Pump Testing Flashcards
Quick Lift Test:
The suction strainer needs ____ inches of clearance in all directions.
24”
What are the names of the four types of pump tests?
Quick lift test, Dry vacuum test, Capacity tests, Pressure control device test
Quick Lift Test:
Operate the primer and record the time it takes until the main pump is ____ water.
Discharging
Quick Lift Test:
What do you do when the test is complete?
Open all discharge valves that serve hose is connected to the test kit with rpm at medium speed to warm engine and transmission properly.
Dry Vacuum Test:
Run the primer to a vacuum gauge reading of ___?
22 in of Hg.
Dry Vacuum Test:
Air should not leak into the pump at a rate that will reduce the vacuum more than ___ inches of Hg. in ___ minutes.
10” in 5 minutes
Dry Vacuum Test:
What do you recheck if the test fails?
All drains, discharges, and suction valves for closure
A pressure control device test is how much psi?
250 psi
Adjust throttle and discharge valves to deliver ____% capacity at ___ psi and ____ pressure?
50%, 250psi, Pump Discharge
All valves shall be closed no faster than ___ seconds.
5
The pressure rise shall not exceed ___ psi.
30
Raise engine speed to ___ rpm for ___ minutes for cool down period before shutting engine down.
1000 rpm for 5 minutes
What three percentages are used for the capacity tests?
50%, 70%, and 100%
50% Capacity Test:
This test is run at ___ psi.
250 psi
50% Capacity Test:
Net pump pressure for ___ minutes.
10 min.