Heat Pump 2 Flashcards
During the heating cycle, the outdoor coil is use as;
The evaporator.
During the cooling cycle, the indoor coil becomes;
The evaporator.
During the defrost cycle, the outdoor fan is usually;
Turned off.
Heat pump systems which use a thermostatic expansion valve at each coil will also have;
A by-pass lines with check valves.
Refrigerant flow through the compressor;
is always the same regardless of operating mode.
Because of the possibility of liquid flood-back, a heat pump that uses a reciprocating compressor should be equipped with a;
Suction Accumulator.
A scroll type compressor;
is less susceptible to damage from liquid flood-back.
On a split system heat pump. A “no heat/no cooling” service call, you turn the thermostat to the fan on/ cont position and the indoor fan operates. This action verifies that;
The transformer is functioning.
On most air-to-air heat pumps;
The indoor and outdoor coils are the same size and physical capacity.
A heat pump system, operating at 45°F ambient, may be _______ efficient than electric resistance heat
3 to 4 times more.
Since electric resistance heat produces 1 watt of usable heat for each watt of energy purchased, electric resistance heat has a COP of;
1:1
As outdoor ambient air temperature decreases, a heat pump’s COP;
Decreases.
During the defrost cycle, the system switches to the ___________ Mode.
Cooling.
During the heating mode, the refrigerant in the indoor coil is under;
High pressure.
What three things happen in most air-to-air heat pump during defrost?
The reversing valve must switch to cooling mode, the outdoor fan shuts off and auxiliary heat is energized.
High suction pressure and low discharge pressure on a heat pump system operating in either the heating or cooling mode can be an indication of;
Compressor inefficiency.
The preferred method to preform adjustments to the refrigerant charge in a heat pump system is in the ________ more.
Cooling.
You answer a service call for insufficient heat. You find the suction pressure is higher and discharge pressure is lower than normal. Using a digital thermometer, you measure the line entering the reversing valve from the compressor discharge and find 215°F. You then measure the line leaving the reversing valve that connects to the indoor coil and find 185°F. These readings are an indication of;
A faulty reversing valve.
The customer complaint is not enough heat. You install service gauges and find the low side pressure is higher than normal and the high side pressure is lower than normal. You switch to the cooling mode and find the pressures are normal. The most likely cause of the problem is;
A stuck open check valve at the outdoor coil.
A customer complains that their heat pump systems blows cool air periodically during the heat mode. This could be caused by;
A faulty defrost relay (does not energized the aux. heat during the defrost mode.)