Interpret CEC Rules and Regulations Concerning HV Control and Protective Equipment Flashcards
According to CEC regulations, what safety feature must compartments containing HV fuses have?
Interlocking
When used indoors, HV fuses must be in an acceptable enclosure or in a room of what type of construction?
Non-combustible
What are three pieces of HV equipment that frequently use HV fuses?
- Transformers
- Capacitors
- Motors
Spacing between fuses must increase with fuse _______ rating
Voltage
When used for the protection of VT’s, the current rating of a fuse must not exceed _____ A
3
Which table in the CEC provides information on the rating of HV fuses for transformers?
Table 50
Which table in the CEC provides information as to minimum spacing distances between HV fuses assembled in the field?
Table 35
With what type of HV switch are current-limiting fuses commonly used?
Load-break
What is the purpose of fuse interlocking?
To prevent someone entering a fused cubicle compartment that is live
Is there a difference between the spacing requirements of expulsion and non-expulsion fuses?
Yes. For any given voltage, more spacing is required between the expulsion types than between the non-expulsion types