Master Electrician Practice Exam Flashcards

1
Q

Where conductor is marked RHW-2 on the insulation what does the “-2” represent?

A

The conductor has a maximum operating temperature of 90 degrees C

As indicated in Table 310.104(A), conductor insulation type RHW-2 and other types identified by the suffix “2” are rated 90º C for wet locations as well as dry and damp locations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

For a grounded electrical system supplied by a feeder or branch circuit, the equipment grounding conductor shall be sized in accordance with

A

The overcurrent protective device.

As per Section 250.32(B)(1), the equipment grounding conductor shall be sized in accordance with Section 250.122 which states the minimum size size equipment grounding conductor is to be selected from Table 250.122, which is based on the rating or setting of the feeder or branch-circuit overcurrent protective device.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Determine the allowable ampacity of a size 350 kcmil THW aluminum conductor installed in a raceway with four(4) other current carrying conductors when the expected temperature is 44 degrees C

A

350 kcmil THW AL ampacity = 250 amperes before derating
250 amps x .82 (temp. correction) x .8 (adjustment factor) = 164 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Determine the maximum number of 125 volt, general-purpose duplex recptacles the NEC permits to be protected by a 20-ampere, 120-volt single-pole circuit breaker in a commercial building.

A

13 receptacles

In accordance with Section 220.14(I), the load of 180 VA is applied to duplex receptacles mounted on a single yoke or strap. To determine how many receptacles are permitted to be on one circuit, first find the VA of the circuit:

120 volts x 20 amperes = 2,400 VA (circuit)

Then divide the VA of the circuit, 2,400 VA, by the VA of one receptacle,

180 VA: 2,400 VA (circuit) ÷ 180 VA (1 receptacle) = 13 receptacles

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For lighting systems operating at 30-volts or less, the output circuits power supply are to be rated for NOT more than ____.

A

25 amperes

Article 411 addresses low-voltage lighting systems. It is intended to cover low-voltage interior lighting and low-voltage landscape lighting installations. Section 411.2 states, for lighting systems operating at 30 volts or less, the output circuits of the power supply are to be rated for not more than 25 amperes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where there are tenant spaces in retain shopping mall, each occupant shall have access to the main disconnecting means, EXCEPT:

A

Where the service and maintenance are provided by the building managment.

The intent of Section 240.24(B)(1)(1) is to recognize in some situations it is better to have the building management have control of the overcurrent devices than the tenant. Where the electrical service and electrical maintenance are provided by the management and are under continuous building management supervision, the overcurrent devices shall be permitted to be accessible to authorized management personnel only.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Determine the conductor allowable ampacity when give the following related information:

*ambient temperature of 44 C

*250 kcmil THWN copper conductors

*four (4) current-carrying conductors in the raceway

*length of raceway is 50 feet

A

167 amperes

250 kcmil THWN copper ampacity = 255 amperes before derating
255 amps x .82 (temp. correction) x .8 (adj. factor) = 167.28 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

In general, the grounded conductor and the grounding conductor must be bonded together in ____.

I. panelboards used as service equipment

II. all sub-panels

A

Panelboards used as service equipment

As mandated in Section 250.24(A) the grounded service conductor of an ac electrical system shall be connected to the grounding electrode conductor at each service. The purpose of this grounding method is to limit the voltage to ground imposed on the system by lightning and line-surges. This grounding connection also stabilizes the voltage to ground during normal operation, including short-circuits. Section 250.24(A)(5) prohibits re-grounding of the grounded conductor on the load side of the disconnecting means. This requirement prevents parallel paths for neutral current on the load side of the disconnecting means.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Using the standard method of calculation, what is the demand, in KW, on the ungrounded (line) service-entrance conductors of an apartment complex that has 35 electric ranges rated at 11.5 kW each?

A

50 KW

When using the standard method of calculation for dwellings, in accordance with Section 220.55, the use of Table 220.55 is permitted when determining the demand loads for household cooking appliances on service-entrance and feeder conductors. It is unlikely all cooking appliances will be in operation simultaneously and Table 220.55 was developed based on utility demand that proves this point.

Since the ranges in this question have a kW rating of more than 8¾ and less than 12, apply the values given in Column C of Table 220.55 as shown:

35 ranges = 15 kW + 35 kW (1 kW per range) = 50 kW demand

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Electrical services and feeders of a recreational vehicle park shall be calculated on the basis of NOT less than ____ per RV site equipped with (1) 50 ampere 120/240 volt receptacle, (1) 30 ampere 120-volt receptacle and (1) 20 ampere 120-volt receptacle.

A

9600 VA

120*50= 6000 VA

120*30=3600 VA

120*20=2400 VA

6000VA

3600VA

2400VA

12,000 VA *.8=9600 VA

Section 551.73(A) requires where RV sites are equipped with 50-ampere, 120/240, receptacles, they are to be calculated on the basis of not less than 9600 volt-amperes. Also, where the RV site has more than one receptacle, the calculated load shall be calculated only for the highest rated receptacle.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where applying the optional method of calculation for a one-family dwelling, what is the demand load, in kW, for the heating and cooling equipment, on the ungrounded service-entrance conductors for a residence that has the following?

*one blower rated 1.2kW, interlocked with both space heating and AC equipmen

*one central electric space-heating unit rated 25kW

*one air-conditioning unit rated 6.6kW

A

17.03 KW

For loads that do not operate simultaneously, Section 220.60 permits the total load to be calculated based on the largest load being considered. This requirement is also addressed in Section 220.82(C). As per Section 220.82(C)(4), the central space heating load is required to be based on only 65% of the heating equipment load(s).

\*NOTE - Use the larger of the A/C or heating load.
25 kW (htr.) + 1.2 kW (blower) = 26.2 kW x 65% = 17.03 kW demand
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Apply the general method of calculation of dwelling unit and determine the MINIMUM demand load, in VA, where one-family residence has the following fastened in place appliances.

*microwave oven -1250VA

*trash compactor -960VA

*dishwasher-1400VA

*garage door opener-960VA

A

3,428 VA

When using the general method of calculation for dwellings, Section 220.53 permits a demand factor of 75% to be applied to the nameplate rating load of four or more appliances fastened in place, other than ranges, clothes dryers and heating and AC equipment.

microwave oven - 1,250 VA
trash compactor- 960 VA
dish washer - 1,400 VA
garage door opener- 900 VA
4,570 VA x 75% (demand) = 3,428 VA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Where a service riser is installed in wet Location and contains THWN insulated conductors, the wiring method used ____.

A

Permitted

(1) Type IGS cable.
(2) Rigid metal conduit.
(3) Intermediate metal conduit.
(4) Electrical metallic tubing.
(5) Metallic wireways.
(6) Busways.
(7) Metallic auxiliary gutters.
(8) Rigid nonmetallic conduit, underground. (9) Mineral-insulated, metal-sheathed cable.

(10) Flexible metal conduit not over 1.83 m (6 ft) long or liquidtight flexible metal conduit not over 1.83 m (6 ft) long between raceways, or between raceway and service equipment, with equipment bonding jumper routed with the flexible metal conduit or the liquidtight flexible metal conduit according to the provisions of Section 250.102(A), (B), (C), and (E).

Service entrance conductors shall not run within the hollow spaces of frame buildings.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the Maximum distance between supports for straight horizontal runs of trade size 1 1/2 inch threaded rigid metal conduit (RMC)?

A

14 feet

Table 344.30(B)(2) shows horizontal runs of threaded trade size 1½ in. rigid metal conduit to be supported at least every 14 ft.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Overcurrent protection of transformers, of 600 volts or less is required to be sized.

A

In accordance with Table 450.3(B)

Section 450.3(B) requires overcurrent protection of transformers of 600 volts or less to be provided in accordance with Table 450.3(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A thermal barrier shall be required if the space between the resistors and reactors, of 600 volts or less, and combustible material is Less than ____.

A

12 inches

Because resistors and reactors give off heat, they must be guarded and located at safe distances from combustible material. A thermal barrier is required if the space between the resistors and reactors and any combustible material is less than 12 in. Refer to Section 470.3.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

In movie theaters, all switches for controlling the emergency lighting systems shall be located _____.

A

In the lobby.

in compliance with Section 700.21, in theaters, all switches for controlling emergency lighting systems shall be located in the lobby or at a convenient accessible location. The switches are not permitted to be placed in the projection both or on the stage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Where a 90 amper, 240-volt, single-phase load is located 225 feet from a panelboard and is supplied with 3 AWG copper conductors, determine the approximate voltage drop on the conductors. (K=12.9)

A

10 Volts

To calculate the voltage drop on this circuit, first locate the circular mil of the conductors (52,620 CM) as indicated in Table 8 of Chapter 9. Then apply the single-phase voltage drop formula:

VD = 2KID VD = 2 x 12.9 x 90 amps x 225 ft. = 9.92 volts dropped
CM 52,620 CM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

A one-family residence is served with insulated 120/240 volt service-drop conductors, supported with a grounded messenger wire from the utility company. The service-drop crosses the swimming pool; the pool has a diving board with 5 feet above water level. The NEC requires the conductors to be a minimum height of ___ above the pool water level.

A

22 1/2 feet

When taking these conditions in consideration, Table 680.8 and Figure 680.8 show the conductors are required to have a clearance of not less than 22½ ft. above the water level of the pool. These clearances consider factors as the use of skimmers with aluminum handles during pool maintenance and provide sufficient separation between the overhead conductors and the swimming pool.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

All metallic switchgear rated for over 600 volts shall be provided with a grounding busbar for the purpose of connecting the

A

Metallic shield of cables.

The purpose of connecting the metallic shield of cables to the grounding busbar is to limit the voltage to ground imposed on the system by lightning and line-surges. This grounding connection also stabilizes the voltage to ground during normal operation, including short-circuits.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Conductors tapped from a feeder and supplying the primary of a transformer need to have overcurrent protection, where the length of the tap conductors are not over 25 feet and have an ampacity of at LEAST ____ of the rating of the overcurrent device protecting the feeder conductors.

A

One-Third

As permitted by Section 240.21(B)(3)(1), the tap conductors supplying the primary of a transformer need not have overcurrent protection where the conductors have an ampacity at least one-third the rating of the overcurrent device protecting the feeder conductors. This installation is permitted where the conductor length of 25 ft. is applied to one primary and one secondary conductor and the conductors are protected from damage by being enclosed in an approved raceway.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Electrical equipment such as switchboards, panelboards, industrial control panels, and motor control centers, located in commercial and industrial occupancies are required to be field marked to warn ____ of potential electrical arc flash hazards.

A

qualified persons

Section 110.16 was initiated to require electrical equipment to be field marked to warn electricians of potential electrical arc flash hazards when working on energized (hot) equipment.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

When connecting utilization equipment to a 20-ampere rated branch-circuit that also serves luminaires, the utilization equipment shall have an ampere rating of NOT more than ____.

A

10 Amps

Section 210.23(A)(2) permits a 15- or 20-ampere branch circuit supplying lighting outlets to also supply fastened in place utilization equipment, such as an appliance. The utilization equipment load must not exceed 50% of the branch-circuit ampere rating.

20 amperes x 50% = 10 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at LEAST ____ inside the fountain, when measuring from the outside edges of the fountain.

A

5 feet

The intent of Section 680.57(C)(1) is to prevent contact with the electric sign by unauthorized people around the fountain.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

In an aircraft hanger, the area that extends upward from the floor level ____ above the upper surface of aircraft wings, power plants and fuel tanks shall be classified as a Class 1, Division 2 or Zone 2 location.

A

5 feet

Section 513.3(C)(1) covers the classification of areas in the vicinity of aircraft housed in aircraft maintenance and storage hangers. In order to properly classify hanger areas, the dimensions of the aircraft within the hanger must be known.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

Conductors supplying outlets for arc an xenon motion picture projectors of the professional type shall be a minimum size of ______.

A

8 AWG

Section 513.3(C)(1) covers the classification of areas in the vicinity of aircraft housed in aircraft maintenance and storage hangers. In order to properly classify hanger areas, the dimensions of the aircraft within the hanger must be known.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

Where rigid polyvinyl chloride (PVC) conduit is installed underground to supply a gasonline dispensing unit, threaded rigid metal conduit (RMC) or threaded intermediate conduit (IMC) shall be used for the LAST ____ of the underground run to where the conduit emerges.

A

2 FEET

Exception No. 2 to Section 514.8, makes it clear that, where Type PVC conduit is used for underground wiring supplying motor fuel dispensers, threaded rigid metal conduit or threaded intermediate metal conduit must be used for the last 2 ft. of the underground run to where the conduit emerges.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

Where electrical metallic tubing (EMT) is installed under metal-corrugated sheet roofing decking, a clearance of at least ____ must be maintained between the top of the tubing and the surface of the roof decking.

A

1 1/2 inches

Section 300.4(E) recognizes boxes or raceways located below metal-corrugated roof decking may be damaged by nail or screw penetration during construction. Therefore, a clearance of at least 1½ in. must be maintained between the decking and the boxes or raceways.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

After applyin all demand factors, the ampacity of the service-entrance conductors are required to be NOT less than ___ where both the overcurrent device and its assembly are not listed for operation at 100 percent of their rating.

A

The sum of the noncontinous loads plus 125 percent of the conitinous loads

The purpose of the rule addressed in Section 230.42(A)(1) is to prevent the overheating of the service-entrance conductors. The ungrounded service-entrance conductors must have an allowable ampacity of 100% of the noncontinuous loads plus 125% of the continuous loads to be served.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

When an equipment room houses electircal equipment rated at LEAST ____ or more, the personnel doors intended for entrance to an from egress from working space, shall open in the direction of egress.

A

1200 amps

The requirements presented in Section 110.26(C)(3) are intended to provide access to electrical equipment. However, the primary intent is to provide egress from the area so that workers can exit through doors equipped with panic bars in the event of an arc-flash incident.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

The accessible portion of abandoned supply circuits and interconnecting cables located in an information technology equipment room shall be removed, UNLESS ____.

A

Contained in a raceway.

Section 645.5(G) requires the accessible portion of abandoned supply circuits and interconnecting cables located in an information technology equipment room to be removed, unless contained in a raceway.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

Apply the general method of calculation for dwelling and determine the demand load, in kW, on the ungrounded service entrance conductors for (1) 18 kW residential electric range.

A

10.4 kW

To solve this problem, from Table 220.55, the first step is find the maximum demand for one range not over 12 kW, which is 8 kW (from Column C).

Step 2. According to Note 1 of Table 220.55, for ranges that are over 12 kW but not more than 12 kW, the maximum demand in Column C (8 kW) is increased for each kW that exceeds 12 kW:

18 kW -12 kw = 6 kW X 5% = 30% increase in column C
.30 x 8 kW = 2.4 kW increase 8kw (Col.C) + 2.4 kW= 10.4 kW demand

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

AFCI protection is required for all 15 - 20 ampere, 120-volt branch circuits supplying outlets located in ____.

A

Guest rooms and guest suites of hotels and motels that are provided with permanent provisions for cooking

Boat houses and recreational vehicles do not require all 15- and 20-ampere, 120 volt branch circuits to be provided with AFCI protection. But in compliance with Section 210.18, guest rooms and suites in hotel and motels that are provided with permanent cooking facilities are governed by the same rules for dwelling units addressed in Section 210.12(A), which states AFCI protection is required for the branch circuits.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

What MINIMUM size THWN copper conductors are required to supply a continuous-duty, 25 hp, 208-volt, 3-phase motor? The motor is on the end of a short conduit run that contains only three (3) conductors, at an ambient temperature of 50 deg. C. Consider the motor terminations to be rated for 75º C.

A

1 AWG

To determine the minimum size required of the conductors to supply this motor, first locate the full-load current rating of the motor, 74.5 amperes, from Table 430.250. Next, as per Section 430.22 multiply x 125%, 93.5 amperes. Then, divide by the temperature correction factor, 0.75, found in Table 310.15(B)(2)(a), 124 amperes. Finally, select the conductor size, 1 AWG THWN, as shown in Tbl. 310.15(B)(16).

25 hp motor FLC = 74.8 amps x 125% = 93.5 amperes
93.5 amperes ÷ .75 (temperature correction factor) = 124.6 amperes

*Note - The wire size needs to be increased because of the elevated ambient temperature. Size 1 AWG THWN conductors with an ampacity of 130 amperes should be selected.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
35
Q

Which of the following shall be installed on a critical branch of the emergency system in health care facility

A

Nurse Call Systems

As mandated in Section 517.33(A)(5), upon loss of the normal power in health care facilities, the critical branch of the emergency system is to supply power to nurse call systems. The intent of this rule is to provide constant communication between patient care areas and health care staff in the event of an emergency or power outage from the normal power.

36
Q

Where a 20-ampere rated branch circuit supplies (3), 15 ampere, 125 volt recptacle outlets, in compliance with the NEC, the Maximum load, in amperes, any one receptacle is permitted to carry is

A

12 amperes

Table 210.21(B)(2) indicates a 15-ampere receptacle is permitted to have a maximum connected load of 12 amperes. The intent of this requirement is to prevent overheating the receptacles and overloading the circuit.

37
Q

Which of the following listed wiring methods is not approved for use in assembly locations, UNLESS encased in concrete?

A

Schedule 80 PVC

Section 518.4(A) permits nonmetallic conduit (PVC) to be installed in assembly locations only when encased in concrete.

38
Q

All 15 and 20 ampere, 125 and 250 volt, nonlocking receptacles installed in a wet location shall be listed ____ type.

A

Weather Resistant

As per Section 406.8(B), all 15- and 20-ampere receptacles installed in a wet location are required to be listed weather-resistant type. The major differences between weather-resistant and non weather-resistant are that the weather-resistant has additional corrosion protection, UV resistance, and cold impact resistance. The weather-resistance type receptacles are not as likely to become brittle and break.

39
Q

What percent of electrical supplied RV spaces in a recreational vehicle park must have 50-ampere, 125/250 volt receptacle outlets?

A

20 percent

As indicated in Section 551.71, 20 percent of RV sites in RV parks must be provided with 50-ampere, 125/250-volt receptacles to accommodate the larger recreational vehicles.

40
Q

What is the Minimum bend radius of trade size 4 in. rigid metal conduit (RMC) where the bend is not made with a one-shot or full-shoe bender?

A

24 inches

The values shown Table 2 of Chapter 9, helps to prevent deforming or crimping the conduit when bending and ease the strain on conductors when pulling the conductors into the conduit.

41
Q

Type AC cable shall NOT be used _____.

A

Where embedded in plaster in wet locations.

Due to corrosive conditions, Section 320.12(5) prohibits Type AC cable to be used where embedded in plaster in wet locations.

42
Q

Where portions of a cable, raceway or sleeve are known to be subjected to different temperatures and where condensation is known to be a problem, the raceway or sleeve shall___.

A

Be filled with an approved material.

Section 300.7(A) addresses the problem of condensation forming in raceways or sleeves that are subjected to temperature differences as a result of air circulating through the raceway from a warmer to a colder section. Circulation of air can be prevented by sealing the raceway or sleeve with a suitable pliable compound.

43
Q

What is the Minimum size 75 C copper service-entrance conductors required for a 200 ampere rated commercial service? Assume temperature and the number of current carrying conductors in the raceway is not a consideration

A

3/0 AWG THW

To select service-entrance conductors for commercial services use Table 310.15(B)(16). When ambient temperature is not a factor, you should have selected 3/0 AWG THW conductors which has an allowable ampacity of 200 amperes

44
Q

Determine the MINIMUM size THWN copper feeder conductors required by the NEC to supply the following 480-volt, continuous duty, 3-phase, induction type, Design B, motors.

* 1 -40 hp
* 1 -50 hp
* 1 -60 hp

A

First, find the full-load current ratings of the motors as shown in Table 430.250. Next, apply Section 430.24(1)&(2), where the feeder conductors are to have an ampacity of 125% of the FLC rating of the highest rated motor in the group, plus the sum of the FLC ratings of all other motors in the group. The conductor size is to be selected from Table 310.15(B)(16):

40 hp FLC = 52 amps x 100% = 52 amperes
50 hp FLC = 65 amps x 100% = 65 amperes
60 hp FLC = 77 amps x 125% = 96 amperes
Total = 213 amperes

Size 4/0 AWG THWN copper conductors with an ampacity of 230 amperes should be selected.

45
Q

Two or more motors may be installed without individual overcurrent protection devices if rated less than 1 hp, and the full-load current rating of each motor does not exceed ____ if the are on 120 volt, 20 ampere branch circuit

A

6 amperes

As addressed in Section 430.53(A)(1), two or more motors may be connected to the same 120-volt, 15- or 20-ampere, branch-circuit provided each motor is not over 1 hp, the full-load rating of each motor does not exceed 6 amperes, and the rating of the branch-circuit protective is not exceeded.

46
Q

Where a listed packaged spa or hot tub is installed outdoors, the unit is permitted to be cord-and-plug connecetd, provided the cord is NOT longer than ____ and protected by GFCI.

A

15 feet

As per Section 680.42(A)(2), in regard to outdoor installations of spas and hot tubs, the units are permitted to be cord-and-plug connected with a cord not longer than 15 ft.

47
Q

A three-phase, 480-volt, 100 ampere noncontinuous load is located 390 feet from a panelboard. What MINIMUM size THWN aluminum feeder conductors are required to limit the voltage drop
to 3 percent? (K = 21.2)

A

1/0 AWG

To find the correct wire size, first find the voltage drop permitted:

3% of 480 volts = .03 x 480 volts = 14.4 (voltage drop permitted)

Next, find the wire size as express in circular mils:

CM = 1.732 x K x I x D
VD permitted

CM = 1.732 x 21.2 x 100 amps x 390 ft. = 99,446 CM
14.4 volts

Then, select the conductor size from Table 8 of Chapter 9:

Size 1/0 AWG conductors with a circular mil area of 105,600 CM should be selected.

48
Q

Two rigid conduits are to support a weatherproof 18 cu in box, with threaded hubs, which contains 125-volt, 20 ampere receptacle outlet. The conduits are to be threaded wrench-tight into the hubs and, in general, shall be securedd within at LEAST ____ of the enclosure.

A

18 inches

Section 314.23(F) requires that conduit be supported within 18 in. of the enclosure if the enclosure contains devices or luminaires.

49
Q

In general, if a cablebus system is rated 95 amperes, the MAXIMUM allowable rating of overcurrent device used to protect the cablebus is ___.

A

100 amperes

In accordance with Sections 240.4(B)(2)&(3), under this condition, you are permitted to go up to the next standard size rating of 100 amperes. The standard size ratings of overcurrent protective devices are listed in Section 240.6(A).

50
Q

A twenty-five foot long tap conductor tapped from a 100 ampere rated feeder conductor, shall have an ampacity of NOT less than ____.

A

33.3 amperes

In compliance with Sections 240.21(B)&(B)(2)(1), when given these conditions, the tap conductors are to have an ampacity of not less than one- third of the rating of the overcurrent device protecting the feeder conductors:

100 amperes (overcurrent protective device) ÷ 3 = 33.3 amperes

51
Q

Disregarding exceptions, bonding between Class 1 locations and the point of grounding for service equipment may be done by ____.

A

Bonding Jumpers

Section 501.30(A) clarifies that the approved method of bonding between Class I locations and the point of grounding for service equipment must be done by using bonding jumpers with approved fittings. This bonding method is intended to provide a mechanical/electrical connection that is low impedance and free from accidental arcing due to loose connections.

52
Q

Determine the demand load, in VA, on the ungrounded service-entrance conductors, for the general-lighting and receptacles for a 25,000 sq. ft. office building that has one hundred-fifty (150) general-purpose duplex receptacles. Consider the service overcurrent protection device is NOT listed for continuous use.

A

127,875VA

To find the general lighting load, first, multiply the square footage of the building, 25,000 sq. ft., by 3.5 VA (shown in Table 220.12) and as per Section 230.42(A)(1), multiply by 125% = 109,375 VA. To determine the receptacle connected load, as per Section 220.14(I), multiply the number of receptacles, 150, by 180 VA = 27,00 VA. To find the receptacle demand load, apply the values given in Table 220.44, first 10 kVA @ 100%, remainder over 10 kVA @ 50% = 18,500 VA. Finally, add the lighting demand load, 109,375 VA, and the receptacle demand load, 18,500 VA together = 127,875 VA.

25,000 sq. ft. x 3.5 VA x 125% (lighting) = 109,375 VA
150 receptacles x 180 VA each = 27,000 VA
1st. 10,000 VA @ 100% = 10,000 VA
27,000 VA - 10,000 VA = 17,000 VA @ 50% = 8,500 VA
TOTAL = 127,875 VA

53
Q

When an electrical service is required to have a grounded conductor present, what is the smallest grounded conductor permitted for an electric service using size 1000 kcmil copper ungrounded (phase) conductors?

A

2/0 AWG

In compliance with Section 250.24(C)(1), the grounded conductor shall not be smaller than the required grounding electrode conductor specified in Table 250.66. Table 250.66 shows when using size 1000 kcmil copper service-entrance conductors, the minimum size copper grounding electrode conductor required is 2/0 AWG

54
Q

A motel to be constructed will have two (2), 20-ampere, 120-volt circuits provided for the exterior electric signs. Determine the demand load, in VA, for the electric signs, on the feeder and service-entrance conductors.

A

3000 VA

In compliance with Section 220.14(F), each electric sign branch circuit is to be calculated at a minimum of 1,200 VA. This VA rating is to be multiplied by 125%; for the purpose of calculations, electric signs are to be considered continuous loads. Refer to Section 600.5(B).

1200 VA x 2 (signs) x 125% = 3,000 VA

55
Q

Luminaires shall be installed so that the adjacent combustible material is not subjected to temperatures in excess of ____.

A

90 degrees C

Section 410.11 regulates the placement of luminaires near combustible material so that they do not become a heat source that could ignite the combustible material. This rule helps to prevent hot particles from broken incandescent lamps igniting the combustible material.

56
Q

An aluminum grounding electrode shall be ____.

A

Prohibitied

Because of the corrosive properties of aluminum conductors, Section 250.52(B)(2) prohibits aluminum materials to be used as grounding electrodes.

57
Q

A panelboard is limited to 42 overcurrent protective devicees where ____.

A

The panelboard is a “split-bus” type panelboard.

A required by Exception No. 2 of Section 408.36, a panelboard constructed with two main circuit breakers shall not contain more than 42 overcurrent protective devices. This type of panelboard is commonly called a “split-bus” type panelboard and is used usually for residential installations.

58
Q

When rigid polyvinyl chloride conduit (PVC) is used to enclose conductors feeding a wet-niche luminaire in a permanently installed swimming pool, a ____ insulated copper grounding conductor shall be installed in this conduit, unless a listed low-voltage lighting system not requiring grounding is used.

A

8 AWG

As mandated by Section 680.23(B)(2)(b) where rigid nonmetallic conduit is used between a forming shell for a wet-niche luminaire and a junction box or other enclosure, a size 8 AWG insulated copper bonding jumper is required to be installed in the conduit to provide electrical continuity between the forming shell and the junction box or enclosure.

59
Q

In general, what is the largest size transformer, in kVA, that may be installed in a an area or room that is NOT constructed in a fire-resistant manner?

A

112 1/2 KVA

As required by Section 450.21(B), transformers over 112½ kVA in rating are to be installed in a transformer room of fire-resistant construction.

60
Q
A
61
Q

When calculating the total load of an office building, and the number of general-purpose receptacles to be installed is not yet determine, an additonal load of ____ volt-amp(s) per square foot is required for the receptacle outlets.

A

One VA

In compliance with Section 220.14(K)(2), when calculating the total load of an office building or a bank and the number of general-use receptacles to be installed is unknown, a minimum load of one VA per sq. ft. is to be added to general lighting load. This requirement is in place because it is very common for banks and office buildings to construct facilities on the first floor of a multi-story building with tenant spaces on the remaining floors. Under these conditions, the future tenant’s general-use receptacle requirements are unknown.

62
Q

Where a central vacuum assembly is located in a storage closet adjacent to the laundry room of a dwelling, accessible non-current-carrying metal parts of the assembly shall be ____.

A

connected to an equipment grounding conductor

To prevent a shock hazard, Section 422.15(C) requires all accessible metal parts of a central vacuum assembly to be connected to an equipment grounding conductor.

63
Q

Conductors other than service-entrance conductors shall be permitted to be installed in a cable tray with service-entrance conductors provided _____.

A

A solid fixed barrier of material compatiable with the cable tray is installed to seperate the systems.

Cable tray systems are permitted to support service-entrance conductors and the general rule, as indicated in Section 230.44, is the cable tray shall only contain service-entrance conductors. But the exception following this rule permits other conductors in the cable tray with the service-entrance conductors where the cable tray is provided with a solid fixed barrier to separate the service-entrance conductors from other conductors installed in the cable tray.

64
Q

The MAXIMUM allowable ampacity of a size 750 kcmil aluminum conductor where there are six (6) current - carrying conductors in the raceway, installed in a dry location, where the ambient temperature will reach 22 degrees C is

A

361.92 amperes

Size 750 kcmil AL ampacity (before derating) = 435 amperes
435 amps x 1.04 (temp. correction) x .8 (adj. factor) = 361.92 amperes

65
Q

Fixed outdoor electric deicing equipment shall be considered as a ____ load.

A

Continuous load.

Fixed outdoor deicing equipment can operate for over 3 hours, therefore it is to be considered a continuous load when sizing conductors and overcurrent protective devices. Refer to Section 426.4.

66
Q

What is the MINIMUM size copper common grounding electrode conductor required to run through a building to four (4) separetley derived systems (transformers) each having size 3/0 AWG copper secondary conductors?

A

3/0 AWG

A common grounding electrode conductor for multiple separately derived systems such as transformers is permitted by Section 250.30(A)(6). Section 250.30(A)(6)(a)(1) requires the common grounding electrode to be not smaller than 3/0 AWG copper.

67
Q

The NEC permits trade size 3/8 inch flexible metal conduit (FMC) to be used to enclose tap conductors for luminaires, provided the length of the FMC does not exceed _____.

A

6 feet

Section 348.20(A)(2)c. makes it clear that trade size 3/8 in. flexible metal conduit, in lengths of not more than 6 ft., is permitted to enclose tap conductors between the outlet box and the terminal housing of luminaires.

68
Q

What is the MAXIMUM distance allowed to support intermediate metal conduit (IMC) from a junction box, where the structural members do not permit fastening?

A

5 feet

According to Section 340.30(A)(1) fastening of IMC is required within 3 ft. of junction boxes. However, Section 342.30(A)(2) permits fastening of the conduit to be increased to within 5 ft. of the junction box, where structural members do not readily permit fastening within 3 ft.

69
Q

When combination surface nonmetallic raceways are used both for signaling and for power and lighting circuits, the different systems shall be ____.

A

Run in seperate compartments.

Section 388.70 requires signaling and power and lighting conductors installed in surface nonmetallic raceways to be run in separate compartments. This separation requirement prevents the inductive effect on the lower voltage conductors from the higher voltage conductors.

70
Q

What is the MAXIMUM load, in VA, the branch-circuit conductors of a 20-ampere, 277-volt circuit are permitted to carry when supplying a conitnuous lighting load? Consider the overcurrent protection device protecting the branch circuit is not listed for operation at 100% of its rating.

A

4,432 VA

Section 210.19(A)(1) requires branch-circuit conductors that supply continuous loads to have an ampacity of not less than 125% of the load to be served. Therefore, when supplying continuous loads, the conductors may carry no more than 80% than which they are rated for.

100 ÷ 125 = .8 or 80%.

277 volts x 20 amperes x .8 = 4432 VA

71
Q

All 240-volt, twist lock, 30-ampere receptacles on a construction site where supplied from a temporary service, are required to be provided with ____ when not covered by an assured grounding program.

A

GFCI protection

To protect personnel from shock hazards, as specified in Section 590.6(B), the receptacles are to be provided with GFCI protection.

72
Q

In commercial and industrial establishments, all 15 and 20 ampere, single-phase, 125-volt receptacles installed in ____ require GFCI protection for personnel.

A

Kitches and Bathrooms.

As per indicated in Section 210.8(B)(1), if 125-volt, single-phase, 15- and 20-ampere receptacles are provided in bathroom areas of nondwelling occupancies, GFCI protected receptacles are required. Likewise, as mandated in Section 210.8(B)(2), where these receptacles are located in kitchens of nondwelling occupancies, they are also to be GFCI protected, whether or not the receptacle serves countertop areas.

73
Q

Communications wires and cables shall have a voltage rating of NOT less than ____.

A

300 volts

Section 800.179 requires communications wire and cables to have a voltage rating of not less than 300 volts, to permit communications cable to substitute for 300-volt power-limited fire-protective signaling cable and to carry the voltages found on a telephone line (ringing voltage up to 130 volts), plus to coordinate with protector requirements.

74
Q

An emergency system is required to have NO more than _____ to have power available in the event of failure of the normal electrical supply system.

A

10 seconds

In the event of failure of the normal electrical supply system, in order to minimize the duration of time of the loss of lighting, and if necessary, where persons can evacuate the building safely, Section 700.12 mandates an emergency system is required to have no more than 10 seconds to have emergency lighting, emergency power, or both available.

75
Q

X-Ray equipment installed in a hospital may be served by a hard service cord with a suitable plug provided the branch-circuit rating does NOT exceed ____.

A

30 amperes

The exception to Section 517.71(A) allows X-ray equipment to be served by a hard-service cable or cord provided the branch circuit rating does not exceed 30 amperes.

76
Q

The overall length of a power-supply cord to mobile home is required to be not more than ____.

A

36 1/2 feet

As indicated in Section 550.10(D), the overall length of the power-supply cord to a mobile home must not exceed 36½ ft. The intent of this requirement is to limit voltage drop on the conductors supplying the mobile home.

77
Q
A
78
Q

A recreational vehicle campground has one hundred-fifty campsites with electrical power. Twenty-five of the campsites are reserved as tent sites. How many of the sites are required to have a 20-ampere, 125-volt receptacles provided?

A

150

Section 551.71 requires every RV site equipped with electrical supply to be provided with at least one 20-ampere, 125-volt receptacle.

79
Q

For other than one-family dwellings, an emergency disconnect switch must be provided for spas and hot tubs NOT less than ___ away from the spa or hot tub and must be readily accessible to the users.

A

5 feet

The provisions of Section 680.41 require a disconnecting means be provided for spas and hot tubs that is capable of being used in an emergency. The emergency shutoff switch must be located within sight of and at least 5 ft. from the spa or hot tub and must be clearly labeled “Emergency Shutoff”.

80
Q

Where size 6 AWG THWN copper branch-circuit conductors supply a 240-volt, single-phase, 5000 VA non-motor operated appliance, the MAXIMUM standard size circuit breaker permitted for overcurrent protection on this circuit is rated ____.

A

35 amperes

The rules governing overcurrent protective devices for non-motor operated appliances such as electric ranges, cooktops, ovens and water heaters are found in Section 422.11(E). By using the single-phase current formula, first find the load, in amperes, of the appliance and multiply the load by 150%:

I = Power I = 5,000 VA = 20.8 amperes x 150% = 31.2 amperes
Volts 240 volts

Since this value does not correspond to a standard overcurrent device ampere rating, as per Section 422.11(E)(3), the next higher standard rating is permitted. As shown in Section 240.6(A), the next standard size circuit breaker with a rating of 35 amperes should be selected.

81
Q

The ampacity of size 1/0 AWG THWN/THHN, dual-rated copper conductors enclosed in rigid metal conduit (RMC) when installed underground in direct contact with the earth is ___.

A

150 amperes

Section 300.5(B) requires that the inside of all raceways placed underground be classified as a wet location. Table 310.104(A) shows when conductors with THWN insulation are installed in a wet location to be rated for 75º C. Table 310.15(B)(16) shows 1/0 AWG 75º rated copper conductors to have an allowable ampacity of 150 amperes.

82
Q

Every electrified truck parking space intended to provide an electrical supply for transport refrigerated units shall be equipped with a ____.

A

I. 30 ampere, 480-volt, 3-phase, 3-pole, 4-wire receptacle
II. 60 ampere, 208-volt, 3-phase, 3-pole, 4-wire receptacle

In compliance with Section 626.31(C), the truck parking spaces shall be equipped with one or both of the type of receptacles mentioned.

83
Q

Flexible cord is permitted to be connected to fluorescent luminaires where the cord ____.

A

Is visible its entire length

Section 410.62(C)(1)(2)a. allows flexible cord to be connected to fluorescent luminaires where the cord is visible its entire length.

84
Q

An outdoor motor fuel gasoline dispensing pump is considered to be a Class 1, Division 2 hazardous location up to ___ above grade level within ____ horizontally from any edge of the motor fuel pump enclosure.

A

18 inches - 10 feet

Table 514.3(B)(1) indicates the area around an outdoor motor fuel dispensing device is considered to be a Class I, Division 2 location up to 18 in. above grade level and within 10 ft. horizontally from any edge of the pump.

85
Q
A