Suction Line Velocity - Maximum
3,000 ft/min
Suction Line Velocity - Minimum
1,500 ft/min
Allowable Suction Line Temperature Penalty
2 F degrees
Allowable Temperature Penalty for Discharge, Liquid & Condensate lines
1 F degree
Suction or Discharge line velocity minimum if only horizontal
750 ft/min
Liquid Line Velocity - minimum
No Minimum
Liquid Line Velocity - Maximum
300 ft/min
Guesstimating Pipe length less than 100 ft, multiply by …
2
Guesstimating Pipe length greater than 100 ft, multiply by…
1.5
The rate at which liquid refrigerant drops in pressure when it rises
0.5 psi/ft
What 4 factors must be taken into consideration when sizing pipe?
Cost, Oil Return, Temperature Penalties, Noise
Slope of pipe/ 10 ft.
1/2” in the direction of flow
Pipe length rising greater than 5 ft. need a..
P-Trap
Additional traps every…
10 ft.
Double Risers are used on compressors with…
Unloaders