NH TRIPS Flashcards
NH Recycle Gas Flow to Heater - FAL
NH-FT-621 B/C - 2250 MSCFD
NH Recycle Gas Flow to Heater - FALL (2oo2)
NH-FT-621 B/C - 1400 MSCFD
NH Charge Flow to Heater - FAL
NH-FT-617 B/C - 2000 BPD
NH Charge Flow to Heater - FALL (2oo2)
NH-FT-617 B/C - 1000 BPD
NH RFG to Charge HTR Burners - PAHH - (2oo2)
NH-PT-690 B/C - 40 PSIG
NH RFG to Charge HTR Burners - PAH - (2oo2)
NH-PT-690 B/C - 35 PSIG
NH RFG to Charge HTR Burners - PAL - (2oo2)
NH-PT-690 B/C - 1.25 PSIG
NH RFG to Charge HTR Burners - PALL - (2oo2)
NH-PT-690 B/C - 0.25 PSIG
NH PILOT GAS to Charge HTR Burners - PAHH - (2oo2)
NH-PT-115 B/C - 15 PSIG
NH PILOT GAS to Charge HTR Burners - PAH - (2oo2)
NH-PT-115 B/C - 12 PSIG
NH PILOT GAS to Charge HTR Burners - PAL - (2oo2)
NH-PT-115 B/C - 2 PSIG
NH PILOT GAS to Charge HTR Burners - PALL - (2oo2)
NH-PT-115 B/C - 1 PSIG
NH Flow to Stripper Reboiler Heater - FAL
NH-FT-617 B/C - 7500 BPD
NH Flow to Stripper Reboiler Heater - FALL (2oo2)
NH-FT-617 B/C - 5625 BPD
NH RFG to Reboiler HTR Burners - PAHH - (2oo2)
NH-PT-689 B/C - 40 PSIG
NH RFG to Reboiler HTR Burners - PAH - (2oo2)
NH-PT-689 B/C - 35 PSIG
NH RFG to Reboiler HTR Burners - PAL - (2oo2)
NH-PT-689 B/C - 1.25 PSIG
NH RFG to Reboiler HTR Burners - PALL - (2oo2)
NH-PT-689 B/C - 0.75 PSIG
NH PILOT GAS to Reboiler HTR Burners - PAHH - (2oo2)
NH-PT-148 B/C - 15 PSIG
NH PILOT GAS to Reboiler HTR Burners - PAH - (2oo2)
NH-PT-148 B/C - 12 PSIG
NH PILOT GAS to Reboiler HTR Burners - PAL - (2oo2)
NH-PT-148 B/C - 2 PSIG
NH PILOT GAS to Reboiler HTR Burners - PALL - (2oo2)
NH-PT-148 B/C - 1 PSIG
NH Recycle Gas Compressor Suction Drum - LAHH (2oo2)
NH-LT-634 B/C - 90 %
NH Recycle Gas Compressor Suction Drum - LAH
NH-LT-634 B/C - 80 %