Interpret CEC Rules and Regulations Concerning HV Installations Flashcards

1
Q

What are three different locations where it is necessary to place a “DANGER - HIGH VOLTAGE” warning?

A
  • On all HV conduits and cables at points of access to conductors
  • On all cable trays containing HV conductors
  • On exposed portions of all HV cables
  • At electrical equipment vaults (rooms, areas or enclosures)

See CEC Rule 36-006

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Which table in the CEC lists the radii of bends for HV cables?

A

Table 15. CEC Rule 36-102

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the minimum vertical ground clearance for 15kV open-line conductors?

A

6.1m. See Table 34

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Is it permissible to install HV cables in elevator shafts?

A

No. See CEC Rule 36-116

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Which table in the CEC lists the minimum size of bare copper conductor for grounding purposes in HV installations?

A

Table 51. See CEC Rule 36-300

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Under a fault condition, the maximum voltage rise on all parts of the station ground grid should not exceed _____

A

5000V. See CEC Rule 36-304

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which table in the CEC lists the maximum tolerable touch and step voltages for HV installations?

A

Table 52

How well did you know this?
1
Not at all
2
3
4
5
Perfectly