Power Engineering Flashcards
What is the phase difference between a phase voltage and a line voltage in a 3 phase AC system
30 degrees (positive)
What is the magnitude difference between a phase voltage and a line voltage
Line voltage = root(3) x phase voltage
What is the phase of Vrn
0 degrees
What is the phase of Vyn
-120 degrees
What is the phase of Vbn
120 degrees
What is the phase of Vry
30 degrees
What is the phase of Vyb
-90 degrees
What is the phase of Vbr
150 degrees
For a Star connected 3 phase ac system what type of voltage and current is through/ across the load
Phase voltage
Line current
For a delta connected 3 phase ac system what type of voltage and current is through/ across the load
Line voltage
Load current
What is the equation for power in a delta using a 3 wattmeter method
P=3xVphxIline x power factor
What are the equations to determine the power measurements using the 2 wattmeter method
P1 = Vbr x Ir x power factor P2 = Vyb x Iy x Power factor
For a unbalanced delta 3 phase system what are the equations for the line currents
Ir = Iry - Ibr Iy = Iyb - Iry Ib= Ibr - Iyb
What are the equations relating Voltage, turns and currents in an ideal transformer
Vp/Vs = Np/Ns = Is/Ip
Does a current flow in the primary current in an ideal transformer if no load is connected to the secondary
No
What is flux measured in
Webbers
Magnetic flux density measured in and what is the equation
Tesla
B= Flux/(cross sectional area)
What is magnetic field intensity measured in and what is the equation
Amps per meter
H = (NxI)/L
What is the equation for the max Vrms in a transformer
Vrms_max =4.44 x N x f x Bmax x Ac
What is a typical value for Bmax for iron
0.9-1.3T
What is the equation for the max current in a Transformer
(Current density limit x coil area x Fill Factor)/N
What are the equivalent circuit parameters of the transformer equivalent circuit
R1eq- equivalent copper loss X1eq- Reactance leakage Z1s- Secondary load equivalent Rc- Iron loss Xm- Magnetising reactance
For a Delta - Delta or Star - Star 3 phase transformer What is the phase shift between primary and secondary line voltages and how do the bank and phase ratios relate
No phase shift
Bank ratio = Phase ratio
For a delta star 3 phase transformer what is the phase shift between primary and secondary line voltages and how do the bank and phase ratios relate
Secondary line voltage leads the primary by 30 degrees
Bank Ratio = phase ratio/(root3)
For a Star Delta 3 phase transformer between primary and secondary line voltages and how do the bank and phase ratios relate
Secondary line voltage lags the primary by 30 degrees
Bank ratio = Phase ratio x root 3
What are the 2 ways the electromagnets can be switched on and off in a synchronous generator
Power electronic converter or commutator
What is synchronous speed in an induction motor
1 period of the mechanical flux rotating 1 full mechanical revolutions
What is the equation for the synchronous speed of an induction motor
Ns= (120xFs)/p
How is a torque produced by an induction motor
Sinusoidal flux will cause a sinusoidal voltage which will cause a force to be produced which is larger on one side of the rotor which produces torque.