Q & A Flashcards
What is the fire rating for building having more than 2 basements?
All structural members up to and including the floor of the lowest level of discharge of underground buildings more than 7000 mm below or more than two level below the lowest level of exit discharge (i.e. All High depth Underground Buildings or Structures) shall be at least 2 hours fire rated construction.
What is the maximum size of a kitchen allowed in a non-sprinklered building?
For a non-sprinkler protected building, the floor area of the kitchen compartment shall not exceed 150 m2.
What is the definition of a high-rise building or structure?
The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having total height of occupiable or usable space of more than 23 Meters above the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Highrise Building.
What is the definition of a midrise building or structure?
The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having total height of occupiable or usable space between 15 Meters to 23 Meters from the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Midrise Building.
What is the definition of a low-rise building or structure?
The occupancies or Multiple and Mixed occupancies, facilities, buildings and structures having total height of occupiable or usable space up to 15 Meters from the lowest grade or lowest level of Fire Service Access into that occupancy is categorized as Low-rise Building.
What is the definition of a low depth structure or building?
A structure or a building with up to two basements or up to 7 m below the level of exit discharge
What is the definition of a high depth structure or building?
A structure or a building with more than two basements or more than 7 m below the level of exit discharge.
What is the fire rating and the minimum size of the Emergency Command Centre?
The Emergency command centre shall be separated from other parts of the same building by compartment walls and floors having fire resistance of at least 1 hour with fire suppression system. Minimum size shall be 8.9 m2.
At what level shall the fire pump be installed within the building?
Fire pumps shall be located on the ground floor or below grade level with protected dedicated access from the fire engine access level.
At what level shall the intermediate fire pumps and water tanks be located for high-rise buildings?
Where multiple pump sets are required in a Highrise building, Intermediate Fire Pumps and Water tanks shall be located at not more than 90 m intervals from the First Fire Pump located at the lowest level of the structure.
When can the separation between the kitchen and the dining area be exempted?
Separation requirement for kitchen could be exempted when all the cooking facilities in the kitchen are fitted with an approved extinguishing system such as Kitchen hood suppression. Separation requirement for kitchen could also be exempted when an eating establishment is separated from other parts of the same building by walls and floors having fire resistance of at least 1 hour and doors having fire resistance of at least half an hour.
What is the fire rating for the separation between theatre, cinema or concert hall from other parts of the building?
A theatre, cinema or concert hall shall be separated from other parts of the same building, which is of a different purpose group, by compartment walls and floors having a fire resistance of at least 2-hour. If the building is protected by an automatic sprinkler system, the fire resistance rating of the compartment walls or floors can be reduced to 1-hour.
What is the fire rating for hotel bedrooms?
Each hotel bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having fire resistance rating of at least 1 hour.
What is the fire rating for labor accommodation bedroom?
Each labor accommodation bedroom shall be compartmented from adjoining rooms and other parts of the same building by construction having fire resistance rating of at least 1- hour.
What are the kitchen fire rating requirements for a labor accommodation?
Kitchens are only allowed on the ground floor and shall be enclosed with minimum 1-hour fire rated compartment wall, including 1⁄2-hour fire rated door. Kitchen shall be separated by 1 hour fire rating and a protected corridor away from the dormitory sleeping area on the ground floor.
What is the fire rating required for motor vehicle workshop?
A motor vehicle workshop shall be separated from any other part of the same building by compartment walls and floors having fire resistance of not less than 2 hours.
What is the fire rating and ventilation requirement for a spray painting booth or for any spray painting process?
Areas in which spray painting or other allied processes are performed or carried out, shall be separated from other parts of the same building by compartment walls and floors having fire resistance of not less than 2 hours. Spray painting booths shall have built in vapor extraction system.
What is the size requirement for cold room and the fire rating of the construction?
Where a cold room has a floor area exceeding 20 m2, a separate outer layer of non- combustible construction, including the door, having minimum 1-hour fire resistance rating (with sprinkler), shall be provided to compartmentalize the cold room enclosure from other areas. Provision of the fire resisting outer layer enclosure, including the fire door to the cold room would not be required if the cold room has a floor area not exceeding 20 m2 and is sprinkler protected. The storage materials shall not include highly flammable chemicals. Cold room lesser than 20 m2 provided with at least one hour fire rating compartment, need not be provided with sprinklers provided that the storage shall not include flammable materials.
What shall the maximum allowable area of a mezzanine floor?
The aggregate area of mezzanines within a room, other than those located in special-purpose industrial occupancies, shall not exceed one-third the open area of the room in which the mezzanines are located.
What is a breeching inlet?
A connection through which the Civil Defence fire department can pump supplemental water into the sprinkler system, standpipe, or other system, furnishing water for fire extinguishment to supplement existing water supplies.
What is the definition of fire access level?
Level where Civil Defence Fire Appliances (Fire Truck/Engine) are deployed and where fire fighters have direct access into the building.
What is the definition of fire engine access road?
The road to the building or structure to allow access for Civil Defence fire-fighting and rescue apparatus.
What is the definition of fire engine access way?
The path adjacent to the building or structure to allow operational setup for Civil Defence fire-fighting and rescue apparatus such as Aerial Appliances.
What is a landing valve?
A 65 mm diameter water outlet normally located inside or near the staircase landing for trained or Civil Defence fire fighters to use during fire.
What is the maximum distance allowed between the edge of a fire engine access way and the breeching inlet?
Buildings fitted with standpipes and automatic sprinkler system shall have access ways for pumping appliances within 18 m of the breeching inlet. The breeching inlets shall be visible from the access ways.
What is the spacing requirement for private fire hydrants along fire engine access way and access road?
Spacing between Private Hydrants along Fire Engine access way and access road are as follows:
i. Residential and Commercial Occupancies shall be 120 m
ii. Light Hazard Storage Occupancies shall be 100 m
iii. Ordinary Hazard Storage Occupancies shall be 100 m
iv. Light Hazard Industrial Occupancies shall be 100 m
v. Ordinary Hazard Industrial Occupancies shall be 100 m
vi. High Hazard Occupancies shall be 60 m
What is the minimum flow rate for each private fire hydrant?
Minimum flow rate for each Private fire hydrant shall be 500 Gallons per Minute.
What is the minimum pressure required for fire hydrant in relation to landing valves?
Minimum Pressure required for Private fire hydrant is 6.9 bars.
What is the minimum duration of fire fighting water supply for private fire hydrant?
Private Fire Hydrant Water supply for fire fighting shall be for 2 hours.
What is the height limitations for a fire hydrant?
The center of a hose outlet shall be not less than 457 mm and not more than 914mm above final grade
How far shall the distance be between the fire engine access way and any access opening of a building?q
Access way shall be positioned so that the nearer edge shall be not less than 2 m or more than 10 m from the centre position of the access opening, measured horizontally.
What is the gradient requirement for a fire engine access way?
Access way shall be laid on a level platform or if on an incline, the gradient shall not exceed 10%.
What is the maximum allowable dead end distance for a fire engine access way?
Dead-end access way and fire engine access road shall not exceed 45 m in length or if exceeding 45 m, be provided with turning facilities.
What is the minimum height clearance along fire engine access way and access road?
Overhead clearance of access way and fire engine access road shall be at least 4.5 m for passage of fire fighting appliances. Overhead obstruction to access way could be entrance gate, link or bridges connecting buildings.
In what type of building shall a fire lift be required?
In any building which is classified as high-rise or High depth building having more than 2 level of basement, there shall be provided at least one fire lift, which shall be contained within a separate protected shaft or a common protected shaft containing other lifts subject to such other lifts being served at each storey by a fire fighting lobby.
What is the minimum dimension of a fire lift car?
Minimum dimension of a Fire lift car shall be of 1950mm either in length of breadth.
What is the minimum width of a fire fighting staircase?
Fire-fighting stairs should be a minimum of 1200 mm wide.
What is the size requirement for a fire fighting lobby?
The fire fighting lobby shall have a clear floor area of not less than 5 m2. The clear floor area should not exceed 20 m2 for spaces serving up to four lifts or 5 m2 per lift for spaces serving more than four lifts.
Where can landing valves be installed in accordance to preference?
Landing valves shall be located in accordance to the following preference:
i. In fire Fighting lobby (if provided), for the first landing valve.
ii. In Fire fighting or exit staircase, for the first landing valve.
iii. In smoke free enclosure or external corridor.
iv. In the common corridor or area within a protected shaft.
What is the length of coverage for one landing valve?
Every part of the floor area shall be within 30 m coverage of a landing valve.
When shall an emergency command centre be provided?
An Emergency Command Centre shall be provided in any building which is ‘Highrise’ with 23 m or more in height with the exception of One-and-Two-Family Dwelling and such Emergency Command Center shall have the following:
i. Fire lift
ii. Emergency voice communication system
iii. Engineered smoke control system.
What is the size requirement for an emergency command centre?
An Emergency Command Centre shall be of adequate size to house all the terminals and supervisory/control equipment, etc of the building’s fire protection/detection systems and a free working space of at least 8.9 m2 with no dimension lesser than 2440 mm.
Where shall the emergency command centre be located?
An Emergency Command Centre shall be located adjacent to the fire lift lobby at the designated storey of the building (i.e. the lobby of the building on the first storey or immediately adjacent thereto).