T or F
Calcium Chloride Brine Solutions are suitable for food processing applications because it uses simple table salt in it’s mixture
False
T or F
When using an electric float for the control of ammonia systems a needle vive must always be used to control the amount of liquid refrigerant entering the chiller, this valve is normally located up stream of from the liquid line solenoid valve
True
T or F
Calcium Chloride may be stored in the same location or equipment room as ammonia as long as there is no direct source of heat
False
T or F
Copper or brass may be used in ammonia systems as long as there is no moisture present in the equipment room
False
T or F
The minimum test pressure for the “low side” of an air cooled ammonia system is equal to or greater than the setting pressure of the relief device
False
T or F
Cascading is desirable if system temperatures of lower than -125F are required
True
The liquid recirculating pump as used with two stage liquid recirculation ammonia systems is located between the:
a) compressor and receiver
b) low pressure and high pressure receiver
c) low press receiver and evaporator
d) high press receiver and evaporator
low pressure receiver and evaporator
The boiling point of R-717 at atmospheric pressure is
a) -28C
b) -27.6F
c) -28F
d) -27.6F
-28F
When installing globe valves in any system for component isolation, how should they be installed on horizontal line runs?
a) valve stem should be vertical to line run
b) stem should be horizontal to line run
c) stem may be in any position as long as high press side of system is exerted on bottom side of seat assembly
d) stem should be at right angles to horizontal run of pipe and the high press side exerted on bottom side of seat assembly
stem should be at right angle to horizontal run of pipe
What component is not normally required in cascade systems?
a) condenser
b) receiver
c) refrigerant flow control on secondary coil
d) low stage condenser
receiver
Which type of intercooler is not suitable for ammonia compression systems?
a) dry type
b) shell and coil
c) open type
d) any of the above are suitable
dry type
Multi-stage or booster compression systems are normally required for low temp applications such as ammonia blast freezers. This type of compression system is normally good for applications above -90F and should be used if the reciprocating compression ratio of a single stage system exceeds:
a) 20:1
b) 10:1
c) 5:1
d) 3:1
10:1
Multi-stage cascade systems can be divided into two major groups which are
a) cascade or extra low
b) cascade or multi-stage
c) cascade or direct
d) any of the above could be considered correct
cascade or direct
An ammonia receiver has the following dimensions 3ft x 60” long. What is the correct PRV capacity? Factor for R718 = 1, For R-717 = 0.5
a) 90cu/ft/min
b) 90 lbs/min
c) 7.5 cu/ft/min
d) 7.5 lbs/min
7.5lbs/min
C=FDL (60”/12”) to get feet
The corrosiveness of a brine or eutectic mixture should be maintain between _____ and ______ and can be determined by a PH tester
a) 7 and 6.5
b) 7 and 7.5
c) 7 and 8.5
d) none of the above
7 and 8.5
The normally temperature drop through a low temperature chiller is normally:
a) 2C at a flow rate of 10 to 15gals/ton
b) 2F at a flow rate of 10 to 15gals/ton
c) 10F at a flow rate of 2 to 9 gals/ton
d) 10C at a flow rate of 2 to 9 gals/ton
2F at a flow rate of 10 to 15 gals/ton