Interpret CEC Rules and Regulations Concerning HV Installations Flashcards
What are three different locations where it is necessary to place a “DANGER - HIGH VOLTAGE” warning?
- On all HV conduits and cables at points of access to conductors
- On all cable trays containing HV conductors
- On exposed portions of all HV cables
- At electrical equipment vaults (rooms, areas or enclosures)
See CEC Rule 36-006
Which table in the CEC lists the radii of bends for HV cables?
Table 15. CEC Rule 36-102
What is the minimum vertical ground clearance for 15kV open-line conductors?
6.1m. See Table 34
Is it permissible to install HV cables in elevator shafts?
No. See CEC Rule 36-116
Which table in the CEC lists the minimum size of bare copper conductor for grounding purposes in HV installations?
Table 51. See CEC Rule 36-300
Under a fault condition, the maximum voltage rise on all parts of the station ground grid should not exceed _____
5000V. See CEC Rule 36-304
Which table in the CEC lists the maximum tolerable touch and step voltages for HV installations?
Table 52