PPT Flashcards
Reverse-Cycle Refrigeration
- Air-conditioning equipment can only pump heat in ____ direction
- Heat pumps can heat two ways;
- into as well as out of a ______
- Also having a four-way ________ valve
- These valves are used to switch the unit between _______ and _______ modes
- one
2. structure, reversing, heating and cooling
Heat Sources For Winter:
- Air conditioners pump heat from low temperature inside
the structure to a higher temperature outside the house - At 0F outside air temp, there is still __% usable heat in the air
- The heat pump removes ____ from the outside air in the winter and deposits it in the conditioned space to heat it; an air-to-air heat pump
- 85%
3. heat
The Four-Way Reversing Valve
- Allows heat pump to pump heat in ___ directions
- Diverts heat-laden discharge gas to either ____ or cool in conditioned space
- Refrigerant is directed from the _______ to the indoor coil in the heating mode
- Refrigerant is directed from the compressor to the ______ coil in cooling mode
- two
- heat
- compressor
- outdoor
The Four-Way Reversing Valve: Control and Operation
- Controlled by the space temperature _________
- Four port valve that has a slide mechanism in it:
- Position of the slide determines the mode of operation: heating or cooling
- Smaller, direct-acting, four way reversing valves
- pressure difference pushes the slide mechanism
thermostat
What terminal is a conventional heat pump wired to?
B
What terminal is a non-conventional heat pump wired to?
O
Default/fail to O means ?
heating
Gas line in heat pump:
- HIGH temp superheated gas means the unit is in what mode?
- LOW temp superheated gas means the unit is in what mode?
- heating mode
2. cooling mode
Air Coils:
- circulates _______
- absorb heat from or release heat to ___
- Fins increase the heat _________ surface area
- refrigerant
- air
- exchanging
Ground Coils: Uncommon*
- Underground tubing through which refrigerant is circulated in ground-source heat pump
- outdoor coil for direct-exchange heat pump
- difficult to troubleshoot or ______
- repair
Water Coils:
- Heat transfers between refrigerant from indoor coil and water from water loop
- Installed near indoor ____
- Refrigerant and water pumped in separate but _______ tubes
- coil
3. adjacent
Water Loop:
- Tubing running to and from water _____
- Tubing is submerged in ______
- Used in closed-loop water-based systems
- Tubing water does not mix with body of _____ or refrigerant
- coil
- water
- water
Common Water-Based Solutions:
- Salts; name two
- Glycols; name two
- Alcohols; name two
- calcium chloride, sodium chloride
- Propylene glycol, ethylene glycol
- methyl alcohol, ethyl alcohol
Ground Loops:
- Tubing running to and from water coil _________
- Transfers heat between water coil and ______
- Can be horizontal or vertical
- can run in series or with ________ branches
- underground
- ground
- parallel
Auxiliary Heat: Balance point:
- When heat pump output _____ heat loss of the conditioned space
- If heat loss is greater than heat production, ________heat is required
- equals
2. auxiliary
Auxiliary Heat:
- Supplementary heat source in order to temper air
- Usually electric resistance heating coils, but it could be a gas-fired or oil-fired heating system
- Also used during reverse cycle ______ and for emergency heat operation
- defrost
During defrost of outdoor coil the unit will go into cooling mode in order to bring hot gas back to outdoor unit in order to melt the ___
ice
The Air-to-Air Heat Pump:
- The air-to-air heat pump resembles the central air-conditioning system
- Changes in terminology in a heat pump system:
- the coil that serves the inside of the house is called the ______ coil
- the coil that is located outside the house is called the _____ coil - Mode determined by the direction in which the _________ flows
- indoor, outdoor
3. refrigerant
Refrigerant Line Identification:
- The larger line is called the gas line because it always carries ___
- The suction line in the cooling mode and the discharge line in the heating mode
- The smaller line is called the liquid line because only liquid ________ travels through it
- The liquid flow toward the inside unit in ______ and towards the outside unit in _______
- gas
- refrigerant
- summer, winter
Metering Devices:
- Metering devices needed at _____ heat exchanger
- Types used in heat pumps;
_____-orifice devies
_________ tubes
____
Flow ____ pistons
- each
2. fixed orifice, capillary, TXVs, flow check
Metering Devices:
- Specially designed for ____ ____ applications
- There must be a metering device at the ______ unit in the heating mode
- There must be a metering device at the indoor coil in _______ mode
- heat pumps
- outdoor
- cooling
Thermostatic Expansion Valves:
- Check valves are piped parallel to the TXV to allow refrigerant to bypass the control when needed
- in cooling mode, the valve needs to meter the flow of liquid refrigerant into the indoor coil
- in heating mode, the liquid needs to move freely toward the outdoor unit - A vapour-charged TXV with a limited charge in the bulb usually used
- Bidirectional thermostatic expansion valves have a _____ valve built in
- check
In any type of hot pull down you need an ___ TXV
MOP - maximum operating pressure
Thermostatic expansion valves:
- Generally allow flow in only ___ direction
- Solutions for more flow directions;
Check valves running ______ to each TXV - Must have ___ compatible with coil and compressor
- one
- parallel
- MOP
The Capillary Tube:
- Often encountered on older pieces of equipment
- Will allow refrigerant flow to ____ ways
- Typically two capillary tubes are used
- Check valves are used to reverse flow but cannot meter flow based on ________ outlet temp (SH)
- Must be sized for specific flow amount
- Different sizes used for ______ and outdoor coils
- both
- evaporator
- indoor
Combination of Metering Devices:
- Uses the capillary tube at the indoor coil
- used in the ______ mode
- Load is relatively _______ in the warmer months - Uses thermostatic expansion valve at the outdoor coil
used in the _______ mode
- allows system to reach maximum ________ quickly
- cooling, constant
2. heating, efficiency
Electronic Expansion Devices:
- Can meter refrigerant in ____ directions
- If indoor and outdoor coils are close together, ____ device can be used
- The correct superheat will be maintained in both heating and cooing modes
- both
2. one
Orifice metering devices:
- used in conjunction with _____ valves
- One device is located at each ____
- The bore at the indoor coil is ______ than the bore at the outdoor oil
- Normally used with a ______ filter drier
- check
- coil
- larger
- bi-flow
Flow Check Pistons:
- Meters refrigerant flow in ___ direction
- Allows refrigerant to flow ______ and unrestricted in the other direction
- systems use two flow check pistons oriented in opposite directions
- one
2. freely
Liquid Line Accessories:
- Two standard filter driers can be used on systems with check valves:
- only one drier In the circuit at a time
- they are installed with arrows pointing in the same direction as the _____ valves - Bi-Flow filter driers: use this for heat pumps
- two driers in one
- designed for ____ pump applications
- check
2. heat pump