OCB Allis Chalmers Flashcards
1
Q
Type
A
BZO-160-161J
2
Q
Amps
A
1200
3
Q
Volts
A
161KV
4
Q
Impulse insulation level
A
750KV
5
Q
Interrupting amps at rated volts
A
12,500
6
Q
Interrupting capacity
A
35MVA
7
Q
Operator type
A
Pneumatic type PN-700
8
Q
Normal pressure
A
130
9
Q
Motor on
A
120
10
Q
alarm on
A
105
11
Q
alarm off
A
110
12
Q
lock out
A
90
13
Q
lock out reset
A
100