General Flashcards
What are the initial checks undertaken when traction power cannot be obtained?
Trips, Switches, Gauges and Cocks
TRIPS
-trip is lowered and set
SWITCHES
-Switches are in their normal position
-Circuit breakers are in normal position
-Door closed button is activated
GAUGES
-Main res pressure within tolerance (585-725)
-Brake pipe air pressure within tolerance 550 (above 425)
-Control reservoir pressure within tolerance (above 490)
COCKS
-BVICS is open
-Red EC and Yellow TECHAV are in normal position
Ensure 110vDC by:
-LP flag is lowered, EP brake operational
-Bell operates
What does the ROBBDS test stand for?
R- Reverser
O- traction Overload reset
B- Brake pipe reduction
B- control governor Bypass
D- Door loop bypass
S- Second controller
Step 1 in ROBBDS test?
REVERSE
Check if train powers in reverse
If it does, it indicates a faulty reverser
Step 2 in ROBBDS test?
OVERLOAD RESET BUTTON
Press the Traction Overload Reset button
Will reset any overloaded or resettable equipment
If train powers, proceed and submit a TMM
Step 3 in ROBBDS test?
BRAKE PIPE REDUCTION
-Make a brake pipe reduction below 325 to open control gov
-Restore brake pipe to above 430 to close control gov
Try for power
If train powers, the control governor was faulty (debris most likely)
Proceed and book TMM
Step 4 in ROBBDS test?
CONTROL GOVERNOR BYPASS BUTTON
-Turn Red EC
-Set foot pilot valve and press control gov bypass button
If train powers, something on primary safety circuit was faulty
Step 5 in ROBBDS test?
DOOR LOOP BYPASS
-Isolate Door Loop Bypass switch and try for power
If power is obtained, fault is in traction inhibit system
Submit TMM and DETRAIN passengers at next opportunity
Step 6 in ROBBDS test?
SECOND CONTROLLER
-Try for power at rear cab
If train powers, can be powered from rear with competent employee
Or return to rear
If traction cannot be obtained, declare train disabled
What is a Local fault light usually to do with?
An overload
What is the Line Switch fault light usually to do with?
The Traction motors
What does a This Car illuminate light indicate?
-That one of the fault lights illuminated is for this motor car
-Park brakes are applied
What does the Control Reservoir do?
Gives traction power
What is the pressure of the Control Reservoir?
490kPa (+-20)
What is the result of a rupture in the Control Reservoir, or the relevant isolating cocks being isolated?
The switches will remain open and traction power will be unavailable on that car
If the Control Reservoir is ruptured or isolated, what must be done to gain traction power?
(Line switch fault light)
The Traction motor Cut out switch must be put to ‘All out’ and a TMM submitted
The Rheo brake on that car will then need to be isolated to resolve a ‘Rheo’ fault light (caused by the isolated traction motors)
If Traction motors are isolated (either all out, 1&2 or 3&4) what must be done after isolating them?
Press the Overload reset button before testing for power
Can a drive reinstate the Main Isolation Switch at any time?
No
If overhead is lost, what must be done?
-Stop train safely
-Check train is not derailed (if it is, check for fouled lines)
-Contact Train controller
-Secure the train
What is powered directly by 1500v DC?
-Pantographs
-Motor Alternators
-Compressors
-Traction equipment
-Associated circuits
When a loss of overhead occurs, how many times will the overhead system try to reset itself?
Twice
What happens to the doors if overhead power is lost?
They will release
If overhead power is lost and unable to be restored, metrol will make a group call instructing drivers to lower pantographs
What must a driver do?
-Observe the rear of the train confirming the trailing pantographs have lowered (lowered by LSM)
-Press the Local MA EP stop valve
-Press the Local Pantograph EP Stop valve
If overhead is lost, all trains have lowered their pantographs, and then power is restored, how will the train controller instruct drivers?
TC will deal with one train at a time, and depart them at one minute intervals
If a train fails and communication is unavailable, should the drive immediately assume a loss of overhead has occurred?
No, follow fault finding procedures
(Trip, Switches, Gauges, Cocks)
What things tell a driver that 110v DC is present?
-Bell is operational
-Low pressure flag is down
-EP brake is operational
How does a driver check for the presence of 240v AC power?
-Illumination of non-emergency saloon lights
-Illumination of the van area cab light
-Operation of the headlights
If overhead power has been restored, but no communication is available, what are the wait times before applying traction?
How must the train be driven?
UP train- 30 seconds
DOWN train- 60 seconds
Drive in SERIES until the next station, then resume normal operation
Contact Train controller at earliest opportunity
If overhead power is lost and there is a suspicion of a disarranged overhead, what must be done?
-Do NOT exit the cab
-Make regular PA announcements to keep passengers on the train
If 1500v is lost and the Emergency lights turn on, how long will they run for before they need to be reset?
How are they reset?
Run for 2 hours
Battery charger light will flash to indicate a reset is required
To reset, turn marker light toggle switch from auto to any other position, and then back to auto
How long will the PA remain operational if overhead power is lost?
How it is reset?
Up to two hours
Will reset with the emergency lighting
What is the purpose of the LSM?
(Loss of Overhead Shutdown Module)
What does it do?
To reduce the impact of 1500v DC defects from overloading the substation when power is returned
It will switch off certain circuits to prevent overloading the substation
What is the LSM Speed Threshold?
Set to 8km
LSM will take defined actions if the speed is under or over 8km
If overhead power is lost and the 110v DC output drops to 95v DC for 2 continuous seconds, while the BVICS is open and train is travelling above 8km, what will happen?
The LSM will operate
EP circuit breaker will trip (flag will rise)
Motor alternator will shutdown, but the contractor will remain set to ON
When the BVICS are closed on trailing motors, the train is stationary or moving under 8km, timers are at zero, what will the LSM do?
-Leading pantograph will be raised
-Trailing pantographs will be lowered
-Leading motor alternator contractor will be ON
-Trailing MA contractors will be OFF
If overhead is lost, what is the timer set to for the VICERS?
What will happen when it expires?
5 minutes
VICERS Activation Valve will open, all Brake Pipe air will exhaust to atmosphere
If overhead power is restored when all trains have lowered pantographs, how does the train controller determine which train if defective and caused it?
Works with the trains one by one
Each driver to raise all pantographs and start all MA’s
When power is lost again, the defective train is identified
Once a certain motor car has been determined as the reason for an overhead outage, how is the 1500v DC equipment on that car isolated?
-Lower the local pantograph using the local EP valve
-Isolate the pantograph electrically and pneumatically (elec= toggle switch, pneu=van cock)
-Turn the motor cut-out switch to ‘All out’
Do trains cause substations to short?
Yes
What does a LOCAL fault light indicate?
An overload has tripped on a motor car
What does a LOCAL fault light together with a THIS CAR fault light indicate?
An overload has tripped on this motor car
What kind of fault is a LINE SWITCH fault light usually associated with?
A fault related to the traction motors
A line breaker has failed to close
What does a RHEO BRAKE fault light indicate?
A rheostatic brake has failed to set up correctly on a motor car
What does a AIR COND fault light and a THIS CAR fault light indicate together?
An air conditioning fault on that motor car
What does a steady AIR COND light indicate?
No more than one air conditioner has failed on any one car
What does a flashing AIR COND fault light indicate?
At least one car has BOTH the air conditioners inoperative
What does a WHEEL SLIP fault light indicate while stationary?
There is a fault in the wheel slip unit and its associated equipment
What does an illuminated WHEELSLIP light indicate when the train is in motion?
A difference in speed of greater than 15km between axles on one motor car or trailer car during powering or braking
What equipment does the CONTROL circuit breaker supply 110v DC current to?
(So they can operate)
-Master controller and Reverser
-Traction equipment reset button
-Remote pantograph raise and lower buttons
-Electric brake demand circuit (Rheo)
Will a train fail if the CONTROL circuit breaker on the leading motor trips?
Yes
When the CONTROL circuit breaker trips, what must be done?
Why?
The cause of the fault must be determined and isolated
The operation of the master controller will be effected, and the train cannot be driven from the leading motor
If the CONTROL circuit breaker trips after using the Remote Panto Raise button, what will the drive have to do?
-Raise the pantographs manually on each motor car using the Local Panto EP button
-Send a TMM
If the CONTROL circuit breaker trips after using the Remote Panto Lower button, what will the drive have to do?
-Reset the CONTROL circuit breaker
-Electrically isolated the pantograph EP valve with the switch
-Press the remote pantograph lower button
This determines if the fault is with the EP valve
Can a train enter or remain in service if the pantographs cannot be lowered electrically from the leading motor?
No
If the CONTROL circuit breaker trips after using the Traction Equipment Reset button, what will the drive have to do?
-Identify the defective motor by using the THIS CAR fault light
-Isolate the traction equipment by placing the motor cut-out switch to ALL OUT
-Complete a TMM
If the CONTROL circuit breaker trips with the Master controller closed (haven’t touched anything) what is the probable cause?
A short circuit exists between the CONTROL circuit breaker and the master controller
With the master controller closed and the reverser in off, is there any current flowing from the master controller to the train cable, traction equipment, or rheo brake demand circuit?
No
If the CONTROL circuit breaker trips with the reverser in Forward, Neutral or Reverse, what are the probable causes?
-Short circuit on the electric brake demand wire in the train cable
-A fault in the rheostatic brake control equipment on any motor car
If the CONTROL circuit breaker trips, with the reverser in Forward, Neutral or Reverse, why could the fault be in either the train cable or rheostatic brake control equipment?
Because the rheostatic brake demand current is sent via the train cable to the rheostatic brake control equipment on every motor car
Can the CONTROL circuit breaker trip due to a short circuit on the rheostatic brake circuit when the train is stationary?
Yes, even though the rheostatic brake is not working while stationary, the circuits are energised ready on every motor car via the train cable
(If reverser in FWD, NEU, REV)