A Restaurant has a 15.5 ft plug strip for their TV’s, which are likely to be used at the same time. What is the VA?
2880 VA
feet/1 (since it’s likely), then round up = 15.5/1 = 16… * 180VA = 2880VA
A Restaurant has a 15.5 ft plug strip for their TV’s, which are unlikely to be used at the same time. What is the VA?
since unlikely, use 5 as denominator, round up
feet/5 )since it’s unlikely), then round up = 15.5/5 = 4…* 180VA = 720va
What is the expansion rate of 500ft type RTRC that goes from a temp change of 80 F to 50 deg F?
355.44
delta T consonant * ft / 100 = rate
temp change = 30 F, rate from table = .54/100 * 500 = 2.7… look up rate in
one Q on expansion…
Manhole covers shall have a min weight of?
100 lbs
110.26A2
What is the min rating for a laundry circuit in a single family dwelling?
20 amp 1500 watts
210.11C2, 220.12J, 220.52B
18 feet of show window requires how many receptacles above window?
2
below 18=1, 18 or above = 2
mincode/2 + mincode = 12/2 + 12 = 18
210.62
A conference room is 250 sq ft and has a 12.5-foot wall. How many floor receptacles are needed?
1
less than 322.5ft = 1, everything else = 2…
mincode/2 + mincode= 215/2 + 215 = 322.5
210.71(b)(2)
Circuit breakers used as switches in 120-volt florescent lighting shall be marked as?
SWD and HID
(only for florescent lighting)
240.83D
What is the minimum height of a SE conductor rated 600volts going above a pedestrian walkway?
15 feet
230.24(B)
Edison based fuses shall not operate at over how many amps?
30 amps
240.51A
What cannot be connected to the supply side of a service disconnect?
230.82 1-9
What is the minimum size copper-clad grounding electrode conductor needed for a 200 amp single phase dwelling copper feeder?
2 awg
83% rule…100-400amp……multiple by 83%… 200 * .83 = 166A…
Pg150…feeder over 100A so use 75deg copper…2.0 copper feeder = 2awg copper clad ground pg 116
2awg on table 250.66
What is the min size wire needed to supply a 100-amp single phase 3 wire main serbicve on a mobile home?
4 copper
100 * .83 = 83…use 75 deg… = #4 copper
310.15(b)(7)
A single-family dwelling unit has a 100-amp service. What size feeder will be required to supply a 75-amp electric space hater and a 25-amp air conditioner?
2
310.15(b)(16)
Non coincidental loads so use largest = 75A…feeder less than 100 = 60 deg column = #2 copper
Type NM cable shall ber approved for installing under the lowder edges of joist in crawspaces if the wire is at least _____ size
3x8AWG or 2x6AWG
334.15(c)
Type NM cable shall be secured how many inches from a non-metallic box if there is no clamp?
8 inches
314.17C
Type NM cable shall be secured how many inches from a metallic box if there is no clamp?
12 inches
314.17C
Light poles shall have a handhole of not less than ____
2” x 4”
410.30.B.1
What type of cable does a garbage dispisal cord have to be made of?
422.16(B)(1)
listed for use
By what percent is the FLC of a wound rotor motor multiplied to determine the motor’s minimum OCPD using inverse time breaker?
150%
430.52
What is the maximum surface temperature of T2A?
536
500.8C (masters)