Lightning Protection Lvl 1 Flashcards
Lesson 5: Concealed and Structural Steel Systems
When they are to be concealed, lightning conductors may be installed?.
Select one:
a. behind exterior wall facing
b. between wall studs
c. under roof framing
d. under roofing materials
e. all of the above
e. all of the above
If the lightning conductor is run in metal conduit, it must be bonded to the conduit at?.
Select one:
a. any point where the conduit is not electrically continuous
b. both ends
c. the center of the conduit
d. a. and b.
e. all of the above
d. a. and b
In masonry chimneys, both strike termination devices and lightning conductors can be concealed within the chimney itself or attached to the exterior and routed through the structure to conceal main conductors.
Select one:
True
False
True
Lightning conductors and all other lightning protection components concealed in steel reinforced concrete must be connected to the reinforcing steel at?.
Select one:
a. the center
b. the lower extremities
c. the upper extremities
d. b. and c.
e. a., b., and c.
d. b. and c
Long vertical reinforcing steel members must have additional connections to the lightning conductor at intervals not exceeding?.
Select one:
a. 50’
b. 75’
c. 100’
d. 200’
D 200’
Horizontal lightning conductor runs must be connected to the reinforcing steel at intervals not exceeding?.
Select one:
a. 50’
b. 75’
c. 100’
d. 200’
C 100’
Grounding electrodes for concealed systems follow the same rules as those for exposed systems.
Select one:
True
False
True
Grounding electrodes located under basement slabs or in crawl spaces need to be installed as close as possible to the outer perimeter of the structure.
Select one:
True
False
True
Where ground rods are used for grounding electrodes, they must be in contact with the earth for a minimum of?and extend to a depth ofnot lessthan?below finished grade, except as permitted by the requirements for shallow soil.
Select one:
a. 4’ / 6’
b. 6’ / 8’
c. 8’ / 10’
d. 10’ / 12’
c. 8’ / 10’
The structural steel framework of a structure can be utilized as a main lightning conductor of the lightning protection system if?.
Select one:
a. it is electrically continuous
b. it is less than 30’ in length
c. it is made electrically continuous
d. a. or c.
e. a., b., or c.
d. a. or c.
Strike termination devices must be connected to the structural steel framing by?.
Select one:
a. direct connection
b. the use of an external lightning conductor that interconnects all strike termination devices
c. the use of individual conductors routed through the roof or parapet walls to the structural steel framework
d. any of the above
D all
When the external lightning conductor is used, it must be connected to the structural steel at intervals not exceeding?.
Select one:
a. 50’
b. 75’
c. 100’
d. 150’
c. 100’
Which of the following isNOTa method to connect the lightning conductor to the structural steel?
Select one:
a. Brazing
b. Mechanically
c. Welding
d. None of the above
D none of the above
When making the connection for a lightning conductor mechanically, the steel must be cleaned down to the?.
Select one:
a. base metal
b. first layer of paint
c. primer
d. a. or c.
A base metal
When a bonding plate is used on a structural steel member, it must have a minimum surface area of at least?.
Select one:
a. 4 in2
b. 8 in2
c. 1 ft2
d. 2 ft2
b. 8 in2