“Fire door keep locked” is the sign for a small, locked cleaner’s cupboard. On which side of the door must it be fixed?
Outside
Is this statement true or false? Minor amendments can be made to a door closer’s fixing position without invalidating its performance and fire test evidence.
False
Why would a door closer slam a door closed?
The closer has lost its hydraulic fluid
The hydraulic valves have not been adjusted
What’s the maximum delay allowed in BS EN 1154 (from fully open to fully closed) on a delayed action closer fitted to a fire door?
25 seconds
Is the following statement true or false? A mortice lock on a 1 hour fire door will need an intumescent gasket, but this is not necessary on a ½ hour door.
True
A cylinder rim nightlatch and its box strike are surface fixed, so they don’t need any intumescent protection. Is this always true?
False
In what circumstances can you fix a letterplate to a fire door?
If there’s fire test evidence for it
Floating spindles are not…..
fixed to the operating furniture
What are the benefits to bolt-through fixings?
More durable in daily use
What is required to hold a fire door closed?
All fire doors need either a closer or a lock to hold them closed
Under what circumstances might a surface fixed item pose a risk to a fire door?
If it has bolt-through fixings
If it wraps around the edge of the door
What might stop a latch on a fire escape door from closing on its strike?
Door dropped
Door/frame gap too tight
Strike tongue not angled
Is the following statement true or false? All fire doors need a latch to hold them closed.
False
What’s the name of the document which gives detailed guidance on door hardware for fire and escape doors?
Code of Practice: Hardware for fire and escape doors
Is this statement true or false? If a door is installed as a fire door, then the position of the hinges must be the same as when it was fire tested.
True