General Questions Flashcards

1
Q

Dwelling services are sized at what %

A

83%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Non-coincidental loads are sized at what percent of highest load

A

125%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Feeders less than or equal to 100 amps use what column

A

60 degree C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Capacitors are rated for what percent of total amps

A

135%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How many feet of show window requires it’s own recept

A

12 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How many feet above sidewalk must service entrances conductors be

A

10 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the minimum disconnect size for a commercial building

A

60 amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What size grounding electrode conductor must be protected from physical damage

A

6 or smaller

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Minimum ground rod diameter

A

5/8”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Minimum ground rod spacing

A

6’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Minimum ground ring wire size

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When sizing a disconnect, you must round down if the amperage is below

A

800 amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Elementary schools require what type of recept

A

Tamper Proof

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Car wash recepts are what type of location

A

Wet location

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Minimum light pole hand hole size

A

2”x4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

General use snap switches at good for what percent of its rated use?

A

80%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the maximum surface temperature of T2A

A

536 degrees

18
Q

In hospital general care areas, each bed location needs how many recepts

A

8

19
Q

In hospital critical care areas, each bed location needs how many recepts

A

14

20
Q

How many inches must separate class 1 and class 2/3 circuits

A

2 in

21
Q

What is the smallest size conductor that can be run in parallel

A

1/0

22
Q

Wire for services is sized using what temp column

A

75 deg C

23
Q

What percent of FLA must motor conductors be sized for?

A

125%

24
Q

What percent of motor FLA must a disconnect be sized for?

A

115%

25
Q

For taps between 10’ and 25’, each motor feed must be able to carry what percent of the load

A

1/3

26
Q

How many watts per HP

A

746

27
Q

How big is a straight through junction box

A

Largest Pipe size x 8

28
Q

How big is a angle pull junction box?

A

Largest pipe x 6 + all other pipes

29
Q

What is the voltage drop formula to find circ mils

A

(2KIL)/((VD%)(v))

30
Q

What do you multiply voltage by for all 3 phase equations

A

Square root of 3

31
Q

How do you find single phase neutral amps

A

Amp difference between 2 legs

32
Q

How do you find 3 phase neutral amps

A

Total amps / 2

33
Q

Motor overcurrent protection table

A

430.52

34
Q

How far under waterline must a wet niche fixture be?

A

18”

35
Q

Conduit to wet niche fixtures must be corrosion resistant and made of

A

Rigid brass

36
Q

Electrical wires going over a pool must be how high

A

22.5’

37
Q

Fixed metal parts within 5’ of pool must be

A

Bonded

38
Q

Minimum distance from the edge of stud to a cable in wall

A

1 1/4”

39
Q

At what voltage does direct burial cable have to be shielded

A

2000 volts

40
Q

Minimum space between recessed light fixture and insulation

A

3 in

41
Q

Conductors supplying several motors shah be rated for

A

The sum of all motors plus 25% of largest

42
Q

You must use mc or conduit if occupancy is over

A

100 people