Money Maker Packet - Chapter 3 and 4 Flashcards

1
Q

The minimum distance any edge of a stud must be from the edge of a hole for NM cable is?

A

1 1/4 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When direct burial cable exits the ground, it shall be enclosed in a raceway or enclosure extending to a level of ________ feet above grade.

A

8 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

At what rated voltage does direct-burial cable have to be shielded?

A

2000 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the smallest size conductor you can run in parallel?

A

1/0

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the minimum size wire needed to supply a 100-amp single phase, 3-wire main service on a mobile home

A

4 copper

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What type of conductor is rated for direct burial?

A

UF

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When using a round box where conductors or connectors requiring the use of locknuts or bushings are to be connected, to what part of the box can they not be connected?

A

Side of the box

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Type NM cable shall be approved for installation under the lower edges of a joist in crawlspaces if the wire is at least three _____ AWG

A

8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

A fixture box shall be independently supported if the fixture weighs more than how many pounds?

A

50 lbs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Floor boxes must be made of what?

A

UL listed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the maximum distance from a panel that a type MI cable must be secured?

A

6 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the temperature rating for the conductor type NM cable?

A

60 C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What type of cable is approved for service entrance cable used in underground installation?

A

USE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

8 feet of equipment grounding conductor cannot be made of what?

A

FMC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A general-use snap switch shall be connected to no more than what percentage of motor loads?

A

80%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Receptacles marked ______ are designed for the direct connection of aluminum conductors.

A

ALR

17
Q

What color triangle marking will be on a noise-canceling outlet?

A

orange

18
Q

Light poles shall have a handhole of not less than ______.

A

2” x 4”

19
Q

What is the minimum space between a recessed future and thermal insulation?

A

3 inches

20
Q

A furnace has to be run on what type of circuit?

A

Individual Branch Circuit

21
Q

Electrically operated kitchen waste disposers shall be permitted to be cord and plug connected with a flexible cord not more than how many inches and not less than how many inches?

A

36 and 18

22
Q

What type of cable does a garbage disposal cord have to be made of?

A

Listed for Use

23
Q

Branch circuits supplying two or more outlets for fixed electrical space heating equipment shall be rated for not over how many amps?

A

30 amps

24
Q

A conductor supplying a single motor used in varying duty applications shall have a minimum ampacity of _______ percent of the motor’s FLC?

A

110%

25
Q

Fuses are put on the current-carrying conductor as well as the grounded conductor if it is what type of motor feeder?

A

3-wire/ 3 phase

26
Q

By what percent is the FLC of a wound rotor motor multiplied, to determine the motor’s minimum OCPD using an inverse time breaker?

A

150%

27
Q

Disconnecting means for motor circuits rated 600 volts or less shall have an ampere rating not less than ____ percent of the FLC rating.

A

115%