LSA and FFA Flashcards
1
Q
Hydrant Pressure pax
A
With 2 hoses running, 4bar
2
Q
Heads spaced
A
4m apart
3
Q
Hi Fog pressure in machinery space
A
100bar
4
Q
HiFog in accom
A
10bar
5
Q
Fire Plan Contents
A
• the location of A-class and B-class divisions • the location of fire alarms • the fixed extinguishing system and the location of the release stations • the location of fire pumps and hydrants • the location of portable firefighting equipment, hoses and extinguishers, including the fireman’s outfit and breathing apparatus • the location of emergency stops, fire dampers and ventilator controls • the location of the emergency generator
6
Q
Fire Hose Lengths
A
Min 10m
Machinery space max 15
Max 20 accom
Breath exceedes 30m, min 25m
7
Q
Fire Pumps pax ship
A
at least 3