제 진입 저항에 대한 특정 기준을 충족해야함
3.5 Resistance to Forced Entry for Windows 9.7.5.3
What is the height above ground level beyond which windows resistant to forced entry are not required?
강제 진입을 방지할 수 있는 창문이 필요하지 않은 지면 위의 높이는 얼마?
Answer: 2 m
Reference:
9.7.5.3. Resistance to Forced Entry for Windows
(1) Windows, where any part is within 2 m of the outside ground level, must meet certain standards for resistance to forced entry
창문 (부품이 외부 지면에서 2m 이내에) =
강제 진입 저항에 대한 특정 기준을 충족해야함
3.5 Resistance to Forced Entry
An entrance door is shown on a set of plans
as being a stile-and-rail panel type with a panel thickness of 12 mm, opening outward.
Does this proposal conform to the minimum requirements listed in the Code?
일련의 도면에 입구 문이 표시됨.
패널 두께가 12mm인 stile-and-rail 패널 유형으로 바깥쪽으로 열림.
이 제안은 강령에 나열된 최소 요구 사항을 준수함?
Answer:
No.
Reference:
9.7.5.2. Resistance to Forced Entry for Doors
(8) Except for storm doors or screen doors, doors described in Sentence (1) that
swing outward shall be provided with hinges or pins so that the doors cannot be removed when they are in the closed position
바깥쪽 스윙에는 힌지 or 핀이 제공,
도어가 닫힌 위치에 있을 때 제거할 수 없음.
3.5 Resistance to Forced Entry
An entrance door is shown on a set of plans as being a stile-and-rail panel type with a panel thickness of 12 mm, opening outward.
Does this proposal conform to the minimum requirements listed in the Code?
일련의 도면에 입구 문이 표시됨.
패널 두께가 12mm인 stile-and-rail 패널 유형으로 바깥쪽으로 열림.
이 제안은 강령에 나열된 최소 요구 사항을 준수함?
Answer:
No.
Panels must be 19 mm.
- 9.7.5.2.(3)(c) clauses (a) and (b) contain additional requirements for wood doors.
Ensure that hinges have non-removable pins or security pins inserted in the door
패널은 19mm여야함.
- 조항 9.7.5.2.(3)(c) 조항 (a) 및 (b)는
목재 문에 대한 추가 요구 사항을 포함.
경첩에 제거할 수 없는 핀 or
도어에 삽입된 보안 핀이 유무확인.
Reference:
9.7.5.2. Resistance to Forced Entry for Doors
(8) Except for storm doors or screen doors, doors described in Sentence (1) that
swing outward shall be provided with hinges or pins so that the doors cannot be removed when they are in the closed position
바깥쪽 스윙에는 힌지 or 핀이 제공,
도어가 닫힌 위치에 있을 때 제거할 수 없음.
3.5 Resistance to Forced Entry
List the other Resistance to Forced Entry requirements for doors.
9.7.5.2 Resistance to Forced Entry for Doors
(4)~(9)
(4) door - deadbolt lock + cylinder
(5) Inactive leaf in double doors = heavy-duty bolt top & bottom
(6) hinges (=with correct secrew)
(7) Strike plates for deadbolts
(8) Provided with hinges or pins
(9) Solid blocking (at lock height)
3.5 Resistance to Forced Entry
List the other Resistance to Forced Entry requirements for doors.
9.7.5.2 Resistance to Forced Entry for Doors
(4)~(9)
(4) door - deadbolt lock + cylinder
(5) Inactive leaf in double doors = heavy-duty bolt top & bottom
(6) hinges (=with correct secrew)
(7) Strike plates for deadbolts
(8) Provided with hinges or pins
(9) Solid blocking (at lock height)
3.5 Resistance to Forced Entry 9.7.5
Must all doors located as described in Sentence 9.7.5.2.(1)
conform with the prescriptive requirements listed above?
Answer:
No,
if the door has at least a Grade 10 rating when tested in accordance to ASTM F476, the door is deemed to provide equivalent performance.
Reference:
9.7.5.2.
(2) Doors, frames and hardware that conform to a security level of at least Grade 10 as described in the Annex to ASTM F476, “Security of Swinging Door Assemblies”, are not required to conform to Sentences (3) to (7).
Answer:
Also, these requirements do not apply to ——– doors to garages or other ——— spaces.
Reference:
9.7.5.2.
(1) Except for exterior doors to garages and to other ancillary spaces, this Article applies to,
(a) swinging entrance doors to dwelling units,
(b) swinging doors between dwelling units and attached garages or other ancillary spaces, and
(c) swinging doors that provide access directly or indirectly from a storage garage to a dwelling unit.
3.5 Resistance to Forced Entry 9.7.5
Must all doors located as described in Sentence 9.7.5.2.(1)
conform with the prescriptive requirements listed above?
Answer:
No,
if the door has at least a Grade 10 rating when tested in accordance to ASTM F476, the door is deemed to provide equivalent performance.
Reference:
9.7.5.2.
(2) Doors, frames and hardware that conform to a security level of at least Grade 10 as described in the Annex to ASTM F476, “Security of Swinging Door Assemblies”, are not required to conform to Sentences (3) to (7).
Answer:
Also, these requirements do not apply to exterior doors to garages or other ancillary spaces.
Reference:
9.7.5.2.
(1) Except for exterior doors to garages and to other ancillary spaces, this Article applies to,
(a) swinging entrance doors to dwelling units,
(b) swinging doors between dwelling units and attached garages or other ancillary spaces, and
(c) swinging doors that provide access directly or indirectly from a storage garage to a dwelling unit.
Clear height
The clear height over stairs is measured vertically from a line drawn through the outer edges of the nosings
For stairs *within dwelling units, the clear height must be not less than *.** m (6’5”)
For stairs *not within dwelling units the clear height must be not less than *.** m (6’ 9”)
Width
At least one stairway between each floor level within a dwelling unit must have a width not less than *** mm (2’ 11”)
Required exit stairs must have a width not less than *** mm (3’)
Clear height
The clear height over stairs is measured vertically from a line drawn through the outer edges of the nosings
For stairs *within dwelling units, the clear height must be not less than 1.95 m (6’5”)
For stairs *not within dwelling units the clear height must be not less than 2.05 m (6’ 9”)
Width
At least one stairway between each floor level within a dwelling unit must have a width not less than 860 mm (2’ 11”)
Required exit stairs must have a width not less than 900 mm (3’)
9.8.3 Stair Configurations
Which of the following configurations is not permitted in dwelling units?
a) Straight flights,
b) Curved flights,
c) Rectangular treads with winders
d) Spiral stairs with curved winders
Answer:
**
Reference:
9.8.3.1. Straight and Curved Runs in Stairs
4.1: Stair Configurations
Which of the following configurations is not permitted in dwelling units?
a) Straight flights,
b) Curved flights,
c) Rectangular treads with winders
d) Spiral stairs with curved winders
Answer:
d)
Reference:
9.8.3.1. Straight and Curved Runs in Stairs
9.8.4.4 Uniformity & tolerances of risers & treads XX
The difference between highest & lowest risers within a flight of stairs is limited to 00 mm
계단 내 가장 높은 라이저와 가장 낮은 라이저의 차이
= 00mm로 제한됨.
The difference between greatest and smallest tread depth within a flight of stairs is limited to 00 mm
계단 내 최대 트레드 깊이와 최소 트레드 깊이의 차이
= 00mm로 제한됨.
difference for tread depth or riser height for adjacent stairs cannot exceed 5 mm
인접한 계단의 디딤판 깊이 or 라이저 높이의 차이
= 5mm를 초과할 수 없음.
9.8.4.4 Uniformity & tolerances of risers & treads XX
The difference between highest & lowest risers within a flight of stairs is limited to 10 mm
계단 내 가장 높은 라이저와 가장 낮은 라이저의 차이
= 10mm로 제한됨.
The difference between greatest and smallest tread depth within a flight of stairs is limited to 10 mm
계단 내 최대 트레드 깊이와 최소 트레드 깊이의 차이
= 10mm로 제한됨.
difference for tread depth or riser height for adjacent stairs cannot exceed 5 mm
인접한 계단의 디딤판 깊이 or 라이저 높이의 차이
= 5mm를 초과할 수 없음.