Missed Questions Flashcards
100%
Calculate the voltage in the circuit when the total amperage is 20.4 amps and the resistors have values as follows: R1=10 ohms, R2=50 ohms, R3=20 ohms. (Parallel)
120 Volts
Volts = Amps / 1/R1 +1 ?R2 + 1/R3
Which of the following devices may be wired into the starting circuit of a single phase motor to improve the starting torque?
Start Capacitor
Another Winding
A single phase motor with an improved power factor, reduced motor current, increased efficiency and high starting torque is the
capacitor start-capacitor run (CSR) motor.
Correct. Because of the run and start capacitor, this motor offers the advantages listed above. The down side is additional cost.
In a CSR motor with a 10 microfarad run capacitor and a 110 microfarad start capacitor, the total capacitance will be
120 microfarads.
Correct. The capacitance of capacitors, when wired in parallel as in a CSR motor, are added together the same as resistors in a series circuit.
Which of the following reduced voltage starters uses a switching arrangement to connect the windings of three-phase motors in different configurations during startup and normal operation?
Star-delta starters.
Star & Wye are the same meaning
According to NEC (National Electrical Code), a general-use switch may be used as the controller for a stationary motor rated at two horsepower or less and at 300 volts or less if it is rated at not less than
twice the full-load motor current
A rather common indication of a defective starting relay in a single phase motor
is for the motor to hum but not start.
A type of current relay that uses a bimetal strip to open contacts in both the starting and running contacts is called a
hot-wire relay.
A pneumatic timing relay operates by
filling a bellows with air.
Correct. When energized, a bellows fills with air, which takes time. The time can be adjusted by a needle valve, which regulates the rate at which the bellows fills. When fully expanded, the bellows operates a snap-action switch.
The combination safety limit and fan control on a residential furnace turns the fan on and off by sensing the furnace air temperature. If the furnace temperature rises too high, the safety limit de-energizes the
gas valve.
Correct. The gas valve is shut off while the fan is allowed to continue running in order to cool the furnace.
Some codes require a manual reset device on a safety limit
so that the cause of the safety shutdown can be investigated prior to re-start.
A flow switch safety control is used to
prove that flow is occurring.
What is a disadvantage of the mercury bulb switch?
They must be level.
A thermostat is properly calibrated when
set point and control point are equal.
A pressure sensing device that relies on a fluid, such as oil, to provide a frictionless seal is the
inverted bell.
Correct. This device is suitable on only very low pressure, such as static pressure in an air duct, where pressures usually do not exceed several inches of water.
The photo cell in an infrared sensor is made of
lead sulfide.
Correct. Lead sulfide is a semiconductor having the property of decreasing in electrical resistance when exposed to radiation of certain wave lengths.
Aiming of infrared sensors is critical. Why must they be aimed directly at the flame?
Since they see heat, their sensitivity can be reduced by hot refractory.
A type of two-position control that provides for “intermediate” positions as well as the “all-on” and “all-off” positions is the
floating control.
While proportional control action has the disadvantage of control point shift but has no time-lag factor, floating action has the disadvantage of time lag influence but has no control point shift. What control action combines the advantages of both?
Proportional integral.
Checking amperage on a system during general maintenance
can indicate a problem with the system.
When changing or adding oil to a compressor
it is best to buy the smallest possible containers and use the entire contents at once.
avoid pouring the oil from a container into the compressor.
use an oil charging pump.
D. *all of the above. Correct.
As the evaporating temperature of any vapor compression system is lowered,
compressor capacity is lowered.
As a “rule of thumb”, for every 12,000 btuh of cooling capacity in an open compressor air conditioning system, the heat rejection is roughly
15,000 btuh, or 1.25 times the net refrigeration effect.
Correct. Like any rule of thumb, this number can vary. However, as a basis for estimation, it has long been considered that the heat rejection from an air conditioning system is about 15,000 Btuh for every 12,000 Btuh of cooling capacity. This assumes open-type compressors, where the refrigerant suction vapor does not receive any heat from the compressor motor as it does in hermetic motor-compressors.
The difference in temperature between condensing temperature and entering water or air temperature is known as
temperature split
Correct. The condensing temperature should be at least 15 or 20 degrees higher than the temperature of the entering water or air to avoid the need for an unreasonably large and costly condenser.
A decrease in condensing temperature will
decrease condensing pressure, decrease suction temperature and increase system capacity.
Subcooling in the condenser will
increase system capacity.
Correct. An increase in subcooling will increase the net refrigeration effect by reducing the flash gas loss.
Compressor capacity controlled by the cylinder unloading method
may result in compressor overheating
Correct. As fewer cylinders are used, less refrigerant is pumped resulting in less refrigerant vapor available for cooling the compressor.
10 in.Hg. vacuum is approximately equivalent to
10 psia.
Pressure PSIA Vaccum HG
0 \ 30 - perfect vacum
5/20
10/10
15/0 - Atmospheric pressure
A term used to rate vacuum pumps is used to describe the pump’s ability to draw a vacuum. Essentially, the pump must create a vacuum within itself that is lower than in the system, so that gases will flow from the system to the pump. The point at which a pump can no longer create a pressure difference is called
blank-off pressure.
Vacuum pump oil is a special oil because
it has a low vapor pressure to ensure that it won’t vaporize at low pressures.
Which of the following methods will not decrease the time needed to evacuate a large refrigeration system?
Triple evacuation.
Correct. Triple evacuation is a method that is no longer recommended since it vented refrigerant into the atmosphere. Further, it did not reduce evacuation time at all, but was a method used to dilute any contaminants within the system as much as possible.
A danger with leaving a vacuum pump running all night is
exceeding the pumps running time capabilities.
pump oil could be lost during a power outage.
*Both B and C from above. Correct.
Vacuum pump oil that is fresh
has a clear appearance.
A refrigerant with the ANSI/ASHRAE Standard 34-1992 safety classification of A1 has
low toxicity and no flame propagation.
All appliances containing more than 50 lbs. of refrigerant (except commercial and industrial process refrigeration) must be repaired when the annual leak rate exceeds
15%
Correct. EPA requires that all appliances containing more than 50 lbs. of refrigerant (except commercial and industrial process refrigeration) must be repaired when the annual leak rate exceeds 15%, and commercial and industrial process refrigeration must be repaired when the annual leak rate exceeds 35%.
When charging a chilled water system, charging is usually done as a liquid. However, if the machine is in a deep vacuum, the initial charge should be as a vapor. Why?
Charging as a vapor until the system temperature has risen above 32°F prevents freezing of water in the tubes.
When charging a system, several methods are available for checking the refrigerant charge. In order to charge by monitoring the subcooling, one must
monitor discharge pressure and liquid line temperature close to the metering device and charge until the liquid line temperature falls below the discharge saturation temperature by the expected amount of subcooling.
Insufficient refrigerant will cause
low suction pressure and insufficient cooling.
Most compressors are positive displacement machines. Name a compressor that is not a positive displacement machine.
Centrifugal.
The ratio of the actual volume of refrigerant vapor pumped to the theoretical displacement volume is known as
volumetric efficiency.
A compressor in which the compressor and motor are both sealed within the same pressurized housing is known as a
hermetic compressor.
Modern high-speed reciprocating compressors typically operate at
1750 rpm.
3450 rpm.
*Both A and B from above. Correct. Modern high-speed reciprocating compressors typically operate at 1750 rpm and 3450 rpm.
Compressor capacity decreases as
discharge pressure increases.
suction pressure decreases
compressor speed decreases.
D *All of the above. Correct.