PRACTICE EXAM Flashcards
An electrical appliance is rated at 1,500 watts, and is connected to 120 volts. What is the resistance associated with the appliance?
9.6 ohms
I = P/E
I= 1500/120
I = 12.5 Amps
R = E/I
R = 120/12.5
R = 9.6 Ohms
What is an askarel?
A group of nonflammable synthetic chlorinated hydrocarbons used as electrical insulating media.
Approximately how many kilowatts are used by a three-phase, 480-volt AC motor that draws a current of 52 amperes and has a power factor rating of 88%?
38,043 watts
or 38kW
P = 1.732 * 480 * 52 * .88 = 38,043 Watts
One horsepower is equal to how many watts?
746 watts
A resistor has the following color bands (in order) : orange, red, brown, silver. What is the resistor value?
320 Ohms (10% tolerance)
What is the greatest root-mean-square (effective) difference of potential between any two conductorsk of a circuit defined as?
Voltage
An appliance draws 40 amperes when used on a circuit. A bad splice is discovered on the line at the appliance on one of the phase conductors. The splice has a measured resistance of 0.5 ohms. How much power is lost at the splice
800 watts
Power loss = I2 *R
P= (40*40) * .5
P = 1600 * .5
P = 800 Watts
A continuous load is a load whre the maximum current is expected to continue for at least how long?
3 Hours
Where metallic plugs or plates are used with nonmetallic enclosures, how far shall they be recessed from the outer surface of the enclosure?
1/4 inch
How far shall the work space extend from the grade, floor, or platform for equipment that is 60 inches in height?
6’ 6 “ = 78 inches
For other than a totally enclosed switchboard or switchgear, what is the minimum amount of space that shall be provided between the top of an unshielded switchboard or switchgear and any combustible ceiling?
3 feet or 36 inches
Where a feeder supplies conitnuous loads or any combination of continuous and non continuous loads, the minimum feeder conductor size shall have an allowable ampacity not less than the nonconitnous load plus what percentage of the conitnuous load?
125%
Where an electrical vault is required or specified for conductors and equipment operating at over 600 volts, nominal, the floor when in contact directly with earth shall be constructed in what manner?
6 inches of concrete
check answer?>
What clearance must be maintained when overhead spans of open conductors or open multiconductor cables of not over 1,000 volts, nominal, pass over residential property.
12 feet
Where the negative polarity of a DC system does not serve as the connection point for the grounded conductor, which color finish can be used to identify the negative ungrounded conductor?
Black
What is the recommended maximum total voltage drop on both feeders and branch circuits to the farthest outlet?
5%
What is the maximum voltage drop for any branch circuit, seperatley derived system, operating 120-volts line-to-line and 60 volts to ground, serving sensitive electronic equipment?
1.5%
check answer?.
Temporary electric power and lighting installations for holiday decorative lighting shall be permitted for a period not to exceed?
90 days
Which type of conduit is not permitted to be used to install underground service conductors?
FMC
The feeder conductor ampacity shall not be less than that of the service conductors where the feeder conductors carry the total load by service conductors with an ampacity of
55 amperes or less
Receptacles in residential units shall be installed that no space measured horizontally along the floor of any wall space is more than how far from a receptacle outlet?
6 feet
When the disconnecting means of a transformer is located remotely it must be
lockable
What must circuit breakers used as switches in high-intensity discharge lighting circuits be marked as?
HID
Which is best defined as an unintentional, electrically conductive connections between an ungrounded conductor of an electrical circuit and the normally non-current-carrying conductors, metallic enclosures, metallic raceways, metallic equipment, or earth?
Ground Fault
What is the maximum permitted length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet for a 12 AWG conductor with a listed outlet branch-circuit type arc-fault interrupter installted at the first outlet box?
70 feet
Resistance-type heating elements in electric space-heating equipment shall be protected at not more than how many amperes?
60 amperes
The service disconnecting means may be installed in all of the following excpet?
The Bathroom
What is the maximum overcurrent protection for a 10 AWG copper conductor?
30 amperes
A motor disconnecting means shall be permitted to be out of sight of the controller for motor ciruits over how many volts?
1000 volts, nominal
For permanently connected appliances, the branch-circuit overcurrent device shall be permitted to serve as the disconnecting means for appliances rated at not over?
300 volt-amps or 1/8 hp
Plug fuses shall be permitted to be used to in circuits supplied by a system having a grounded neutral point whre the line-to-neutral voltage does NOT exceed which of the following
150 volts
Where a main bonding jumper or a system bonding jumper is a screw only, the screw shall be identified with which color finish?
Green
A system that is connected to establish electrical conitnuity and conductivity is considered to be which of the following?
Bonded
High-impedance grounded neutral systems in which a grounding impedance limits the ground fault curretn to a low value shall be permitted for which type of system?
3- phase ac systems of 480 to 1000 volts