official flash cards construction seminars
Nonshielded conductors over 750V
shall be _____
Grounded
What is the minimum distance that is
allowed between switchgear and an
outdoor oil storage tank?
10 ft
What is the minimum vertical separation
on a pole between the supply cable and
the lowest communication attachment?
16”
The vertical clearance for insulated
communication conductors above or
crossing railroad tracks shall be ___feet.
23.5
Minimum clearance for non-insulated
communication conductors over
pedestrian walkways shall be ____ feet.
12
Minimum clearance of open supply
conductors over 750V to 22KV crossing
over bridges shall be ____ feet.
5.5
The minimum vertical clearance between
ordinary supply conductors over 8.7 kV and
communication conductors shall be
____inches.
40 plus .4 per kV over 8.7 kV
Backfill within 6” of conduit should be
free of solid material greater than ____
maximum dimension.
4”
In underground structures, horizontal runs
of supply cables shall be supported at least ____
above the floor.
3”
What is the minimum burial depth for
a 22 kV conductor?
30”
What is the minimum flush burial
depth of a 500 volt conductor?
24”
Bonding shall be provided between all
above ground metallic power and
communications apparatus that are
separated ____ or less.
6 ft
According to the NESC, fall protection is required for over ___feet of elevation.
10
A buried ___ shall be used to bond across a gate, unless a
nonconducting fence section is used.
bonding jumper
Where guarding is required, grounding
conductor guards should extend for not
less than feet above the ground or
platform from which the grounding
conductors are accessible to the public.
8
Strips of metal not less than____ in total length constitute an acceptably made electrode.
10 ft
In areas with high soil sensitivity or shallow bedrock, buried strips of metal not less than in total length, constitute an acceptably made electrode.
10 ft
Pole butt plates shall not be less than thick.
1/4”
Copper wire wrap shall have a continuous bare length below the
ground level not less than___ feet.
12
Copper wire wrap shall not be smaller than ___
6 AWG
Minimum overhang for insulated communication conductors over roads and parking lots shall be feet.
15.5
The supplier or contractor that installs house fire warning is required to provide the building owner with all the following materials except:
drawings that show the interconnection of tandem connected detectors
On a beam ceiling where the beams are less than 12” in depth and spacing is less than 96”, where should the smoke detectors be mounted?
bottom of beam
The maximum air velocity for a smoke detector is ____
300 fpm