MustNo's Flashcards

1
Q

A Restaurant has a 15.5 ft plug strip for their TV’s, which are likely to be used at the same time. What is the VA?

A

2880 VA
feet/1 (since it’s likely), then round up = 15.5/1 = 16… * 180VA = 2880VA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A Restaurant has a 15.5 ft plug strip for their TV’s, which are unlikely to be used at the same time. What is the VA?

A

since unlikely, use 5 as denominator, round up
feet/5 )since it’s unlikely), then round up = 15.5/5 = 4…* 180VA = 720va

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the expansion rate of 500ft type RTRC that goes from a temp change of 80 F to 50 deg F?

A

355.44
delta T consonant * ft / 100 = rate
temp change = 30 F, rate from table = .54/100 * 500 = 2.7… look up rate in
one Q on expansion…

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Manhole covers shall have a min weight of?

A

100 lbs
110.26A2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the min rating for a laundry circuit in a single family dwelling?

A

20 amp 1500 watts
210.11C2, 220.12J, 220.52B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

18 feet of show window requires how many receptacles above window?

A

2
below 18=1, 18 or above = 2
mincode/2 + mincode = 12/2 + 12 = 18
210.62

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A conference room is 250 sq ft and has a 12.5-foot wall. How many floor receptacles are needed?

A

1
less than 322.5ft = 1, everything else = 2…
mincode/2 + mincode= 215/2 + 215 = 322.5
210.71(b)(2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Circuit breakers used as switches in 120-volt florescent lighting shall be marked as?

A

SWD and HID
(only for florescent lighting)
240.83D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the minimum height of a SE conductor rated 600volts going above a pedestrian walkway?

A

15 feet
230.24(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Edison based fuses shall not operate at over how many amps?

A

30 amps
240.51A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What cannot be connected to the supply side of a service disconnect?

A

230.82 1-9

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the minimum size copper-clad grounding electrode conductor needed for a 200 amp single phase dwelling copper feeder?

A

2 awg
83% rule…100-400amp……multiple by 83%… 200 * .83 = 166A…
Pg150…feeder over 100A so use 75deg copper…2.0 copper feeder = 2awg copper clad ground pg 116
2awg on table 250.66

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the min size wire needed to supply a 100-amp single phase 3 wire main serbicve on a mobile home?

A

4 copper

100 * .83 = 83…use 75 deg… = #4 copper
310.15(b)(7)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A single-family dwelling unit has a 100-amp service. What size feeder will be required to supply a 75-amp electric space hater and a 25-amp air conditioner?

A

2

310.15(b)(16)
Non coincidental loads so use largest = 75A…feeder less than 100 = 60 deg column = #2 copper

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Type NM cable shall ber approved for installing under the lowder edges of joist in crawspaces if the wire is at least _____ size

A

3x8AWG or 2x6AWG
334.15(c)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Type NM cable shall be secured how many inches from a non-metallic box if there is no clamp?

A

8 inches
314.17C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

Type NM cable shall be secured how many inches from a metallic box if there is no clamp?

A

12 inches
314.17C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Light poles shall have a handhole of not less than ____

A

2” x 4”
410.30.B.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What type of cable does a garbage dispisal cord have to be made of?

A

422.16(B)(1)
listed for use

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

By what percent is the FLC of a wound rotor motor multiplied to determine the motor’s minimum OCPD using inverse time breaker?

A

150%
430.52

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What is the maximum surface temperature of T2A?

A

536
500.8C (masters)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Where do you need a tamper-proof receptacle?

A

Elementary schools

23
Q

where don’t you need a tamperproof receptacle?

A

high schools

24
Q

Car wash recept is rated for what type of location?

A

Wet location

25
An outdoors gasoline dispensing device up to 18” above grade level within 20” horizontally of any edge of the enclosure is ____?
class I division II 514.3(b)(1)
26
In gas stations, how far from the floor up is class 1 div 1?
18 in 514.3(b)(1)
27
In health care facilities, the EM light circuit shall be wired on the ___
life safety branch circuit 517.32A
28
In general care areas, each patient bed location shall be provided with a min of ___ receptacles.
8 517.18b
29
In critical care areas, each patient bed location shall be provided with a min of ___ receptacles.
14 517.18b
30
Key things to know from chapter 5 especially
recreational vehicles, ventilation areas
31
Indoor receptacles for an electric vehicle charging station shall be mounted at a minimum height of?
18 inches 625.50
32
Outdoor receptacles for an electric vehicle charging station shall be mounted at a minimum height of?
24 inches 625.50
33
For photovoltaic systems, what cannot be connected to the supply side?
non-overcurrent light (device)
34
Key things to know especially in chapter six
office furnishings, x-ray equipment, solar photovoltaic systems, electric vehicle charging stations, swimming pools
35
Key article to know for office furnishings free standing cord and plug
605.9a-d
36
How many #8 THHW compact conductors can be placed inside of 1” EMT trade size conduit?
6 Annex C table C.1A Compact
37
What size RMC pipe is needed for total square inch area (include insulation) of (4) #8 THHN and (6) #10 THHN wires?
1 inch table 4 and table 5…. #8 thhn = .0366 * 4 …. #10 thhn = .0211 * 6….. table 4, over two wire 40% = 1 inch Watch out for nipples…use 60% for nipples
38
How many #10 RHW* conductors can be placed inside of 1” ENT pipe?
10 annex C table c.2
39
A ___ or ___ can pull a permit and be responsible for the work on a single-family dwelling
homeowner, electrical contractor codesec
40
17 feet show window require how many receptacles above window?
Below 18=1 210.62
40
Conference room 12.5 sq ft wall, 323 sq feet, how many floor receptacles?
less than 322.5ft = 1, everything else = 2… mincode/2 + mincode= 215/2 + 215 = 322.5
41
Key things ch 6
Office furnishings, X ray equip, solar photovoltaic, ev charging, swimming pools
42
Rules for feeders and services (dwellings only)
Take amps and multiply by 83% Feeders: 100A or less, use 60 deg column Over 100A use 75 deg Service: always 75 deg Use 90 deg only if lugs and wires are rated
43
Can you run two service panels on one meter?
Yes, if off line side of main -has to be underground
44
Feeders to adjacent buildings
225.30… know this
45
Power formula and ohms law for 3 phase
Multiply voltage by 1.73 first
46
Straight pull box multiplier
8x
47
Angled pull box multiplier
6x
48
Voltage drop formula
2RAD/1000 #wires*Distance *amps*Ohms/1000 Ch9 table 8
49
3 phase voltage drop
Distance *#wires*amps*ohms*.866/1000 Ch9 table 8
50
Copper clad is the same as
Aluminum wire
51
Key things motors
Conductor rating = 125% Disconnect rating = 115% Overcurrent protection = 430.52 Efficiency formula = watts/(volts*amps*power factor) 746watt=1hp
52
OC protection for motor
430.52