OP-2 Flashcards

1
Q

Is OP-2 the regulation

A

Yes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Who ensures appliance with OP-2 annually?

A

POC branch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the form filled out jointly by the worker and operations supervisor?

A

Equipment request order form

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Statement from operations supervisor Permitting work on or near energized equipment they may not require deenergizing for a worker do to safely perform work?

A

OK to Work

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Who issues OK to work and clearances?

A

Operations supervisor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is a worker?

A

Person who is authorized To work under clearances and receive OK to works

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When locking onto a yellow box what must the worker do?

A

Use the lockbox sign on and sign off sheet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

POC branch is responsible for?

A

Preparation review and updating of attachments for OP-2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Who is responsible for resolving conflicts?

A

POC manager

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Is OP-2 training required for new employees or transfers

A

Yes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If a source or hazardous energy cannot be effectively isolated who will approve the established procedure?

A

Branch manager and field division manager

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

EROF will include specific placement of protective grounds between all sources of hazardous energy and work

A

Bracket grounds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The only document of switching operations should be done on?

A

Switching order form

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How are deletions made on a switch in order for?

A

Strike out line with blue or black pen and initialed and dated by the operations supervisor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Any switching that involves repositioning any energy isolation with 600 V or greater should be completed with?

A

Two switch persons

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What must you check instead of indicating lights on a circuit breaker?

A

The position indicator on the breaker

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

If there are issues on switching or questions they should be resolved when and with who?

A

Prior to switching and with the operations supervisor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

If an issue occurs during switching and device is in wrong position then what do you do?

A

Do not proceed any further, recheck and speak with operations supervisor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Operations locks are single keyed and what color?

A

Red

20
Q

Workers locks are what color?

A

Blue

21
Q

Operations supervisor and contractor locks are what color?

A

Orange

22
Q

Who checks the effectiveness of the clearance?

A

Switch person

23
Q

All workers must __ that the clearance limits are in safe position

A

Personally verify

24
Q

After Switching is complete, the operation supervisor prepares to issue the clearance to who?

A

The clearance holders who will then walk it and verify points

25
Q

If grounds are on the equipment request order form, electricians are:

A

First to sign on and last to sign off

26
Q

How does the clearance holder place locks and keys if people are working under them?

A

Place is the lock on the clearance box and places that key into the yellow box. Then place is another lock on the yellow box and holds the key for the remainder of the job

27
Q

Where do unqualified workers and apprentices place their locks and clearance?

A

Multilock hasp under authorized worker

28
Q

Where does the worker card go at the end of the day?

A

The switching center or central location

29
Q

In a temporary release all clearance holders must do what?

A

Report off the clearance

30
Q

What must you get an a temporary release to continue work?

A

OK to work

31
Q

When all crafts release their clearance besides electricians on a temporary release, protective grounds can be removed with an?

A

OK to work

32
Q

Who signed the workers card after verifying the status of the items on the card?

A

Switch person

33
Q

Do each agency participating in the enter connection maintain control of the jurisdiction?

A

Yes

34
Q

What is a document with one agency switching center to another that switching performed on a system is partial or complete for the other clearance?

A

Interconnected system clearance

35
Q

What is the contractor representative responsible for?

A

Maintaining accountability for each worker under the supervision in accordance to lockout tag out

36
Q

What does the project engineer place on equipment that is ready and excepted for testing and energizing?

A

Provisional acceptance tag

37
Q

Should a special conditions tag be used to protect personnel?

A

No

38
Q

Should a special conditions tag be used to provide permanent instruction on equipment?

A

No

39
Q

Is plastic tape allowed as a barricade?

A

No

40
Q

Is OP-2 in affect when a provisional acceptance tag is being placed?

A

Yes

41
Q

What are acceptable lock methods?

A

Zip ties, tie wrap, cable tie

42
Q

What do all switching order forms have?

A

Unique switching number

43
Q

 Group lockout needed for contractors go on?

A

Multilock hasp

44
Q

What are two things that can be used for an OK to work?

A

Blue lock and danger tag

45
Q

Who does annual audit to make sure people are complying with OP-2?

A

POC branch