Line B Testing Mechanical Safety Devices Flashcards
Which code regulates the installation and testing of safety relief valves?
ASME Boiler and Pressure Vessel code
What is the maximum servicing interval for a pressure relief device installed on a 50 psig steam boiler?
Every five years
How often should a lift test be performed for a pressure relief device installed on a 50 psig steam boiler?
Annually
What is the maximum servicing interval for a pressure relief device installed on a 12 psig steam boiler?
Every five years
How often should a lift test be performed for a pressure relief device installed on a 12 psig steam boiler?
Annually
How often should a lift test be performed for a pressure relief device installed on a 150 psig hot water heating boiler?
Every two years
What fluid should a pressure relief device that has been serviced and installed on a steam boiler be tested on?
Steam
What fluid should a pressure relief device that has been serviced and installed on a hot water heating boiler be tested on?
a. Air
b. Steam
c. Water
When performing a lift test for a safety valve installed on a low-pressure steam boiler, at what percent must the pressure be under the device disk prior to lifting the test lever?
At least 75% of the Device set pressure