NEC Test Flashcards
What does “FLC” mean?
Full load current
An electrical device that consists of a frame, a plunger and uses an up and down motion to operate is
called what?
solenoid
Types of equipment grounding conductors?
Rigid metal conduit and Electrical metal tubing
250.118 Types of Equipment Grounding Conductors
What is the cross-sectional area in circular mils of a solid wire with diameter of 0.102?
10,380
Table 8 Conductor Properties
A restaurant has a 15.5-foot plug strip for all their television systems which are likely to be used at
the same time. What is the VA?
2880
220.14 Other Loads — All Occupancies
An apartment has 8 water heaters at 800 watts, what is the VA?
6400
422.13 Storage-Type Water Heaters.
What is the expansion rate of 500 feet of type RTRC. That goes from a temperature change of 80 (F)
degrees to 50 (F) degrees?
2.7
Table 355.44
240 volts to ground, 200 amp panels in condition 3 needs a minimum front clearance of?
4 ft
Table 110.26(A)(1) Working Spaces
What is the minimum clearance in front of a service panel?
3 ft
Table 110.26(A)(1) Working Spaces
The width of the 120/ 240 volt panel working area shall be a minimum of __inches, and the door shall
be open, able to at least 90°.
30 inches
110.26 Spaces About Electrical Equipment
Manhole covers shall have a minimum weight of?
100 lbs
110.73 Equipment Work Space
A 240-volt boat hoist receptacle has to be?
GFCl protected
210.8 Ground-Fault Circuit-Interrupter Protection for Personnel
What is the minimum rating for a laundry circuit in a single family dwelling?
20 amps 1500 watts
220.52 Small-Appliance and Laundry Loads — Dwelling Unit
A receptacle on an individual branch circuit can be rated for what percent?
100%
210.21 Outlet Devices
What size branch circuits shall supply only non-lighting loads?
Larger Than 50 Amperes
210.23 Permissible Loads, Multiple-Outlet Branch Circuits
What type of lamp holder shall be connected to a load in excess of 20 amps?
Heavy duty
210.21 Outlet Devices
The laundry outlet shall be installed within how many feet of the designated appliance location?
6 ft
210.50 General
Receptacle outlet in the floor shall not be counted as part of the required number of wall receptacle
outlets unless located within how man inches of the wall?
18 inches
210.52 Dwelling Unit Receptacle Outlets
What is the minimum number of small appliance circuits for a single-family dwelling?
2 circuits
210.11 Branch Circuits Required
Other than counter-top appliances, what type of device is allowed to utilize the small appliance
circuits in a single family dwelling?
small-appliance branch circuits
required by 210.11(C)(1) shall serve all wall and floor recepta‐
cle outlets covered by 210.52(A)
Receptacle outlets shall be installed so that no point along the wall line of a kitchen countertop is
more than __inches measured horizontally from a receptacle outlet in that space.
24 inches
210.52 Dwelling Unit Receptacle Outlets
What is the minimum length of a countertop in a kitchen that requires the installation of a receptacle?
12 inches
210.52 Dwelling Unit Receptacle Outlets
Island counter tops, with a minimum dimension of 12” W x 24” D, must have at least __
receptacle outlet.
1
210.52 Dwelling Unit Receptacle Outlets
18 feet of show window requires how many receptacles above the window?
1
210.62 Show Windows
What is the maximum distance from a rooftop unit that the rooftop GFCI service receptacle shall be
located?
25 ft
210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet.
A conference room is 250 sq. ft and has a 12.5-foot wall. How many floor receptacles are needed?
1
210.71 Meeting Rooms.
Does a vehicle garage door (OUTSIDE) require illumination under the illuminated entryway rule?
No
210.70 Lighting Outlets Required.
General branch circuit lighting load for a hospital shall be calculated at __watts per square foot?
2 watts
Table 220.12 General Lighting Loads by Occupancy
In dwelling units, new additions to the lighting branch circuit shall be calculated in accordance with
220.12 when over __ square feet.
500
220.16 Loads for Additions to Existing Installations.
Where SE cable enters the building, the conduit has to be?
Sealed
230.8 Raceway Seal
The conductors for festoon lighting shall be supported by messenger wire in all spans exceeding?
40 ft
What is the minimum service rating for a single-family dwelling with 6 or more 2 wire branch
circuits?
100 amps
230.79 Rating of Service Disconnecting Means.
Circuit breakers used as switches in 120-volt fluorescent lighting shall be marked as?
SWD and HID
240.83 Marking.
What is the minimum height of a service entrance conductor above a pedestrian sidewalk?
10 ft
230.24 Clearances
What is the maximum number of disconnects at the main service?
6
230.71 Maximum Number of Disconnects.
What is the minimum service disconnect of a commercial building?
60 amps
230.79 Rating of Service Disconnecting Means.
What cannot be connected to the supply side of a service disconnect.
230.82 Equipment Connected to the Supply Side of Service
Disconnect
When fuses serve as overcurrent protection, a disconnecting means shall be supplied on the line side
of all fused circuits that exceed 150 volts if the fuses are accessible to who?
Qualified personnel
240.40 Disconnecting Means for Fuses
Edison base fuse holders shall be a maximum of what voltage?
125 volts
240.51 Edison-Base Fuses.
Edison base fuses shall not operate at over?
30 amps
240.51 Edison-Base Fuses.
A type S fuse is installed in an Edison base fuse holder for what primary reason?
Non-interchangeable
A grounding electrode conductor may be spliced together by?
Splicing of the wire-type grounding electrode conductor
shall be permitted only by irreversible compression-type
connectors listed as grounding and bonding equipment
or by the exothermic welding process.
The green screw in a main panel enclosure serves as what?
Main bonding jumper
250.28 Main Bonding Jumper and System Bonding Jumper
High impedance ground systems operate at a minimum of what voltage?
480 volts
250.36 High-Impedance Grounded Neutral Systems.
A concrete encased electrode with electrically conductive coated steel reinforcing bars shall be at
least __ in diameter and a minimum of 20 feet in continuous length.
1/2 inch
What is the minimum size wire for a ground ring?
2 AWG
How many feet of a rod electrode be in contact with the earth?
8 ft
250.53 Grounding Electrode System Installation
A ground rod shall be at least how many inches in diameter?
5/8 inch
250.52 Grounding Electrodes.