Job Info - Lesson 7 Flashcards
Improper electrical terminations lead to high _____? connections which in turn lead to electrical system ______?
Resistance ; Failures
The first consideration in making good electrical connections is the type of conductor _____? invoved. The NEC recognizes copper, aluminum, and copper-clad aluminum, each of which has different ____? characteristics.
Material; Physical
If conductors of dissimilar ____? are to be used, the termination device shall be _____? for use with both types.
Materials; Identified
Splicing devices and _____? utilizing mechanical pressure are common in the electrical industry. Most commonly, screw-on wire _____? are used for splicing conductors.
Terminations; connectors
5) The split-bolt connector utilizes mechanical pressure to establish a splice that maintains excellent mechanical and _____? properties. This type of splicing device is commonly used when _____? one conductor from another.
Electrical; Tapping
6) Lugs are commonly used for both low-and medium-voltage applications. They are easy to use and are frequently found where power _____? conductors terminate in transformers and power ______?.
Distribution; Panelboards
7) One disadvantage with lugs is that the termination is subject to ______? that may impact the overall _____? of the termination. Vibration or heat cycling may result in a loose connection that raises the resistance of the connection, thus subjecting the termination to an increased______?
Influences; Reliability; Temperature rises
8) Compression connectors are also widely used within the electrical industry and can be utilized for both low-voltage and medium-voltage applications. The principle behind the compression connector is the application of _____? pressure, either ______? or by hand, to ensure the connection.
Irreversible ; Pneumatically
9)when the termination is a terminal block, care must be taken to ensure a good electrical connection without_____? the conductor. Terminals should not be used for more than one conductor, unless they are ____? for such use.
Damaging; Identified
10) If the splice is underground, the _____? shall be _____? for direct-burial use.
Device; Identified
11) Equipment, such as conductors, are _____? according to how much heat _____? can occur at the conductor termination.
Rated; rise
12) In general, equipment terminations for circuits rated 100 A or less or designed for f14 AWG through 1 AWG conductors are ____? for use on 60 degree C conductors. Conductors with a higher _____? insulation termination are allowed, Provided the conductor’s ampacity is selected from the _______? rating.
Rated; Electrical; Lowest temperature
13) Both the conductor and equpment temperature ____? shall be considered when designing or installing electrical systems. The ampacity of the conductor shall be selected so that the lowest temperature ____? of the conductor or any equipment in the circuit is never _____?
Rating; Rating; Exceeded
14) Prior to the advent of twist-on wire connectors, electrical connections were made by first _____? the electrical conductors together, then insulating the connection using electrical tape. The introduction of the twist-on wire connector revolutionized the electrical industy, offering electricians a(n)______? effective connector solution that provides a fast, reliable electrical connection.
Soldering; Cost
15) Connectors are generally color-coded. Color-coding offers the electrical installer an indication of fthe connector’s _____? wire range capability. It does not however, indicate an exact wire range and may vary according to _____?.
Approximate; Manufacturer