State the earth return path, external to the installation, for each of the following systems.
i) TN-C-S.
ii) TN-S.
iii) TT.
PEN conductor
Separate Metallic conductor
General mass of earth
3b State what happens to the value of insulation resistance when
i) a parallel conductor is provided
ii) the conductor length is decreased
iii) a distribution board is measured as a whole instead of the individual circuits.
iv) the cross sectional area of conductors is increased
i. Decrease
ii. Increases
iii. Decrease
iv. Stays the same
when undertaking insulation resistance testing as part of a periodic inspection what does GN3 identify as normal practice
For most installations a test between live conductors connected together and earth is satisfactory
OR; testing between live conductors is not generally required
3d State, from the formula Zs = Ze + (R1+R2), what is represented by
i) Zs
ii) Ze
iii) R1+R2.
i. System or total EFLZ
ii. External EFLZ
iii. Resistance of line and cpc conductors
State the
i) purpose of the IP coding system
ii) level of protection provided by IPXXB
iii) level of protection provided by IP4X.
i. Level of protection against solids and moisture.
ii. BS finger to a depth of80 mm
iii. 1 mm wire