What are all The Permissives

A
P-4 Reactor Trip
P-6 Source Range
P-7 At Power
P-8 3 Loop Flow
P-9 Turbine Trip-Reactor Trip
P-10 Nuclear At Power
P-11 Pressure SI
P-12 Low-Low Tavg
P-13 Turbine at Power
P-14 S/G High Level
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

P-4

A

Permissive:Reactor Trip
Setpoint: Rx Trip and Bypass Breakers Open
Coincidence:
Function: Trips Main Turbine, Feedwater ISO with low Tavg (564F), Prevents Re-Actuation of SI after Reset, Transfers Steam dumps from Load Reject to Plant Trip, Arms Steam Dumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

P-6

A

Permissive: Source Range
Setpoint: IR>10^-10 Amps
Coincidence: 1 of 2 IR
Function: Permits Block of Source Range trip on High Voltage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

P-7

A

Permissive: At Power
Setpoint: P-10 or P-13
Coincidence: 1 of 2
Function: Unblocks Pressurizer Low Pressure, Pressurizer High Level, Low Flow in > 1 loop, and RCP undervoltage and underfrequency

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

P-8

A

Permissive: 3 Loop Flow
Setpoint: PR>48%
Coincidence: 2 of 4
Function: Unblocks low flow in 1 loop trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

P-9

A

Permissive: Turbine Trip on Reactor Trip
Setpoint: PR>50%
Coincidence: 2 of 4
Function: Unblocks Reactor Trip on Turbine Trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

P-10

A

Permissive: Nuclear at Power
Setpoint: PR>10%
Coincidence: 2 of 4
Function: Feeds P-7, Blocks Source Range High Voltage, Permits Block of IR Trip, IR Rod Stop, and PR low setpoint trip.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

P-11

A

Permissive: Pressure SI
Setpoint: <1970 psig
Coincidence: 2 of 3
Function: Permits block of pressurizer low pressure SI and Low steam line pressure SI/SLIS. This enables Steam Line Iso on high negative pressure rate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

P-12

A

Permissive: Low-Low Tavg
Setpoint: 550F
Coincidence: 2 of 4
Function: Blocks Steam Dumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

P-13

A

Permissive: Turbine at Power
Setpoint: Pimp>10%
Coincidence: 1 of 2
Function: Feeds P-7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

P-14

A

Permissive: Steam Generator Hi Level
Setpoint: Level >91%
Coincidence: 2 of 4 on any 1 of 4 steam generators
Function: Trips Main Feed Pumps, Trips Main Turbine, FWIS