non-class 1E AC power. Flashcards
1
Q
what is the purpose of the non 1E AC power system and what voltages are distributed?
A
provide a realiable source of power for non-safety related plant auxiliary loads.
* 7.2KV
* 4.16KV
* 480VAC
* 208/120VAC
2
Q
what happens if a flashing 4160V 1E breaker is pressed?
A
it will go solid and prevent the diesel from loading to that bus.
3
Q
what are SLP 1 & 2 used for?
A
lighting & switching.
4
Q
what are SLP 3 & 4 used for?
A
the ring bus.
5
Q
what happens upon a loss of power (normal AC) to UPS?
A
alternate DC is selected, then backup AC is the last option.
6
Q
what are the non-1E AC loads?
A
- NSSS computer
- security system
- PA system
- standby lighting
- BOP computer
7
Q
what causes a station service transformer lockout?
A
- any breaker supplied from the transformer is tripped and their closing circuit is blocked
- the alternate bus power supply breaker is closed and automatic transfer is blocked
- transformer cooling fans and oil pumps stopped
- the 13.8KV bus section is isolated