NC RfG Flashcards
Req’d ROCOF of STG.
2 Hz/sec
FRT for 0% voltage
150 msec
FRT for 50% voltage
450 msec
FRT for 85% voltage
1.5 sec
Is there any difference between FRT for symmetrical vs asymmetrical faults?
No
What is the basis for 150 msec fault clearing time?
Entsoe Implementation Guideline
What is the basis for 250 msec clearance time?
150 mesc Entsoe guideline and assuming a breaker failure.
How does the PLU work?
Difference between turbine exhaust steam pressure and generator current. > setpoint, it closes the steam valves to prevent overspeed.
What is the meaning of Critical Fault Clearing Time?
Clearing time during which the generator is not out-of-step (i.e. - it’s OK)
How does Critical FCT vary with grid SC availability?
Lower SC = lower critical FCT.
IEC standard continuous allowable frequency variation?
+ / - 2% = 49 to 51 Hz
What is the POI voltage range?
87.5% to 110%
Does Poland AP1000 have to abide by 250 Msec FCT?
According to the NCRfG, it is only 150 msec.