Lines that run partially overhead and underground on the same street must be numbered ____?
with a single sequence of numbers.
in the mix of pole, transformer, junction boxes, pull boxes or any cable access points(primary or secondary). how do we number all of them ?
Every equipment location such as pad mounts, junction boxes, pull boxes or any cable access points (Primary or Secondary) shall be numbered as pole would be numbered.
When an equipment location is added between two existinq sequentially numbered equipment locations how do we add a new number to it?
by adding the only fraction allowed ( half 1/2)
how are the underground cables numbered?
Each underground cable shalI be marked at every location where a cable terminates ( Primary or Secondary). The cable shall I be marked with the number designation of the location where the other end of the cable Terminates.
how are Underground service cables shall be numbered?
Underground service cables shall be marked with the number
indicating the location of the power source followed by a dash and
then the service letter designation.
For example from pad number 2 to service A will be (2-A) and to service B would be (2-b) and from pad mount 4.6 to service C would be (4.6-C)
When two cables are laid between two points(transformer or pad) how do we number them?
for Example Two primary cables rising on pole 101 and both cables terminate
in pad 101.1 how do we number the cables.
at the pole: [101.1 1 of 2] and [101.1 2 of 2]
at the pad: [101 1 0f 2] and [101 2 of 2]