NFPA 13 Flashcards

1
Q

All automatic sprinkler systems have which of the following characteristics in
common?
A. Water supply
B. Piping network
C. Sprinklers
D. Each of the above

A

Each of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

In a dry pipe system, the pipes can contain air or what other element under
pressure?
A. Argon
B. Nitrogen
C. Hydrogen
D. Xenon

A

Nitrogen

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

In a differential dry pipe valve system, the air must be maintained at least how
many psi greater than the trip pressure?
A. 20
B. 15
C. 10
D. 5

A

10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When debris in the water is a problem, you should use what type of dry pipe
valve?
A. Low differential
B. High differential
C. Mechanical
D. Latched clapper

A

Mechanical

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What type of automatic sprinkler system should you use in an aircraft hangar?
A. Wet pipe
B. Semidry pipe
C. Water deluge
D. Semi-wet pipe

A

Water deluge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Pre-prime plugs blow out of the sprinklers at approximately what water pressure?
A. 25 psi
B. 20 psi
C. 15 psi
D. 10 psi

A

20 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Automatic sprinklers have orifices graduated in what size increments?
A. 1/2 inch
B. 1/4 inch
C. 1/8 inch
D. 1/16 inch

A

1/8 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A fusible link sprinkler is kept closed by a two-piece link fused together by what
type of metal?
A. Copper
B. Aluminum
C. Solder
D. Steel

A

Solder

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

A dry pendent sprinkler is used when the system is exposed to which of the
following conditions?
A. High ambient temperatures
B. Freezing temperatures
C. Explosive elements
D. Unstable chemicals

A

Freezing temperatures

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A dry pipe alarm system has which of the following characteristics?
A. It is slow acting.
B. It is moderate acting only.
C. It is fast acting only.
D. It is moderate or fast acting.

A

It is moderate or fast acting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The retard switch connected to the alarm port of a wet sprinkler system alarm-
check valve is normally set within what pressure range?
A. 10 to 20 psi
B. 8 to 15 psi
C. 6 to 15 psi
D. 4 t0 15 psi

A

6 to 15 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

In an electronic pressure-drop detector, an overpressure condition of what
magnitude can cause a trouble signal?
A. 250 psi
B. 200 psi
C. 150 psi
D. 100 psi

A

200 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

To prevent freezing of water in a fire protection system, a Utilitiesman normally
installs a supervisory device in a pipe or reservoir with what low water
temperature setting?
A. 40° F
B. 32° F
C. 25° F
D. 0° F

A

40° F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

At what interval should you inspect and test the general condition of sprinkler
heads and sprinkler systems?
A. Monthly
B. Quarterly
C. Annually
D. Every 3 years

A

Annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

At what interval should you inspect and test water flow alarms?
A. Weekly
B. Monthly
C. Quarterly
D. Annually

A

Quarterly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

At what interval should you inspect and test air and water pressure in dry pipe
systems?
A. Weekly
B. Monthly
C. Quarterly
D. Annually

A

Weekly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

At what interval should you inspect and test general condition of standpipe
systems?
A. Weekly
B. Monthly
C. Quarterly
D. Annually

18
Q

At what interval should you inspect and test general condition of hydrants?
A. Monthly
B. Quarterly
C. Annually
D. Every 3 years

19
Q

At what interval should you inspect and test water level in tanks?
A. Weekly
B. Monthly
C. Quarterly
D. Annually

20
Q

What minimum distance must be maintained beneath a sprinkler for proper water
distribution?
A. 48 inches
B. 36 inches
C. 24 inches
D. 18 inches

21
Q

What type of test should be performed quarterly to test the alarm-check valves?
A. 8-inch drain test
B. 6-inch drain test
C. 4-inch drain test
D. 2-inch drain test

A

2-inch drain test

22
Q

When testing a water clapper valve designed to trip at a fixed pressure of 10 to
15 psi, you should maintain what minimum air pressure on this valve?
A. 60 psi
B. 45 psi
C. 30 psi
D. 15 psi

23
Q

When performing a basic inspection of accelerators and exhausters, you should
check what pressure?
A. Water
B. Air
C. Centrifugal
D. Atmospheric

24
Q

When testing deluge and pre-action valves, you should perform the 2-inch drain
test at what time interval?
A. Weekly
B. Monthly
C. Quarterly
D. Annually

25
Q

When performing a deluge valve dry trip-test in a flammable area, you should
use what test in place of the electric test set?
A. Infrared light
B. Hot water only
C. Hot cloth only
D. Hot water or hot cloth

A

Hot water or hot cloth

26
Q

When performing the cathodic protection test with an ammeter, you notice a
diminishing current flow. This is an indication of what type of problem?
A. Failing electrodes
B. Blown fuses
C. Frozen electrodes
D. Broken ground wires

A

Failing electrodes

27
Q

Under normal circumstances, full operational testing of high-speed suppression
systems should be conducted at intervals not to exceed how many years?
A.7
B.5
C.3
D.1

28
Q

What characteristic of carbon dioxide makes it desirable for use on electrical
fires?
A. High-pressure application
B. Electrical conductivity
C. Electrical non-conductivity
D. Low-pressure application

A

Electrical non-conductivity

29
Q

What is the normal cylinder pressure in a high-pressure system?
A. 600 psi
B. 500 psi
C. 400 psi
D. 300 psi

30
Q

In a low-pressure system, liquid carbon dioxide should always be maintained at
what constant (a) pressure and (b) temperature?
A. (a) 300 psi (b) 0°F
B. (a) 300 psi (b) 32°F
C. (a) 200 psi (b) 32°F
D. (a) 200 psi (b) 0°F

A

(a) 300 psi (b) 0°F

31
Q

High-pressure systems require approximately how many pounds of equipment
for every pound of carbon dioxide stored?
A.7
B.5
C.3
D.1

32
Q

Pipe and fittings in a high-pressure system have what minimum bursting
pressure in psi?
A. 7,000
B. 5,000
C. 3,000
D. 2,000

33
Q

Pipe and fittings in a low-pressure system have a minimum bursting pressure of
how many psi?
A. 3,000
B. 2,800
C. 2,000
D. 1,800

34
Q

What automatic device should be installed along with a total flooding system to
conserve carbon dioxide?
A. Closing
B. Venting
C. Door closure
D. Electrical lockout

A

Electrical lockout

35
Q

Installation of a new Halon 1301 system is prohibited without special approval
from whom?
A. NAVFACENGCOM
B. EPA
C. ROICC
D. Base fire chief

36
Q

Regardless of the method being used, what device must be attached to the
releasing mechanism?
A. An auxiliary fan
B. A control valve
C. A light
D. An alarm

37
Q

At what maximum time interval should you replace the frangible disks on low-
pressure storage tanks?
A. 12 years
B. 8 years
C. 7 years
D. 5 years

38
Q

What type of system can be used with dry chemicals?
A. Total flooding
B. Local application
C. Hose line
D. Each of the above

A

Each of the above

39
Q

What is the most widely used dry chemical?
A. Nitrogen
B. Sodium bicarbonate
C. Monoammonium phosphate
D. Potassium phosphate

A

Monoammonium phosphate

40
Q

Dry chemicals are used primarily on what type of fires?
A. Flammable liquid
B. Cellulose nitrate
C. Dry wood
D. Delicate electrical equipment

A

Flammable liquid

41
Q

Dry chemical distribution systems are constructed of what schedule of pipe?
A. 40
B. 30
C. 20
D. 10