Whenever a circuit which is carrying current is opened:
Current tends to continue to flow across the contacts as they separate.
The initials DPDT would normally be used to identify a type of:
Knife switch
The type of knife switch usually used to interrupt field current to generators and synchronous machines is a:
Field switch
Disconnect switches are commonly used on 440 V or higher voltage circuits to:
Isolate or to ground electrical equipment or circuits not in service
Of the following statements concerning mercury control switches, which one is most nearly not correct:
They are generally used only where the circuit voltage is 120 Volts or less
Mercury switches that are commonly used in control circuits where circuit voltage is 230 V or less have what properties?
They are single or double throw action, and they are silent operating.
The main difference between a circuit breaker and other kinds of electrical switches is that circuit breakers:
Open automatically when the current exerts a predetermined limit.
The energy needed to rapidly open the contacts of most circuit breaker designs is usually provided by…
Springs and gravity
What is meant by trip free-operation?
The precedence which takes place over any closing operation
Speed is desirable and opening a circuit breaker for what three reasons?
- Extinguish the arc.
- Minimize damage caused by a fault.
- Reduce the effect of a fault on lines and equipment not directly involved with the fault.
A trip-free operation takes place if…
A circuit breaker is closed while the protective relay is energized.
What are the three means/methods of quenching an arc?
- Increase the length of the arc path.
- Restrict the cross sectional area of the arc path.
- De-ionizing or cooking the gas.
A three phase 138KV circuit breaker can interrupt 12,000A. What is the interrupting capacity in MVA?
138,000 X 12,000 = 1656 MVA
PHEP 30 pg.21
4.8 KV circuit breaker has an interrupting rating of 30,000 A. What is its interrupting capacity when used at 5.1 KV?
Operating P = Rated P
4800V X 30,000A = 5100 V X I
I(rated) = 28,235A
PHEP 30 pg. 21
The closing time of an OCB, becomes more important when it is considered from the standpoint of…
Synchronizing generators.