Pec 4 Flashcards
Where installed in raceways conductors of size ____(mm2) and larger shall be stranded
8.0 mm2
A ________conductor has a trade name “moisture resistant thermoplastic”.
Type THHN
When the voltage between conductors does NOT exceed _____V and the roof has a slope of NOT less than _____(mm) in ______,(mm) the clearance can be reduced to _______(mm).
300 V
100 mm, 300 mm
1,000 mm
The down conductors shall be protected for a minimum distance of _______(mm) above grade level.
1,800 mm
Fuses shall be plainly marked with: (3)
ampere rating, voltage rating, and interrupting rating.
Which of the following statements is NOT true about grounding electrode conductor?
It shall be solid or stranded
It must be continuous
Splice or joints are allowed
It shall be insulated, covered or bare
Splice or joints are allowed
The uses of non-metallic extensions are NOT allowed in all but one of the following. Which one is this?
As an aerial cable
Where exposed to corrosive vapors
Where subject to corrosive vapors
Through floors or partitions
Where subject to corrosive vapors
Fixture wires shall NOT be used as ___________________
branch circuit conductors
Exposed energized parts of motors and controllers shall be guarded against ________ by elevating it __________(mm) or more above the floor.
accidental contact
2,400 mm
Exposed energized parts of motor and controller operating at ___V or more between terminals shall be guarded against accidental contact by enclosure.
50 V
To improve the insulation resistance of a motor, it is first cleaned, washed, varnished then baked. Which is very economical and effective method of baking particularly the inside coils of a large motor?
Putting incandescent lamps around the winding and cover
Hanging resistor strips inside the core and cover
Putting it inside the baking oven and control the oven temperature
Connecting the terminals to variable low voltage supply and increase the baking current gradually until the desired baking temperature is attained, making sure that the rated current is not exceed.
Putting it inside the baking oven and control the oven temperature
_________ includes any switch or device normally used to start and stop a motor by making and breaking the motor circuit current.
Controller
Grounding electrodes shall be installed such that at least _______(mm) of length is in contact with the soil.
2,400 mm
Lamps installed in scene docks shall be so located and guarded and shall provide an air space of NOT less than _______ (mm)between such lamps and any combustible material.
50 mm
Direct burial cables or conductors with a nominal voltage of ____V or less and placed under a one or two family dwelling driveways and parking areas shall have a minimum cover distance of______(mm).
660 V
460 mm
A _________ conductor has a trade name “heat-resistant rubber”.
Type RH
is the permanent joining of metallic parts to form an electrically conductive path which will assure electrical continuity and the capacity to conduct safely any current likely to be imposed. (April 2016)
Bonding
A metal ungrounded gas piping system _______ as a grounding system.
shall not be used
Cartridge fused and fuse holders shall have a maximum operating voltage of ______V.
300 V
The Building Code (PD 1096) of the Philippines has several referral codes. The only no-referral code is
The Philippine Electrical Code
Fire Code
Structural Code
Chemical Engineering Code
Chemical Engineering Code
________ conductors are used for machine tool wiring in dry or wet locations.
Type MTW
Fuses, circuit breakers or combinations thereof shall NOT be connected in ______.
parallel
At least _____(mm) of free conductor shall be left at each outlet, junction and switch point for splices or the connection of fixtures or devices.
150 mm
. Which of the following cables is NOT used as an electrical cable?
Flat cables
Optical fiber cables
Armored cables
Steel cables
Steel cables