Operations Flashcards
SNLNE Sequence 1
Initial condition OK
SNLNE Sequence 2
Apply Brakes
Unit Cooling sys starte
GSU trf oil station started
Carbon dust exhauster started
Oil injection system started
Oil mist exhauster started
SNLNE Sequence 3
Gov oil station started
MIV oil station started
SNLNE Sequence 4
MIV opening Sequence as follows
1. Activate complete opening TLTE > MIV oil station on > Wicket gate opened
2. Open By pass valve
3. MIV open
4. CLose By pass valve
5. Reset complete opening TLTE
SNLNE Sequence 5
Brakes released
No braking residual press
SNLNE Sequence 6
Turbine speed > 90%
SNLNE Sequence 7
Turbine safety device in service
Oil injection sys stopped
SNLE Sequence 8
Excit FB closed & not open
Excit power factor regul off
Gen nominal voltage
SNLE Sequence 9
Synchro auto selected
Unit CB closed & not open
SNLE Sequence 10
Excit power factor regul ON
NSD 1
Speed Gov pulse ctrl mode off
wicket gate opening < SNL
NSD 2
Unit CB open & not closed
NSD 3
Excit FB open & not closed
NSD 4
Stop governor
Seq closing MIV
Turbine speed <90%
NSD 5
Injection sys started
Tur safety device out of service
Wicket gate closed
Turbine speed < 15%