Lightning Protection Flashcards
What book published by the NFPA is the standard for installation of lightning protection systems?
NFPA 780
The tip of air terminals must rise at least __ inches above the surface they are protecting.
10”
Lightning cables must be strapped/supported at least every __ feet in exposed installations.
3’
All structures (with roof perimeter of 250’ or less) must have at least __ down conductors.
2
Except for concrete encased electrodes, a ground ring used as the electrode for a lightning protection system must be at least __ feet from the footing.
2’
What does LPS stand for?
Lightning Protection System.
Metal objects with potential to ground within __ must be bonded to the LPS.
6’
Air terminals must not be more than __ inches away from corners or edges.
24”
The minimum bend radius for cables is __ inches at __ degrees.
8 inches at 90 degrees
On average, down conductors should not be spaced more than ___ feet apart.
100
Before driving a ground rod for LPS, it is recommended you first dig a hole __ feet deep in which to drive.
2’ (2’ hole + 8’ rod = required 10’ depth)
At the foundation of a building, all metal objects with potential to ground within __ feet must be bonded.
12’
Air terminals that extend between 10-24” shall be spaced no less than __ feet apart.
20’
Structures with 250’ or less of roof perimeter are only required to have __ down conductors.
2
T/F: As many grounds are required as there are down conductors.
True
Of buildings 60’ tall or higher, All metal objects with potential to ground within __ feet of the LPS shall be bonded to it.
12’
Air terminals that extend 24” or higher shall be spaced no less than __ feet apart.
25’
Structures with over 250’ of roof perimeter shall require an additional down conductor for each additional ___ feet of roof perimeter.
100’
If a system had 2 ground rods, they would need to be spaced __ feet. Likewise, if a system had 3 ground rods, they would need to be spaced __ feet.
2 = 20' 3 = 30'
T/F: If a conductor is ran through a metal conduit, it only needs to be bonded at one end.
False, both ends
In addition to strike terminals located around the perimeter of the roof, flat or gently sloping roofs that exceed 50’ in width or length must have additional strike terminals installed at intervals not exceeding __ feet.
50’
Exposed down conductors must be protected from physical damage within __ feet from the floor.
6 feet
A ground loop is required if a building is __ feet or more in height.
60’
Aluminum cables and fittings shall not be used within __ inches of grade.
18”