9 kW Open Flue boiler, What is the ventiliation requirement?
Check the data badge, take away 7 kW for adventitaious air and multiply the the remaining 2 kW by 5. Answer is 10 cm2 Ventilation required and an openable window/door leading to the outside.
5 kW Open Flue boiler, What is the ventiliation requirement?
Below 7 kW so adventitious air eliminates the the need for ventilation requirements.
28 kW Room sealed boiler within a compartment ventiliated to the outside, what are the ventiliation requirements?
Top Vent: 28 kW x 5 cm2
Bottom Vent: 28 kW x 5 cm2
18 kW Open Flue boiler within a compartment, ventiliated via an internal room, what are the ventiliation requirements?
Top Vent: 18 kW x 10 cm2 = 180 cm2
Bottom Vent: 18 kW x 20 cm2 = 360 cm2
As we are ventilating to an internal room, a vent is required for combustion air direct from outside.
Effective free area of vent = 18 kW - 7 kW
= 11 kW x 5 cm2
= 55 cm2
9 kW Open Flue boiler within a compartment, ventiliated to the outside, what are the ventiliation requirements?
Top Vent: 9 kW x 5 cm2 = 45 cm2
Bottom Vent: 9 kW x 10 cm2 = 90 cm2
As the compartment ventiliation is direct to outside, no further requirement for additional combustion ventiliation.
What are the flamability limits of Natural Gas?
5-15 %
What is the minimum distance that copper pipe should be from an electrical socket or light switch?
25 mm
Minimum distance that the gas meter should be from a fuse box?
150mm
Unsafe Situations for a flueless cooker?
Cooker bayonet to have a clean U bend looking downwards and be 750 mm distance above the ground level.
Does the cooker have a chain if it is isolated?
The safety lid works properly.
Overall good condition of the appliance?
No water fitting used for cooker pipework?
Not installed in a bathroom.
Correct ventilation?
What is the minimum distance a flue should be from a window?
300mm
How often should a flue be supported?
Every 1.8m
How often should a room sealed boiler be supported?
Every 2m
How far should the guard be from the terminal?
50mm
Where should a carbon monoxide alarm be located?
Between 1m and 3m from the appliance.
Where should the carbon monoxide be if wall mounted?
1.5m from floor level and at least 150 mm below the ceiling but highier than any window or door within the room.