JJ2hydr Flashcards
When making correction on Grid map for private or non county hydrants use what color ink?
Green
What is a map depicting roads, hydrants, numbers and other landmarks either strip or grid?
Response Map
Who shall conduct inspections or test of new hydrants
Regional Fire Prevention or Special Units
- Hydrant is ____ behind curb line
12”-24”
- Center of lowest outlet is ___ above the curb
14” -24”
____degrees to the curb for single hydrant
90
____degrees to the curb for double hydrant
45
___ coats of ___primer one ____traffic signal paint
Two; red
One; Yellow
What should be used to note repairs or obstructions to hydrants
Form 410
A Damaged Fire Hydrant Notification Form 21 should be filled out for all hydrants except?
Private
When cul-de-sac depth exceeds what for commercial and residential mid block hydrants are required?
200’ commercial and 450’ residential
The available flow of hydrant is calculated by?
Testing the static pressure and residual pressure of the hydrant
The FDC shall be installed on the address side of the structure with vehicular access and how far from a
hydrant?
150’
Fire hydrant spacing for single family dwellings?
600’
Hydrant spacing for single family dwellings with more than 1 home per acre hydrant spacing will be?
450’
Non urban properties no part of the structure will be more than what from a hydrant?
750’
All occupancies other than single family dwelling shall be no less than?
300’ from a hydrant
What buildings qualify for the maximum spacing of hydrants of 600’?
Sprinklered
For non sprinklered buildings hydrant distance should be?
400’
All hydrants shall flow what gpm at what psi for how long?
1250 gpms at 20 psi for 2 hours
If there is more than 1 on site hydrant the only difference is there shall be
2500 gpms
All hydrants shall be installed how far from a building?
25’ or have a 2 hour fire wall
When the required fire flow exceeds what does a wharf hydrant need to be replaced with 4” x 2”?
1250gpm
Unless the required fire flow is less the minimum flow from a hydrant shall be?
1000 gpm
No walls, barricades, fences, landscaping etc. shall be placed within?
3’ of hydrants
- All on-site hydrants must have a shut-off valve located?
Minimum of 10’ maximum of 25’
What color are on site hydrants painted?
Red