Lesson 3 Flashcards

Learning to love my father again

1
Q

The purpose of the NEC is to provide electrical installation requirements that protect persons and property from electrical hazards arising from the use of electricity.
Select one:
True
False

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which of the following can be thought of as the foundation of an electrical system?

Select one:

a. The electrical service equipment
b. The equipment grounding conductor
c. The grounding electrode conductor
d. The grounding electrode system

A

D.The grounding electrode system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
Chapters 1 through 4 of the NEC apply   ?  .
Select one:
a. generally 
b. only to special conditions 
c. only to special equipment 
d. only to special occupancies
A

A.Generally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Chapters 5, 6, and 7 often modify or amend the general requirements in NEC chapters 1 through 7.

True or False

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Chapter 8 in the NEC is independent of the other articles, and none of the rules in the rest of the NEC applies to communications systems.

True or False

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which of the following has the responsibility for approval of electrical installations and systems and interpreting NEC rules?

Select one:

a. The authority having jurisdiction (AHJ)
b. The electrical contractor
c. The engineer
d. The property owner

A

A. The AHJ

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Informational notes in the NEC are applicable as rules and must be applied to the rule they follow.
Select one:
True
False

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Exceptions to NEC rules apply only to the rule they follow, unless it is stated differently in the exception.

True
False

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
Article 100 of the NEC contains defined terms used in two or more articles, and Section   ?   of an article often contains defined terms contained only within that article.
Select one:
a. XXX.1 
b. XXX.2 
c. XXX.3 
d. XXX.10
A

B.XXX.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
A(n)   ?   is defined as a reliable conductor that ensures continuity and conductivity between metal parts required to be electrically connected.
Select one:
a. bonding conductor or jumper 
b. equipment grounding conductor 
c. grounded conductor 
d. system bonding jumper
A

a. bonding conductor or jumper

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

A main bonding jumper is the connection between the grounded conductor and the equipment grounding conductor and is located at a separately derived system.

Select one:
True
False

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When grounding is accomplished through a resistor, an impedance device, or a surge arrester, the grounding is considered to be solid.

True
False

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
A grounded conductor of a system could be a   ?   conductor or a phase conductor.
Select one:
a. bonding 
b. grounding 
c. neutral 
d. zero sequence
A

C.Neutral

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which of the following functions are performed by an equipment grounding conductor (EGC)?

Select one:

a. Bonding
b. Effective ground-fault current path
c. Grounding of equipment
d. All of the above

A

D.all the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A supply side bonding jumper is required to be sized based on the overcurrent device protecting the circuit.

True
False

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q
?   of Article 250 specifically applies to grounding systems and circuits over 1,000 volts.
Select one:
a. Part I 
b. Part V 
c. Part IX 
d. Part X
A

D.Part X

17
Q

Notes to NEC tables are enforceable as Code requirements.

True
False

A

True

18
Q
What is the largest size aluminum grounding electrode conductor required by the NEC?
Select one:
a. 2/0 AWG 
b. 3/0 AWG 
c. 4/0 AWG 
d. 250 kcmil
A

D.250 Kcmil

19
Q
How many equipment grounding conductors are required to be installed with branch circuits serving patient care spaces?
Select one:
a. 1 
b. 2 
c. 3 
d. 4
A

B.2

20
Q
Equipment grounding conductors installed with medium-voltage cables are generally required to be sized based on Table 250.122 and never smaller than   ?   copper.
Select one:
a. 2 AWG 
b. 4 AWG 
c. 6 AWG 
d. 8 AWG
A

C.6awg

21
Q
What is the minimum-size copper equipment grounding conductor required for a 60-ampere branch circuit?
Select one:
a. 4 AWG 
b. 6 AWG 
c. 8 AWG 
d. 10 AWG
A

D.10 awg

22
Q
Which part of Article 250 applies specifically to grounding DC systems?
Select one:
a. I 
b. III 
c. V 
d. VIII
A

D.VIII

23
Q

Article 250 includes provisions that permit guards, isolation, or insulation as alternatives to grounding requirements.

True
False

A

True

24
Q
Which of the following does not contain mandatory requirements in the NEC?
Select one:
a. Annexes 
b. Chapter 1 
c. Chapter 2 
d. Introduction
A

A.Annexes

25
Q
According to the NEC Style Manual, if a term is used in more than two articles, it qualifies for inclusion in   ?  .
Select one:
a. Article 90 
b. Article 250 
c. Article 100 
d. Chapter 9 Tables
A

C.Article 100

26
Q

Requirements for installing AC grounding electrode conductors are provided in ? of Article 250.

a. Part I
b. Part III
c. Part IV
d. Part V

A

B.Part III

27
Q

The minimum-size bonding conductor for metal parts associated with neon sign installations shall not be less than ? .

a. the minimum size required for the branch-circuit equipment grounding conductor
b. 12 AWG copper
c. 14 AWG aluminum
d. 14 AWG copper

A

D.14 awg copper

28
Q
The minimum size required for a supply-side bonding jumper is provided in which of the following NEC tables?
Select one:
a. Figure 250.2 
b. Table 250.66 
c. Table 250.102(C)(1) 
d. Table 250.122
A

c. Table 250.102(C)(1)

29
Q

NEC Table 250.66 is used for sizing all of the following except ? .
Select one:
a. bonding jumpers for the grounding electrode system
b. grounding electrode conductor(s) for AC services
c. grounding electrode conductors for separately derived systems
d. wire-type main bonding jumper(s)

A

d. wire-type main bonding jumper(s)

30
Q
If a service is supplied with 300 kcmil copper ungrounded service conductors, what is the minimum size required for a wire-type supply-side bonding jumper?
Select :
a. 2 AWG aluminum 
b. 2 AWG copper 
c. 4 AWG copper 
d. 6 AWG copper
A

b. 2 AWG copper

31
Q
What part of Article 250 covers grounding electrode conductors?
Select one:
a. Part I 
b. Part II
c. Part III 
d. Part IV
A

c. Part III

32
Q

If a grounding and bonding word or term appears in more than two NEC articles, it qualifies for placement in ?

a. .2 section of Article 250
b. Annex A
c. Article 100
d. Article 250

A

c. Article 100

33
Q

Notes to NEC Tables are mandatory requirements.
Select one:
True
False

A

True

34
Q

Which NEC Table provides grounding electrode conductor (GEC) sizes for communications systems covered in Article 800?

a. Table 250.66
b. Table 250.102(C)(1)
c. Table 250.122
d. No table required for sizing a communications systems GEC

A

d. No table required for sizing a communications systems GEC

35
Q
A bonding conductor for a metal water piping system is sized using   ?  .
Select one:
a. Table 250.66 
b. Table 250.102(C)(1) 
c. Table 250.122 
d. Table 310.15(B)(16)
A

b. Table 250.102(C)(1)

36
Q

Chapters 1 through 7 of the NEC can be modified or amended by the provisions of Chapters 5 through 7.
Select one:
True Correct
False

A

True