Line D DFMAs Flashcards
A direct fired make-up air unit is designed for temperatures ranging from -5⁰F to 85⁰F. At what outdoor temperature (within design parameters) will the velocity across the burners be the greatest?
85⁰F
A direct fired makeup air heater has the same function as an RTU.
TRUE / FALSE
FALSE
What is the main benefit of a DFMAH?
No efficiency lost to a heat exchange
Referring to the B149.1 under what conditions can a DFMAH be used?
A DFMAH shall not be installed unless it is necessary to exhaust air and replace it with preheated air
What must be proved before the DFMAH can start?
Any inlet or discharge air louvres must be proved open through an interlock with the control the exhaust system is operating
What is the purpose of makeup air?
To replace the air exhausted by large exhaust appliances which, when properly designed, installed and maintained ensure a neutral pressure in the building
When a DFMAH is used in a kitchen it must be interlocked with the kitchen exhaust fan so that neither fan can operate without the other operating?
TRUE / FALSE
TRUE
List three things that could affect the external static pressure placed on a DFMAH.
Filters, Grilles, Ductwork
When the DFMAH is in operation the burner is always firing?
TRUE / FALSE
FALSE
What are the two modes of operation for a spray booth DFMAH?
Spray Mode, Bake Mode
In a DFMAH what is adjusted to control air velocity?
Profile plates
Other than make up air for a kitchen or spray booth list three other applications for DFMAH.
Shaft pressurization (stairwell or elevator), storage garage, mine shaft