Pettitech Refrigeration Exam Flashcards

1
Q

A standard air conditioning system that has low temperature rise across the condenser has…?

Multi answers

A

Has lost refrigerant and has low charge.
Has poor evap air flow and evap is frozen
Has a metering device problem I.E too restrictive

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Suction lines should be…?

A

Slightly warmer than your SST
(Saturated Suction Temperature)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

A high suction pressure can be cause by..?

Multi answers

A

Metering device too permissive
Clogged condenser coil
High Humidity

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What determines system pressure when it has been off for some time?

A

Ambient temperature at the outdoor condenser

90 deg. F day 410A the pressure will be around 275 PSIG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Liquid lines should be…?

Multi answers.

A

Slightly warmer than ambient Outdoor air
Slightly cooler than SCT
Noticeably warmer than suction line
Noticeably cooler than Discharge line

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Proper use of a vacuum pump?

Multi answer

A

Remove non condensables
Dehydrate a system
Includes frequent changing of oil
Requires pateint
Includes a Micron gauge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

To determine that refrigerant recovery procedure is complete…?

A

Acheive partial vacuum, close a strand off valve, watch for minimal pressure rise.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

True or Flase
Temperature does not reveal the intensity of heat in a substance; it merely tells you its quantity.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Proper Subcooling is an indication that…?

Multi answer

A

The condenser did its job
System charge is correct

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The heat that must be released by the condenser is…?

Multi answer

A

Latent heat
Absorbed heat (Absorbed in the evap)
Heat of compression(HOC)
Sensible heat

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Superheat is found in…?

Multi answer

A

Suction line
Discharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Superheat is heat that..?

A

Is added after complete vapourization

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Latent heat is…?

A

Causes a change of state

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When air gains moisture, assuming its DB remains constant.

Multi answers

A

Its WB rises,
RH Rises
and DP rises
It has gained latent heat

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When a pipe has condensation on it…?

A

The dew point of the ambient air is high than the pipes temperature

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When Capacitors are connected in parallel…?

A

The individual MFD is the sum of the individual ratings

5mfd+15mfd in parallel =20MFD

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

For PSC motors, the capacitor is…?

A

A run capacitor connected in series with the start winding.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Burnt wires are an indication of…?

Multi Answers

A

A poor connection,
Excessive amperage,
Poor contacts,
Undersizing wiring

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What sequence should be used upon discovering a refrigerant leak?

Multi steps

A

Recover, repair leak,Pressure test, Evacuate, charge, and tag.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

What is the problem when the entire equalizer tube for a TXV has sweat all along it?

Multi answer

A

The TXV is is internally damaged,
Some liquid might be travelling into the suction line,
The valve will function similar to an internally equalized TXV

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Which statements are true?
Evap Saturation should be colder than the suction.
The liquid line should be cooler than condenser saturation.
The suction line should be slightly cooler than evaporator supply air

A

All of those are true.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Thermal convection is…?

A

Heat causing flow of vapour or liquid due to differing densities

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Thermal conduction is…?

A

The transfer of heat energy through molecular vibration, contact, and collision.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Therma radiation is…?

A

The transfer of heat energy through electromagnetic waves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

Kelvin is the absolute expression of..?

A

Celsius

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

Rankin is the absolute expression of…?

A

Fahrenheit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

What would be the Temp. of a substance that has no molecular motion?

Multi answer

A

-460F
-273C
0R
0K

Absolute zero

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

Low suction pressure can be cause by..?

multiple answers

A

A TXV/EXV that is stuck nearly shut,
A piston restriction,
A liquid line kink,
Low airflow,
Plugged Filter drier,
Low return air temp.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

Air conditioning high head pressure can be caused by…?

Multi answers

A

Non-condensibles,
Clogged Condenser coils,
High humidity

30
Q

On a TXV the high side liquid pressure exerts an_ influence on the valve?

31
Q

On a TXV the spring exerts an ____ influences on the valve?

32
Q

On a TXV the sensing bulb exerts —— influence on the valve.

33
Q

As humidity rises, the air temperature difference across an evaporator…?

34
Q

Clogged air filters cause liquid refrigerant to flow to the comoressor?

35
Q

What is the volume of displacement if a compressor has a volumetric efficiency of 70% and a cylinder diameter of 2” and the piston stroke is 3”?

Use v=3.14(r^2)h

A

6.59 Cubed
V=3.14(r^2)h
V=3.14x(1^2)x3
V=3.14x1x3
V=3.14x3
V=9.42
9.42xVOL EFF
9.42x0.70
=6.594

36
Q

When the airflow of an air conditioning evaporator is poor…?

A

The evap will probably freeze up,
Could potentially send liquid to compressor

37
Q

When the evaporator airflow is poor the evaporator air delta T dry bulb is??

A

Increased because the air has more contact time.

38
Q

When the condenser airflow is poor the evaporator air delta T dry bulb is..?

A

Decreased because the evaporator pressure and saturation temperature is increased

39
Q

When the condenser airflow is poor the head pressure is..?

A

Increased because thermal transfer is poor

40
Q

When the metering device is too permissive the evaporator air delta T dry bulb is

A

Increased because the evaporator has less vapour, more liquid

41
Q

When the metering device is too permissive the subcooling is..?

A

Decreased because saturation temperature is decreased,
Decreased because the liquid flow rate is increased in the liquid line

42
Q

When the metering device is too permissive the superheat is…?

A

Decreased because the evaporator has less vapour, more liquid

43
Q

When the metering device is too permissive the head pressure is…?

A

Decreased because the condenser has more vapour, less liquid,
Decreased, because the liquid flow out of the condenser is increased.

44
Q

When the metering device is too permissive the suction pressure is..?

A

Increased, because heat of compression increases,
Increased, because more liquid flows into the evaporator

45
Q

When the metering device is too restrictive, the evaporator air delta T DB is..?

A

Decreased becausethe evaporator has more vapour less liquid.

46
Q

When the metering device is too restrictive the subcooling is…?

A

Increased, because the liquid flow rate is reduced in the liquid line.

47
Q

When the metering device is too restrictive the superheat is..?

A

Increased because the evaporator has more vapour, less liquid

48
Q

When the metering device is too restrictive the head pressure…?

A

Increases, as theirs more liquid, less vapour

49
Q

When the metering device is too restrictive the suction pressure is..?

A

decreased, because there is less liquid in the evaporator

50
Q

When the system charge is low the txv will…?

A

The TXV will try to open trying to decrease superheat

51
Q

When the system charge is low…?
(Multi answer)

A

The evap can freeze up,
A hermatic compressor will run hot,
Compressor amperage will be low,
System tonnage will be low

52
Q

When the system charge is low the condenser delta T dry bulb is…?

A

Decreased because the condenser Saturation temperature is decreased

53
Q

When the system charge is low the evaporator delta T dry bulb is….?

A

Decreased because the evaporator refrigerant heat absorption is less latent, more sensible

54
Q

When the system charge is low the evaporator air delta T dry bulb is…?

A

Decreased, because the evaporator has more vapour, less liquid

55
Q

When the system charge is low the subcooling is….?

A

Decreased because the condenser saturation temperature is decreased,
Decreased, because the condenser has less liquid, more vapour

56
Q

When the system charge is low the subcooling is…?

A

Decreased, because the head pressure is low

57
Q

When the system charge is low the superheat is…?

A

Increased, because the condenser has more vapour, less liquid

59
Q

When the system charge is low the head pressure is..?

A

Decreased, because the suction pressure is low

60
Q

When the system charge is low the suction pressure is…?

A

Decreased, because there is less liquid in the evaporator.

61
Q

Name a HCFC?

Hydrochlorofluorocarbon, Multi answers

A

R22
R123
R124

62
Q

Ozone is…?

Multi answers

A

Is an active form of oxygen,
Is comprised of 3 oxygen atoms,
In the stratosphere filters solar uv
Is depleted by Chlorine atoms :o

63
Q

Name a HFC refrigerant?

Hydrofluorocarbon

A

R134A
R32
R404A
R410A

Their are more types

64
Q

Which type of refrigerant has not been produced since 1995?

A

CFC’s
R11
R12
R115
R113

Chlorofluorocarbon

65
Q

An Azeotropic blend does not change when it…?

A

Evaporates,
Condenses

A mixture of two/more substances with similar boiling points.

66
Q

What type of oil is suitable for R22?

A

Mineral oil

67
Q

What type of oil is suitable with R134A

A

POE(Polyolester Oil)
AB(Alkylbensene Oil)
PAG(Polyalkylene Oil)

68
Q

True or False
Manufacturered Refrigerants are very unique substances that particularly have the uncommon property of being able to become cold when fed into the evaporator. No other substances can behave this way.

A

False,
Natural refrigerants can exibit the same properties
I.E Ammonia, Carbon Dioxide

69
Q

Name a CFC’s

Chloroflurocarbon

A

R11,
R12
R113
R115

70
Q

Charles law is…?

A

The gas law describing the relationship between temperature, volume and pressure.

71
Q

Daltons law is…?

Pressure total= P1+P2+P3,,,,,

A

The gas law of partial pressures; The total pressure of a mixture of gasses is the sum of the individual saturations pressure

72
Q

Boyles Law is…?

P1V1=P2V2

A

The gas law that describes the relationship between pressure and volume, and assumes a constant temperature