The term “rainproof” is typically used in conjunction with enclosure type(s) _____.
NEMA 3R and 3X
Raintight enclosures include
types 3, 3S 3SX, 3X, 4, 4X, 6, and 6P
Rainproof enclosures are types
3R and 3RX
Watertight enclosures are types
4, 4X, 6, and 6P
Table 110.28 Informational Note No. 1
Driptight enclosures are types
2, 5,12,12K, and 13.
Dustight enclosures are
types 3, 3S, 3SX, 3X, 4, 4X, 5, 6, 6P, 12, 12K, and 13
Define approved
Acceptable to the authority having jurisdiction
What word means acceptable to the authority having jurisdiction
approved
Define Identified (as applied to equipment)
Recognizable as suitable for the specific purpose, function, use, environment, application, and so forth, where described in a particular code requirement
what does it mean to be recognizable as suitable for the specific purpose, function, use, environment, application, and so forth, where described in a particular code requirement
Identified (as applied to equipment)
Define Labeled
Equipment or materials to which has been attached a label, symbol, or other identifying mark of an organization that is acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer indicated compliance with appropriate standards or performance in a specified manner
What does it mean to be equipment or materials to which has been attached a label, symbol, or other identifying mark of an organization that is acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer indicated compliance with appropriate standards or performance in a specified manner
Labeled
Define listed
Equipment, materials or services included in a list published by an organization that is acceptable to the authority having jurisdiction and concerned with evaluation of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, materials or service meets appropriate designated standards or has been tested and found suitable for a specified purpose
What does equipment, materials or services included in a list published by an organization that is acceptable to the authority having jurisdiction and concerned with evaluation of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, materials or service meets appropriate designated standards or has been tested and found suitable for a specified purpose mean?
Listed
Installations of communications equipment under the exclusive control of communications utilities located outdoors or in building spaces used exclusively for such installations _____ covered by the NEC. (Are, Are sometimes, Are not, may be)
Are not
Underground cable and conductors installed under a building shall be _____.
in a raceway 300.5(C)
The minimum cover requirement for Type UF cable that supplies a 120V, 15A GFCI-protected circuit under a driveway of a one-family dwelling is _____.
12 in. Table 300.5(A) column 4
Where can you find minimum cover requirements for raceways and conductors for circuits rated 1000 Volts or lower?
Table 300.5A
Wiring located within the cavity of a fire-rated floor-ceiling or roof-ceiling assembly shall not be secured to, or supported by, the ceiling assembly, including the ceiling support _____. (wires, hangers, rods, none of these)
wires 300.11(B)(1)
Where Type NM cables pass through cut or drilled slots or holes in metal members, the cable shall be protected by _____ which are installed in the opening prior to the installation of the cable and which securely cover all metal edges. (anti-short devices, sleeves, plates, listed bushings or grommets)
listed bushings or grommets 300.4(B)(1)
What table can you find conductor applications and insulation rated 600 Volts?
Table 310.4(1)
The minimum working space on a circuit for equipment operating at 120V to ground, with exposed live parts on one side and no live or grounded parts on the other side of the working space, is _____.
3 ft