Minimum thickness (mm) for 1hr fire resistance: Solid RC Slab, average cover to reinforcement
15
Minimum thickness (mm) for 2hr fire resistance: Solid RC Slab, average cover to reinforcement
20
Minimum thickness (mm) for 3hr fire resistance: Solid RC Slab, average cover to reinforcement
25
Minimum thickness (mm) for 4hr fire resistance: Solid RC Slab, average cover to reinforcement
25
Minimum thickness (mm) for 1hr fire resistance: Solid RC Slab, overall depth
100
Minimum thickness (mm) for 2hr fire resistance: Solid RC Slab, overall depth
125
Minimum thickness (mm) for 3hr fire resistance: Solid RC Slab, overall depth
150
Minimum thickness (mm) for 4hr fire resistance: Solid RC Slab, overall depth
150
Minimum thickness (mm) for 1hr fire resistance: Pre-stressed Concrete Slab, average cover to tendons
25
Minimum thickness (mm) for 2hr fire resistance: Pre-stressed Concrete Slab, average cover to tendons
40
Minimum thickness (mm) for 3hr fire resistance: Pre-stressed Concrete Slab, average cover to tendons
50
Minimum thickness (mm) for 4hr fire resistance: Pre-stressed Concrete Slab, average cover to tendons
65
Minimum thickness (mm) for 1hr fire resistance: Pre-stressed Concrete Slab, overall depth
100
Minimum thickness (mm) for 2hr fire resistance: Pre-stressed Concrete Slab, overall depth
125
Minimum thickness (mm) for 3hr fire resistance: Pre-stressed Concrete Slab, overall depth
150
Minimum thickness (mm) for 4hr fire resistance: Pre-stressed Concrete Slab, overall depth
150
Minimum thickness (mm) for 1hr fire resistance: Partition, solid concrete
125
Minimum thickness (mm) for 2hr fire resistance: Partition, solid concrete
150
Minimum thickness (mm) for 3hr fire resistance: Partition, solid concrete
175
Minimum thickness (mm) for 4hr fire resistance: Partition, solid concrete
175
Minimum thickness (mm) for 1hr fire resistance: Partition, solid masonry
125
Minimum thickness (mm) for 2hr fire resistance: Partition, solid masonry
150
Minimum thickness (mm) for 3hr fire resistance: Partition, solid masonry
175
Minimum thickness (mm) for 4hr fire resistance: Partition, solid masonry
200
Minimum thickness (mm) for 1hr fire resistance: Partition, hollow unit masonry
150
Minimum thickness (mm) for 2hr fire resistance: Partition, hollow unit masonry
200
Minimum thickness (mm) for 3hr fire resistance: Partition, hollow unit masonry
250
Minimum thickness (mm) for 4hr fire resistance: Partition, hollow unit masonry
300
Minimum thickness (mm) for 1hr fire resistance: Protection for metal structural members, concrete
25
Minimum thickness (mm) for 2hr fire resistance: Protection for metal structural members, concrete
38
Minimum thickness (mm) for 3hr fire resistance: Protection for metal structural members, concrete
50
Minimum thickness (mm) for 4hr fire resistance: Protection for metal structural members, concrete
75
Minimum thickness (mm) for 1hr fire resistance: Protection for metal structural members, masonry
38
Minimum thickness (mm) for 2hr fire resistance: Protection for metal structural members, masonry
55
Minimum thickness (mm) for 3hr fire resistance: Protection for metal structural members, masonry
75
Minimum thickness (mm) for 4hr fire resistance: Protection for metal structural members, masonry
100
Minimum thickness (mm) for 1hr fire resistance: Protection for metal structural members, metal lath with vermiculite or perlite gypsum plaster
12
Minimum thickness (mm) for 2hr fire resistance: Protection for metal structural members, metal lath with vermiculite or perlite gypsum plaster
20
Minimum thickness (mm) for 3hr fire resistance: Protection for metal structural members, metal lath with vermiculite or perlite gypsum plaster
38
Minimum thickness (mm) for 4hr fire resistance: Protection for metal structural members, metal lath with vermiculite or perlite gypsum plaster
50
Minimum thickness (mm) for 1hr fire resistance: Exterior wall, solid concrete
75
Minimum thickness (mm) for 2hr fire resistance: Exterior wall, solid concrete
125
Minimum thickness (mm) for 3hr fire resistance: Exterior wall, solid concrete
150
Minimum thickness (mm) for 4hr fire resistance: Exterior wall, solid concrete
180
Minimum thickness (mm) for 1hr fire resistance: Exterior wall, solid masonry
100
Minimum thickness (mm) for 2hr fire resistance: Exterior wall, solid masonry
150
Minimum thickness (mm) for 3hr fire resistance: Exterior wall, solid masonry
175
Minimum thickness (mm) for 4hr fire resistance: Exterior wall, solid masonry
200
Minimum thickness (mm) for 1hr fire resistance: Exterior wall, hollow masonry
150
Minimum thickness (mm) for 2hr fire resistance: Exterior wall, hollow masonry
200
Minimum thickness (mm) for 3hr fire resistance: Exterior wall, hollow masonry
250
Minimum thickness (mm) for 4hr fire resistance: Exterior wall, hollow masonry
300
Minimum thickness (mm) for 1hr fire resistance: Column, reinforced concrete (all faces exposed)
200
Minimum thickness (mm) for 2hr fire resistance: Column, reinforced concrete (all faces exposed)
300
Minimum thickness (mm) for 3hr fire resistance: Column, reinforced concrete (all faces exposed)
400
Minimum thickness (mm) for 4hr fire resistance: Column, reinforced concrete (all faces exposed)
450